Installation

Warning: 

Under no circumstances is this heater to be 

installed in a makeshift or "temporary" manner. It may be 
fi red only after the following conditions have been met.

*   DO NOT ATTEMPT TO CONNECT THIS HEATER 

TO ANY AIR DISTRIBUTION DUCT.

*   The services of competent installer are strongly rec-

ommended.

*   Outside combustion air or fresh air into the room may 

be required in your area, consult local building codes 
(see Combustion Air section).

- The services of a competent or certifi ed installer, (certifi ed 
by the Wood Energy Technical Training program (WETT) 
- in Canada, Hearth Education Foundation (HEARTH) - in 
U.S.A.,) are strongly recommended.

BOTH CHIMNEY SYSTEM AND CONNECTOR MUST 
BE LISTED TO: IN CANADA -  ULC S-641 LISTED CON-

IN CANADA -  ULC S-641 LISTED CON-

NECTOR AND ULC-S-629 LISTED CHIMNEY, 

NECTOR AND ULC-S-629 LISTED CHIMNEY, 

IN USA 

IN USA 

-  UL-103 HT LISTED CONNECTOR AND CHIMNEY

-  UL-103 HT LISTED CONNECTOR AND CHIMNEY

Clearances

1.  This heater may be installed using a single-wall con-

nector (smoke pipe) or listed double-wall connector 
(see Mobile Home installation).

2.  Clearances to combustible surfaces and materials 

using single-wall connector are shown in Figure #1, 
page 6.

 

Clearances may be reduced with various heat insulat-
ing materials. Consult local fi re codes and authorities 
for approval.

3.  Alternately, for close clearances, use a listed double-

wall connector.  See Diagram #1, page 6.

Chimney and Connector

Connect to a listed chimney or a chimney suitable for use 
with solid  fuel that is lined and in good condition and 
meets local building codes. The chimney fl ue size should 
be the same as the stove outlet for optimal performance. 
Reducing or increasing the fl ue size may adversely affect 
stove performance. Chimney fl ue exit is to be 3 feet (1 m.) 
above roof and two feet (0.6 m.) above highest projection 
within 10 feet (3 m.). The installation must meet all local 
codes. Do not connect this unit to a chimney fl ue serving 
another appliance. Minimum system height is 15 feet (4.6 
m.) (measured from base of appliance).

Double-Wall Connector

Use a listed double-wall connector.

-  Install all components to the chimney connector 

manufacturer's installation requirements.

Single-Wall Connector

Smoke pipe must be:
*   as short and straight as possible, use six inch diam-

eter, 24 gauge black pipe that is clean and in new 
condition.

*   secured at every joint and collar with 3 sheet metal 

screws.

*    installed with the crimped or male ends pointing down.  

This will carry any liquid creosote or condensation 
back into the stove.

*    The chimney connector shall not pass through an attic, 

roof space, closet or similar concealed space, fl oor, 
or ceiling.  Where passage through a wall, or partition 
of combustible material is desired, the installation 
shall conform to CAN/CSA-B365, Installation Code 
for Solid-Fuel-Burning Appliances and Equipment.

Procedure

1.  If a listed chimney and double-wall connector is to 

be connected to the stove, install all components to 
the chimney manufacturer's installation requirements.  
(Outside combustion air may  be required, consult 
local building codes.  See Combustion Air section.)

2.  If it is desirable to use smoke pipe in conjunction with 

the insulated chimney, see step 4.

3.  If a roof or ceiling support is used in the installation, 

you will fi nd the chimney manufacturer's complete 
instructions packed with the roof support.

4.  To start installing smoke pipe (chimney connector), 

slip crimped edge of the pipe inside the stove collar.  
Use holes provided in collar to secure pipe with two 
screws.

5.  Install the remaining lengths of pipe one on top of the 

other to the fi nished height of the chimney connector 
and secure to each other.

Содержание SUPER 27

Страница 1: ...tioninstructions Contact local building or fire officials about restrictions and installation inspection requirements in your area TESTED and LISTED to CAN ULC S627 AND UL 1482 Meets the Environmental...

Страница 2: ...ntenance 3 Maintenance Checks 4 Creosote 5 Formation and Need for Removal 5 Chimney Fires 5 In Case of a Chimney Fire 5 Avoiding a Chimney Fire 5 Assembly 6 Crate Removal 6 Optional Ash Cleanout Syste...

Страница 3: ...maintained in good condition Periodically inspect seals and replace if necessary Follow instructions included in the DR31 WDGKIT kit obtainable from your nearest Pacific Energy dealer 5 DOORGLASS Dono...

Страница 4: ...he Chimney System Top baffle board blanket Baffle Top heat shield and mounting bolt Baffle Gasket Brick Rails Manifold Blower The blower should be cleaned out a minimum every six months by using a vac...

Страница 5: ...t be lived with Regular inspection and clean ing is the solution The use of dry seasoned wood and ample combustion air will help to minimize the buildup Chimney Fires The result of excessive creosote...

Страница 6: ...to bottom pallet 4 Place stove body carefully on its back 5 Using two 3 4 wrench remove 1 x 1 2 bolts and save for later use 6 Remove pallet retaining brackets from stove bottom Optional Ash Cleanout...

Страница 7: ...o flooring using two 1 4 x 2 or longer lag screws Mobile Home Installation Warning Under no circumstances is this heater to be installed in a makeshift or temporary manner It may be fired only after t...

Страница 8: ...Minimum 7 2 1m Ceiling Height Attachment to floor for mobile homes Non combustible floor protector 48 1219 mm 3 914 mm Minimum Hooded vent or 90 elbow turned The chimney may incor porate an offset To...

Страница 9: ...ve performance Chimney flue exit is to be 3 feet 1 m above roof and two feet 0 6 m above highest projection within 10 feet 3 m The installation must meet all local codes Do not connect this unit to a...

Страница 10: ...llation requires the unit to be secured to the structure to prevent dislodging of the air duct To draw outside air from behind the stove an outside air adaptor may be required see Optional Blower sect...

Страница 11: ...for the first 2 3 times it is very important that the room be well ventilated Open all windows and doors Smoke and fumes caused by the curing process may cause discomfort to some individuals Lighting...

Страница 12: ...ry replace with gasket 139 5availablefromyourPacificEnergydealer Re install baffle assembly in reverse order The two side pieces of insulation must be tight against the siderails Restarting After Exte...

Страница 13: ...ill al low the fan to turn on as the stove heats up to operating temperature It will also shut the blower off after the fire has gone out and the unit cooled to below a useful heat output range Manual...

Страница 14: ...latch Excessive Creosote Buildup See 1 2 3 above Low Heat Output 1 Wood is wet Use dry wood 2 Fire too small Build a larger fire 3 Draft too low Chimney plugged or restricted inspect and clean Won t B...

Страница 15: ...ant Nickel CAST 31RSNI 10 Door Handle Assembly WODC 4147C 11 Boost Manifold 4105 12 Firebrick Set BRIC SSERA 13a Brick Rail Left Right SSER RAILSET 14 Replacement Baffle Kit SSER DBAKIT 15 Baffle Pin...

Страница 16: ...kel CAST 31NI Door Casting Radiant Nickel CAST 31RSNI 12 Door Handle Assembly WODC 4147C 13 Boost Manifold 4105 14 Firebrick Set BRIC SSERA 15a Brick Rail Left Right SSER RAILSET 16 Replacement Baffle...

Страница 17: ...anding the basic functions of this design Traditionalwoodstoveshadabasiccombustion systemwhichallowedaconsiderableamountof heat energy to escape up the chimney as un burned gases and particulates smok...

Страница 18: ...ts back 5 Using a 3 4 wrench remove 1 x 1 2 bolts and save for later use 6 Remove pallet retaining brackets from stove bottom Pedestal Kit 1 With the unit on its back and the removable cover facing up...

Страница 19: ...either A B C as shown below if you are installing the optional ash cleanout system or 1 full brick in place of A B if you are not installing the ash cleanout system Next install the side firebricks 4...

Страница 20: ...20 SUPER SD1 300913 24...

Страница 21: ...300913 24 SUPER SD1 21...

Страница 22: ...22 SUPER SD1 300913 24...

Страница 23: ...07 INSTALLEZ ET UTILISEZ SELON LES INSTRUCTIONS D INSTALLATION ET D OP RATION FOURNI AVEC L APPAREIL CONTACTEZ LES OFFICIELS DE LA CONSTRUCTION OU DE SERVICE D INCENDIE POUR DES INFORMATIONS QUANT AUX...

Страница 24: ...PACIFIC ENERGY FIREPLACE PRODUCTS LTD 2975 Allenby Rd Duncan B C V9L 6V8 Phone 250 748 1184 Web site http www pacificenergy net Printed in Canada...

Отзывы: