STEP 2: COMPLETE ELECTRICAL CONNECTION
Dimming Applications — Daisy Chain ed Units
Hortiled Top luminaires can be “daisy-chained” in series
(see chart on page 12 for maximum number of luminaires
per daisy chain). Each string of luminaires will have a main
supply cord and daisy-chain connector cords.
1
Turn off and lock out the branch circuit.
2
Connect the whip end of the main power supply
cord to branch circuit and the dimming cord
to the pre-installed dimming circuit. See steps 2
to11in
STEP 2: Dimming Applications - Standalone
Units
(page 11).
3
When daisy chaining luminaires, remove pre-
installed connector cap(s) in 3-pin connectors on
“power out” side of luminaire(s) between adjacent
modules.
TIP:
Store removed connector caps in a safe place since they will
need to be re-installed if daisy-chain connector is ever removed.
4
Securely connect the modules with connector
cables (available in lengths of 3 ft / 6ft / 10 ft / 15ft).
drip loop
power
dimming
Coil and secure excess cable - allowing for drip
loops to draw moisture away from connectors.
Daisy-chain connector cables have a 5-pin Y-dim
female connector on one end, and a 3-pin male
connector on the other end. The 3-pin male
connector on the cord must be installed into the
corresponding 3-pin female “power out” connector
on the luminaire. The 5-pin Y-dim female connector
must be installed into the corresponding 5-pin male
“power in” connector on the luminaire.
3-pin
male connector
5-pin
female connector
5
While power connection is daisy-chained, control
needs to be wired separately to each luminaire.
Install control cable for 0-10V dimming solution
into open strain relief for each 5-pin female
Y-connector connector .
6
Continue until daisy chain is complete.
Always ensure that cords are:
• not concealed or extended through a wall, floor,
ceiling, or other parts of the building structure,
• not located above a suspended ceiling or
dropped ceiling,
• not permanently affixed to the building
structure,
• routed so that they are not subject to strain and
are protected from physical damage,
• visible over their entire length, and
• used within their rated ampacity as determined
for the maximum temperature of the installed
environment specified in the instructions.
7
Ensure that connector cap remains firmly installed
in last luminaire of daisy chain string to ensure safe
operation and IP66 integrity.
WARNING
Both connectors on the luminaire must be sealed
(either with a power cord, daisy-chain connector
cord or a cap) once installed. Use of luminaire(s) with
exposed connectors will void the product warranty.
8
Switch on the branch circuit.
ATTENTION
When luminaires are mounted consecutively, the
distance between each luminaire must be a minimum of
8.25 in. (210 mm).
ATTENTION
10 cm
10 cm
8.25 in
(210 mm)
8.25 in
(210 mm)
power supply cord
(dimming)
daisy-chain connector
cable (dimming)