16
| Operation
Example 6: Alarm configuration
Configuration > Alarms
2020–09–23
Alarm delay at start up
60 s
Search alarm no:
53
Filter alarm supply air
>
Air and temperature control
>
Extra functions
>
Extra sensors and alarms
>
Fire/Smoke
>
Component malfunction
>
Manual operation and warnings
>
Configuration > ... > Filter alarm supply air
2020–09–23
Action:
No action
Level:
Class B
Delay:
300 s
Limit X1:
0 m
3
/h
Limit Y1:
10 Pa
No:
53
Limit X2:
2000 m
3
/h
Limit Y2:
150 Pa
Name:
Filter alarm supply air
Original name:
Filter alarm supply air
6.1.6
System information
Shows information about the air handling unit, installation site, control unit, communication and the
Pacific Ventilation product. To enter information, such as site specific unit name or server partner’s
contact information, go to
System information setup
with user level
Service
.
Example 7: System information
System information
2020–09–23
Unit information
Installation address
Service partner
Communication
Access Control Unit
Pacific Ventilation product
System information setup
>
214959 | A002