Signals test
1. Enable the 5345/5445 (connect input pin 5 to pin 6 on J7).
2. Verify that the motor has holding torque by attempting to
rotate the motor shaft. The energized motor shaft is either
immovable or very resistant to rotation when the 5345/5445
is enabled.
3. Jog the motor (connect input pin 7 to pin 9 on J5 ). The
motor moves at the default jog speed.
4. Remove the jog input.
5. From the terminal or computer, type GO.VEL <enter>. This
moves the motor at the default run speed.
6. Type DIR = 1 <enter>. This changes the default direction
(if DIR = 0 was the initial setting).
Repeat Step 5. The motor should run in the reverse direction.
7. Continue exercising the unit, testing it in your application.
Getting help
If you need further help with your installation, contact Pacific
Scientific at 978-988-9800 from 8 a.m. to 5 p.m. Eastern