26
Time of Duration
Trigger Level2 overload protection time
5000 mS
Level3 Overload Value
Level3 overload protection value
120% P
Rated
Time of Duration
Trigger Level3 overload protection time
1000 mS
Under-Volt Protection
Under-voltage protection switch
Disable
Protection Value
Under-voltage protection value
10% V
Rated
Protection Delay
Under-voltage protection detection delay 1000 mS
Time Of Duration
Trigger under-voltage protection time
1500 mS
Under-Curr Protection
Under-current protection switch
Disable
Protection Value
Under- current protection value
10% I
Rated
Protection Delay
Under- current protection detection
delay
1000 mS
Time Of Duration
Trigger under- current protection time
1500 mS
Short-Circuit Protection Short-circuit protection switch
Disable
Protection Value
Short-circuit protection voltage value
5% V
Rated
Protection Delay
Short-circuit protection detection delay
10 mS
Time Of Duration
Trigger Short-circuit protection time
20 mS
Protection Switchs
Relevant protection switchs
---
Password
Password
User Default Settings
---
Reset
Factory Reset
Restoring factory Settings (except for
information records)
---
Error Log reset
Clears fault Records
---
System Data Reset
Clears UI or all system setting
---
User Data Reset
Clears selected data
---
5.4 Warning list
Name
Description
Troubleshooting
Write EEPROM Err
Unrecoverable
error
Write
EEPROM
Error
Power off, Restart.
Read EEPROM Err
Read
EEPROM
Error
Power off, Restart.
Write FLASH Err
Write FLASH Error
Power off, Restart.
Read FLASH Err
Read FLASH Error
Power off, Restart.
Diff Speci Err
Different
from
Master
specifications
Power off, Restart.
External Error
Recoverable error
A fault was detected
through dry contact
input
Check whether dry contact signal input is
normal and exclude alarm signal.
Driver Protect
Driver circuit error
Power off, Restart.
HW Over-Volt P
The
hardware
over-voltage circuit
Confirm start overshoot or steady
overshoot (overshoot in working process),