“Regusol X 25-B” / “Regumaq X 30-B”

Replacement high-efficiency pump storage cylinder circuit

Technical advice

Important information on the replacement / connection
of controllers and speed controlled high-efficiency pumps. 

In addition to the power supply cable (230V), speed controlled high-
efficiency pumps call for a separate cable for the transmission of the
control  signal.  The  most  common  control  signals  are  0-10  V  and
pulse-width  modulated  signals  (PWM)  of  proportional  or  inverted
type. 

The type of signal is specified in the operating instructions of the cor-
responding  pump!  If  the  control  signals  of  the  controller  and  the
pump are not coordinated, an operation is not possible.

General information regarding pin assignment:

Control cable

Power
supply 230 V

blue

brown

L

N

PE

Signal output
(PWM or 0-10V)

GND (

earth)

DANGER

!

Always  disconnect  the  power  supply  before  starting  work  on
electrical components.

To avoid malfunctions and severe damage to installations with
speed controlled high-efficiency pumps, the following must be
observed:

– The pump must only be replaced with a pump with identical

control signal!

– The  controller  must  only  be  replaced  with  a  controller  with

identical control signal!

– When combining a pump and a controller with different con-

trol signals, operating safety is no longer guaranteed. Wrong
control signals may cause damage to the installation and en-
danger health!

– Work on electrical installations must only be carried out by a

qualified electrician.

– If not stated otherwise, all work and settings must only be car-

ried out by a trained tradesman.

– Under working conditions, high-efficiency pumps are almost

silent. Malfunctions caused by airlocks could be confounded
with a pump defect. This has to be taken into account when
carrying out the functional test! 

NOTICE

The following functional test has to be carried out when putting the
controller or pump into operation and when replacing them:

– Switch pump to “ON” in the manual menu (relay test) – the pump

is in operation now.

– Now switch pump to “OFF” in the manual menu – the pump is no

longer in operation.

The installation and operating instructions that come with the pump,
controller and station have to be read in their entirety before installa-
tion and initial operation. The instructions have to remain with the user
of  the  system.  Claims  of  any  kind  due  to  damages  caused  by  the
nonobservance  of  the  instructions  or  incorrect  use  cannot  be  ac-
cepted.

Connection of the high-efficiency pump “Wilo-Yonos PARA RS”
to  the  controller  “Regtronic  RQ-B”  (“Regumaq  X  30-B”)  and
“Regtronic RX-B“ (“Regusol X 25-B”)

Insert the enclosed pump connecting cable for power supply and the
PWM cable for control signal transmission into the appropriate con-
nections  on  the  reverse  of  the  high-efficiency  pump.  The  locking
mechanism at the PWM connection must be observed. For the con-
nection to the controller “Regtronic RQ-B”, insert the individual con-
trol signal cable marked “PWM1” into the high-efficiency pump. For
the connection to the controller “Regtronic RX-B”, use the double con-
trol signal cable and connect the cable marked “PWM2” to the high-
efficiency pump. 

PWM connection

Power supply 230V

Electrical connection to the controller “Regtronic RQ-B”

Electrical connection to the controller “Regtronic RX-B”
The control cable for the connection to the controller “Regtronic RX-
B” is a double cable. Please observe that both plugs are connected
to  the  corresponding  pumps.  The  replacement  pump  “Wilo-Yonos
PARA RS” has to be connected to the cable marked “PWM2” and the
solar  circuit  pump  “Wilo-Yonos  PARA  ST”  to  the  cable  marked
“PWM1”. 