3.5
Roof beam supports
Requirements for roof beam supports:
-
Must be calculated, provided and installed by the contractor (unless already
present in the construction).
-
Must be positioned under the support feet or the frame to hold the weight of
the IntrCooll®, including frame and ducting.
Steel support beams (examples)
Already present in the construction
installed by the contractor
3.6
Opening and curb
To install the IntrCooll® properly, prepare the building on the proposed
installation location of the IntrCooll®.
-
Prepare an opening in the roof of at least (add additional space the
construction around the ducting):
•
IntrCooll® Std.: 600 mm x 600 mm
•
IntrCooll® Plus: 900 mm x 900 mm
-
The unit must be positioned 100% level. If not level, water can leak into the
ducting.
24