Pacific energy VISTA D SERIES Скачать руководство пользователя страница 3

34 3/4”
883mm 

15”

381mm

9”

229mm

9”

229mm

8”

203mm

16”

406mm

Clearances

Masonry or Factory Built Fireplace

The minimum required clearances to surrounding  combustible 

 replace 

are listed below and in Fig. #1.

Minimum Clearances to Combustibles

(Measured From Insert Body)

Adjacent Sidewall ........................... 9 in. (229 mm.)
Mantel ........................................... 15 in. (381 mm.)
 

Top Facing .............................. 15 in. (381 mm.)

 

Side Facing ............................... 9 in. (229 mm.)

Mantel or Top Facing

Side F

acing

Hearth

Adjacent 

Wall

Fig. # 1

  36 1/2"

927mm

 

   *42"

[1.07m]

 

26"

661mm

 

*30"

[762mm]

  19 1/2"

495mm

 

  2 3/8"

59mm

 

 

6 5/8"

170mm

 

  19 3/4"

501mm

 

  14 1/2"

368mm

 

 

6 1/8"

157mm

 

  20 5/8"

525mm

 

 

9 3/4"

249mm

 

  23 1/4"

591mm

 

  20 1/4"

514mm

 

  22 1/2"

571mm

 

 

Safety

READ  ALL  INSTRUCTIONS  BEFORE  INSTALLING 

AND USING THIS APPLIANCE. FAILURE TO FOLLOW 

INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, 

BODILY INJURY, OR EVEN DEATH.

We strongly recommend that smoke detectors be installed. 

If smoke detectors have been previously installed, you may 

notice that they are operating more frequently. This may be 

due to curing of stove paint or fumes caused by accidentally 

If necessary, relocate them to reduce their sensitivity.

SAFETY  NOTICE:  If  this  stove  is  not  properly  installed,  a 

tions and installation inspection requirements in your area.

 ed by the Wood 

Energy  Technical  program  (WETT)  -  in  Canada,  Hearth 

Education Foundation (HEARTH) - in U.S.A. (or equivalent) 

are strongly recommended.

Dimensions

*Oversized Surround

20

051

6

-2

0

 

         

VISTA 

INSERT-D 

                     3

Содержание VISTA D SERIES

Страница 1: ...may result For your safety follow the installation instructions Contact local building or fire officials about restrictions and installation inspection requirements in you area IMPORTANT THESE INSTRU...

Страница 2: ...Label 19 PLEASE SAVE THESE INSTRUCTIONS This manual describes the installation and operation of the Pacific Energy VISTA INSERT wood heater This heater meets the 2015 U S Environmental Protection Agen...

Страница 3: ...22 1 2 571mm Safety READ ALL INSTRUCTIONS BEFORE INSTALLING AND USING THIS APPLIANCE FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH We strongly recommend tha...

Страница 4: ...System Top baffle board blanket Baffle Top heat shield and mounting bolt Baffle Gasket Brick Rails Manifold Blower The blower should be cleaned out a minimum every six months by using a vacumn on the...

Страница 5: ...insert must be protected from hot embers by non combustible material ex tending 16 406mm USA and 18 457mm CANADA to the firing side and 8 203mm to other sides of the unit Consult CAN CSA B365 Installa...

Страница 6: ...r other obstructions especially if it has not been in use for some time Theexistingfireplacedamperistobelockedopenorremoved completely WARNING Do not remove bricks or mortar from your existing firepla...

Страница 7: ...ert Note Forbetteraccess thetopofthecasingmayberemoved Fig 6 If it is necessary to get access to the connector pipe through the flue outlet of the Insert the baffle can be removed see Baffle Removal s...

Страница 8: ...3 Center assembled surround on the firebox and slide gently into position Fig 10 Be careful to align notches in surround with top Engage the mounting brackets over the mounting screws in the casing s...

Страница 9: ...l Code and in the USA with the National Electrical Code ANSI NFPA 70 lat est edition Combustion Air Consult local building codes regarding combustion air sup ply Intake or combustion air can be suppli...

Страница 10: ...Close door 5 Begin normal operation after a good coal base exists and wood has charred Curing of the Paint Finish When burning your stove for the first 2 3 times it is very im portant that the room be...

Страница 11: ...Energy Technical Training program WETT in Canada HearthEducationFoundation HEARTH inU S A are strongly recommended Over Firing Over firing can be caused by operating the unit with the door open damag...

Страница 12: ...nite chimney fires Thesearehotfires suchaswhenburninghousehold trash cardboard Christmas tree limbs or even ordinary fuel wood eg with a full load on a hot bed of coals and with the air inlet wide ope...

Страница 13: ...estricted check flue Provide outside air for combustion Glass is Dirty 1 See 1 2 and 3 above 2 Door Gasket leakage Replace gasket Check latch Low Heat Output 1 Wood is wet Use dry wood 2 Fire too smal...

Страница 14: ...heater in the upright position install firebricks as follows First install 4 firebricks against the rear wall Next install the side firebricks 2 each side Lastly place 4 firebricks on the bottom of t...

Страница 15: ...s required 5096 99 Firebrick Set BRIC VISTA 12 Brick Rail Set VIST RAILSET 15 Baffle VIST BAFKIT 16 Flame Shield c w Bolt and Nut VINC 2305 17 Baffle Gasket SSER 1395 18 Door Catch c w Bolt WODC 1461...

Страница 16: ...nap Disc Switch Wire VINC 5032 7 Snap Disc Switch 5027 2 All parts may be ordered from your nearest Pacific Energy dealer Contact Pacific Energy for the location of the dealer nearest you 8 Rocker Swi...

Страница 17: ...with the appliance Attach hearth trim to the bottom of the surround with clips provided The clips are installed up through the trim and into the surround This kit contains 1 Hearth Trim 4 Spring Clips...

Страница 18: ...y part that shows in our judgment evidence of defect shall be repaired replaced or refunded at Pacific Energy s option The defective part may be required to be returned to Pacific Energy or an accredi...

Страница 19: ...ID WOOD FUEL FIREPLACE INSERT APPAREIL DU TYPE INSERTION DE COMBUSTIBLE SOLIDE DE CHEMIN E CERTIFIED FOR USE IN CANADA AND U S A CERTIFIE AU CANADA ET AUX ETATS UNIS TESTED TO PROUV SELON ULCS628 93 U...

Страница 20: ...hone 1 250 748 1184 Web site http www pacificenergy net 2975 Allenby Rd Duncan B C V9L 6V8 PACIFIC ENERGY FIREPLACE PRODUCTS LTD Phone 1 250 748 1184 Web site http www pacificenergy net 2975 Allenby R...

Отзывы: