Removing the Manometer/Pressure Gauge

After the manifold pressure is properly adjusted, the Manometer 

or pressure gauge must be removed from the gas valve.
1. Turn the thermostat to its lowest setting.

2. Turn OFF the main gas supply to the unit at the manual shut-

off valve, which is located outside of the unit.

3. Turn OFF all of the electrical power supplies to the unit.

4. Remove the pressure gauge adapter from the gas valve and 

replace it with the 1/8” NPT manifold pressure plug that had 

been removed earlier. 

NOTE:

 Make sure the plug is tight and 

not cross-threaded.

5. Turn ON the electrical power to the unit.

6. Turn ON the main gas supply to the unit at the manual shut-off 

valve.

COMPLETING THE CONVERSION

 WARNING:

Do not alter or remove the original rating plate from 

the furnace.

1. Attach the following labels:

•  The conversion warning label should be affixed to the outside 

of the unit door.

•  The conversion information label should be affixed near the 

rating plate on the inside of the control area.

•  The gas valve conversion label should be affixed on the gas 

valve.

 NOTE:

 Each label should be prominently visible after installation.

2. Reinstall the appliance door.

3. Run the appliance through 3 complete cycles to assure proper 

operation.

REPLACING THE PRESSURE SWITCH(ES)

1. Turn off all electrical power to the appliance.

2. Remove the door from the burner compartment.

3. Label and remove the wires from the terminals of the pressure 

switch(es).

4. Label and remove tubing from pressure switch(es)

5. Remove the tubing from the pressure switch(es).

6. Remove the screws mounting the pressure switch(es).

7. Install the appropriate pressure switch in the same location 

using the supplied screws.

8. Reconnect the tubing to the proper pressure switch(es).

9. Reconnect the wires to the proper pressure switch terminals.

Measuring the Manifold Pressure

The manifold pressure must be measured by installing a pressure 

gauge (Manometer, Magnehelic Meter, etc.) to the outlet end of 

the gas valve as follows:

1. Turn off all electrical power to the appliance.

2. Shut OFF the gas supply at the manual shutoff valve located 

outside of the appliance.

3. Using a 3/16” Allen wrench, remove the manifold pressure tap 

plug located on the outlet side of the gas valve. See Figure 6 

(page 5).

4. Install an 1/8” NPT pipe thread fitting, that is  compatible with 

a Manometer or similar pressure gauge.

5. Connect the Manometer or pressure gauge to the manifold 

pressure tap.

6. Set the room thermostat above room temperature to start the 

furnace.

7. Allow the furnace to operate for 3 minutes and then check 

the manifold pressure. Compare the measured value with the 

value shown in Table 2 (page 3). If the manifold pressure is 

not set to the appropriate pressure, then it must be adjusted.

Adjusting the Manifold Pressure

NOTE:

 Adjustments do not need to be made to LOW fire for 

model VR8205Q2381. Refer to Table 2 for manifold pressures.
1. Single stage gas valve: Remove the cap screw from the top of 

the gas valve regulator. See Figure 2 (page 4) for VR8205S2890 

or VR8215S1289 models.

  2-stage gas valve: For VR8205Q2381 models, remove the 

plastic cap covering the adjustment screws (Figure 4 page 4).

2. Using a screwdriver or Allen wrench (where appropriate), slowly. 

turn the adjustment screw till the appropriate manifold pressure 

listed in Table 2 is achieved. See Figure 2 for VR8205S2890 

or VR8215S1289 models. See Figure 4 for VR8205Q2381 

models or Figure 5 for VR9205Q1127 models.

 

NOTE:

 Turning the screw clockwise increases the pressure, 

turning the screw counter-clockwise decreases the pressure. 

To prevent the screw from backing all the way out from the 

valve, turn the screw slowly.

3. Replace and tighten the cap screw or the plastic cap over the 

adjustment screw.

IN

ON

OFF

Inlet

Pressure

Tap

Inlet

Pressure

Tap

SINGLE STAGE VALVES

Manifold

pressure

Tap

Manifold

pressure

Tap

Manifold

pressure

Tap

2-STAGE VALVE

Model VR8215S1289

Inlet

Pressure

Tap

Model VR8205S2890

Model VR8205Q2381

ON/OFF

Switch

ON/OFF

Switch

ON/OFF

Knob

Figure 5. Inlet & Manifold Pressure Tap Locations

Содержание G7 Series

Страница 1: ... furnace was produced before January 2010 the NOX baffles must be removed from the furnace before conversion WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any ...

Страница 2: ...rews securing the gas manifold assembly to the burner assembly 9 Set the screws aside and remove the gas manifold assembly from the appliance 10 Carefully remove the burner orifices from the gas manifold assembly 11 Read the rating plate affixed to the appliance to determine its rated input Btu hr and the size of the factory installed orifices IMPORTANT NOTE Beforeinstallinganorifice checkthesideo...

Страница 3: ...56 10 0 56 9 0 56 8 5 57 10 0 57 9 0 57 8 5 108 000 56 10 0 56 9 0 56 8 5 57 10 0 57 9 0 57 8 5 118 000 55 10 0 55 9 0 55 8 5 56 10 0 56 9 0 56 8 5 120 000 55 10 0 55 9 0 55 8 5 56 10 0 56 9 0 56 8 5 G7TA GC2TA G7TK GC2TK 60 000 55 10 0 55 9 0 55 8 5 56 10 0 56 9 0 56 8 5 80 000 55 10 0 55 9 0 55 8 5 56 10 0 56 9 0 56 8 5 100 000 55 10 0 55 9 0 55 8 5 56 10 0 56 9 0 56 8 5 120 000 55 10 0 55 9 0 5...

Страница 4: ...hten the plug first to prevent cross threading Tighten with 3 16 Allen wrench Lighting Adjustment of the Appliance WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Never test for gas leaks with an open flame Use a commercially available soap solution made specifically for the detection of leaks to check all connections Afi...

Страница 5: ... Manometer Magnehelic Meter etc to the outlet end of the gas valve as follows 1 Turn off all electrical power to the appliance 2 Shut OFF the gas supply at the manual shutoff valve located outside of the appliance 3 Using a 3 16 Allen wrench remove the manifold pressure tap plug located on the outlet side of the gas valve See Figure 6 page 5 4 Install an 1 8 NPT pipe thread fitting that is compati...

Страница 6: ...1021834R G7SD 038D 23EB1 1 00 1018532R 0 20 1021836R G7SD 038D 24B1 1 00 1018532R 0 20 1021836R G7SD 054D 23EB1 0 80 632495R 0 50 632492R G7SD 054D 24B1 0 80 632495R 0 50 632492R G7SD 072D 35C1 0 80 632495R 0 50 632492R G7SD 072D 35C2 0 80 632495R 0 50 632492R G7SD 072D 35EC1 0 80 632495R 0 50 632492R G7SD 090D 35C1 0 80 632495R 0 60 632493R G7SD 090D 35EC1 0 80 632495R 0 60 632493R G7SD 108D 35ED...

Страница 7: ... G7TE 080D 35C1 0 35 0 75 1021821R 0 50 0 80 1021831R G7TE 080D VC1 0 35 0 75 1021821R 0 50 0 80 1021831R G7TE 100D 35C1 0 40 0 75 1021822R 0 50 0 80 1021831R G7TE 100D VC1 0 40 0 75 1021822R 0 50 0 80 1021831R G7TE 115D 45D1 0 30 0 75 1021823R 0 70 1 50 1021832R G7TE 115D VD1 0 30 0 75 1021823R 0 70 1 50 1021832R G7TK 060C 23A1 0 20 0 60 1021814R NA NA NA G7TK 060C VA1 0 20 0 60 1021814R NA NA NA...

Страница 8: ...Specifications illustrationssubjecttochangewithoutnoticeorincurringobligations 11 18 O Fallon MO Nortek Global HVAC LLC 2018 All Rights Reserved 709369C Replaces 709369B ...

Отзывы: