background image

9 – Error codes and how to solve them : 

This table explains the error codes caused by a defective 

regulating component or by a security operation. You have to call your 
retailer. 

 

Screen and state 
of the heat water 
pump 

Component 

Possible cause 

Intervention of your retailer 
 

E 1   
The heat pump 
continues running 
 

Water temp sensor 

Sensor disconnected, 
non supplied or 
defective 

Check the connections, the wires, change 
it or replace the electronic card 

E 2   
The compressor stops 
and after the fan stops 
too 

Ambient air 
temperature sensor 

Sensor disconnected, 
non supplied or 
defective 

Check the connections, the wires, change 
it or replace the electronic card 

E 3   
The heat pump 
continues running 

Oultlet compressor 
temperature sensor 

Sensor disconnected, 
non supplied or 
defective 

Check the connections, the wires, change 
it or replace the electronic card 

E 4 
Compressor and fan 
stop 

Defrosting system 

The defrosting is 
incomplete and the 
automatism decides to 
stop the heat pump 

Increase lightly the water flow going into 
the heat pump; the effect is to increase the 
temperature of the refrigerant in the 
evaporator. 

E 5 

Magnetic ammeter   

The compressor stops 3 
times in 24h because of 
intensity excess in the 
compressor 

Environment problem 
See DIRECTIONS FOR 
INSTALLATION AND MAINTENANCE 

E 6 
Compressor and fan 
stop 

Oultlet compressor 
temperature sensor 

Oultlet compressor 
temperature detected 
up to 105°C more than 3 
times in 24h   

Environment problem 
See DIRECTIONS FOR 
INSTALLATION AND MAINTENANCE 

E 7 
Compressor and fan 
stop 

Magnetic circuit 
breaker  

Electric current leak 
from the compressor, 
from the fan or from an 
electrovalve; electric 
safety system of the heat 
pump 

Switch off the current and call an 
electrician for repairing or replacing the 
defective component 

 Flow 

switch 

Flow switch 
disconnected, non 
supplied or defective 

Check the connections, the wires, change 
it or replace the electronic card 

E 9 
 

Pressure controller 
High pressure 

Pressure controller is 
disconnected, or 
defective. 
Or increasing in 
pressure in the 
refrigerant circuit 

Call a refrigerating engineer who will do 
the necessary controls of the circuit 
pressure 

E A 
 

Pressure controller 
Low pressure 

Pressure controller is 
disconnected, or 
defective. 

Call a refrigerating engineer who will do 
the necessary controls of the circuit 
pressure 

Or lack of gas in the 
refrigerant circuit. 

 
 
 
 
 
 

 

 10

www.pac-direct.com

Содержание KS12R

Страница 1: ...Swimming Pool Heat Pump User manual MODEL KS8R KS12R KS15R KS20R 1 www pac direct com...

Страница 2: ...e filtration pump is working At the beginning of the season or when the outside temperature is low you must increase the daily filtration time so that the Heat pump can overcome thermal losses of the...

Страница 3: ...risk of overheating Keep out of reach of children and do not to let them play nearby inform them of the dangers of this machine Never introduce a stick or your fingers into the protective grille of t...

Страница 4: ...mes wet you might observe a thin layer of white frost on the gilds of the radiator This is normal To avoid a strong thickness of white frost which would prevent the air to circulate through the gilds...

Страница 5: ...After starting Ensure that operation is regular if high vibrations occur stop the Heat pump and call your fitter Instructions Careful The first pressure on the key ON OFF gives the authorization of st...

Страница 6: ...re desired Adjustment of the stop temperature in cold period Adjustment of the start and stop hour Choosing the heating or the cooling mode On off Defrost forced To adjust the hour Error messages The...

Страница 7: ...ton ON OFF Start between 1 second and 4 minutes in the last active mode heating or cooling Go from heating mode to cooling mode or inversely from cooling to heating Press the button MODE Stop for 4 mi...

Страница 8: ...to confirm the setting 2 Press Timer on to enter timer setting to start the unit Press key adjust hour number Press Timer on again to adjust minute number Press Timer on once more to confirm the sett...

Страница 9: ...emptying THE EXCHANGER MIGHT BURST IF IT HAS NOT EMPTIED COMPLETEY Put back each pipe to its place and screw again the connections to entirely close again to avoid little animal s entry Remark supplem...

Страница 10: ...nt in the evaporator E 5 Magnetic ammeter The compressor stops 3 times in 24h because of intensity excess in the compressor Environment problem See DIRECTIONS FOR INSTALLATION AND MAINTENANCE E 6 Comp...

Страница 11: ...of the condensates not installed or stopped black plastic conduit prolonged with a flexible pipe of evacuation It s natural these condensates are caused by condensation of the humid air on the gilds...

Отзывы: