Valves, co systems

“Regufloor HX”

Control unit with heat exchanger for surface heating systems

Installation and operating instructions for the specialised installer

Read installation and operating instructions in their
entirety before installing the control unit!
Installation, initial operation, operation and main-
tenance must only be carried out by qualified tra-
desmen!
The installation and operating instructions, as well
as  other  valid  documents  must  remain  with  the
user of the system!

Illustr. 1.1 “Regufloor HX” Control unit

1 General information

1.1 Information regarding installation and opera-

ting instructions

These  installation  and  operating  instructions  serve
the installer to install the control unit “Regufloor HX”
professionally and to put it into operation.
Other valid documents – manuals of all system com-
ponents as well as valid technical rules – must be ob-
served. 

1.2 Keeping of documents

These  installation  and  operating  instructions  should
be kept by the user of the system.

1.3 Copyright

The installation and operating instructions are copy-
righted.

1.4 Symbol explanation

Safety  guidelines  are  displayed  by  symbols.  These
guidelines are to be observed to avoid accidents, da-
mage to property and malfunctions.

Content

1.

General information ....................................... 7

2.

Safety notes ....................................................8

3.

Transport, storage and packaging ................. 8

4.

Technical data .................................................8

5.

Construction and function ............................. 9

6.

Installation.................................................... 10

7.

Operating ..................................................... 11

8.

Accessories.................................................. 11

9.

Maintenance ................................................ 11

10. Warranty....................................................... 11
11. Charts.  ........................................................ 12

Subject to technical modification without notice.

115106580     05/2017

OVENTROP GmbH & Co. KG
Paul-Oventrop-Straße 1
D-59939 Olsberg
Phone        +49 (0) 29 62 82-0
Fax             +49 (0) 29 62 82-400
E-Mail        [email protected]
Internet      www.oventrop.com

For an overview of our global presence visit
www.oventrop.com.

!

DANGER

DANGER indicates an immi-

nent dangerous situation which will lead to death or
serious  injury  if  the  safety  guidelines  are  not  obser-
ved.

WARNING  indicates  a  pos-

sible dangerous situation which may lead to death or
serious  injury  if  the  safety  guidelines  are  not  obser-
ved.

NOTICE

NOTICE indicates a possible

damage to property which may occur if the safety gui-
delines are not observed.

CAUTION indicates a possi-

ble  dangerous  situation  which  may  lead  to  minor  or
moderate injury if the safety guidelines are not obser-
ved.

!

WARNING

!

CAUTION

!

EN

Содержание Regufloor HX

Страница 1: ...ole gekenn zeichnet Diese Hinweise sind zu befolgen um Unfälle Sachschäden und Störungen zu vermeiden Inhalt 1 Allgemeine Hinweise 1 2 Sicherheitshinweise 2 3 Transport Lagerung und Verpackung 2 4 Technische Daten 2 5 Aufbau und Funktion 3 6 Einbau 4 7 Betrieb 5 8 Zubehör 5 9 Wartung und Pflege 5 10 Gewährleistung 5 11 Diagramme 6 Technische Änderungen vorbehalten 115106580 05 2017 OVENTROP GmbH C...

Страница 2: ...luckungsgefahr Regelstation nicht in Reichweite von Kindern lagern und installieren Allergien Gesundheitsgefahr Regelstation nicht berühren und jeglichen Kontakt vermeiden falls Allergien gegenüber den verwendeten Materialien bekannt sind 3 Transport Lagerung und Verpackung 3 1 Transportinspektion Lieferung unmittelbar nach Erhalt sowie vor Einbau auf mögliche Transportschäden und Vollständigkeit ...

Страница 3: ...rregler 3 Wärmeübertrager 4 Entleerungs und Entlüftungsventil 5 Manometer 6 Expa Con Kappenventil 7 Membranausdehnungsgefäß 8 Halterung Membranausdehnungsgefäß 9 Membransicherheitsventil 10 Tauchhülse 11 Pumpe Abb 5 1 Übersicht Regufloor HX Die Regufloor HX Regelstation wird zur konstanten Vorlauftemperaturregelung für Flächenheizungen ein gesetzt und ermöglicht mit Hilfe des Wärmeübertra gers ein...

Страница 4: ...1 auf das Hyco con HTZ Regelventil aufschrauben und den Fühler in die in den Vorlauf der Primärseite installierte Tauchhülse Teil 10 Abb 5 1 einstecken und mit der Schraube befestigen Dabei ist darauf zu ach ten dass das Kapillarrohr nicht geknickt oder flach gedrückt wird Zum Einbau der Regelstation in einen Einbauschrank bitte Abschnitt 4 2 Abmessungen Anschlussmaße be achten GEFAHR Der Vorlauf ...

Страница 5: ...n Sekundärkreis ein stellen Reglereinstellbereich 20 50 C 7 3 Korrekturfaktoren für Wasser Glykol Gemische Die Korrekturfaktoren der Frostschutzmittelhersteller müssen bei der Durchflusseinstellung berücksichtigt werden 8 Zubehör Zur Absperrung von Vor und Rücklauf können die Oventrop Kugelhähne 1406383 DN 20 G3 4 IG x G1 AG 1406384 DN 25 G1 IG x G1 AG an die Regelstation montiert werden Das Zubeh...

Страница 6: ...on HTZ Druckverlust p mbar Durchfluss V l h Druckverlust p mbar Durchfluss V l h Druckverlust p Pascal P Abweichung Druckverlust p Pascal Medium Wasser Referenztemperatur 50 C 6 Kanäle primärseitig 7 Kanäle sekundärseitig Druckverlust p mbar Massenstrom qm kg h Druckverlust p Pascal Umdrehungen ...

Страница 7: ...tructions are copy righted 1 4 Symbol explanation Safety guidelines are displayed by symbols These guidelines are to be observed to avoid accidents da mage to property and malfunctions Content 1 General information 7 2 Safety notes 8 3 Transport storage and packaging 8 4 Technical data 8 5 Construction and function 9 6 Installation 10 7 Operating 11 8 Accessories 11 9 Maintenance 11 10 Warranty 11...

Страница 8: ...f ingestion Store and install the control unit out of reach of children Allergies Health hazard Do not touch the control unit and avoid any contact if allergies against the used materials are known 3 Transport storage and packaging 3 1 Transport inspection Upon receipt check delivery for any damages caused during transit Any damage must be reported immediately upon re ceipt 3 2 Storage The control...

Страница 9: ... exchanger 4 Draining and venting valve 5 Pressure gauge 6 Expa Con Valve with lead sealable cap 7 Diaphragm expansion tank 8 Bracket for diaphragm expansion tank 9 Diaphragm safety valve 10 Immersion pocket 11 Pump Illustr 5 1 Summary Regufloor HX The control unit Regufloor HX is used for flow tem perature control in surface heating systems The in tegrated heat exchanger allows a separation of th...

Страница 10: ...part 3 illustr 6 1 onto the regulating valve Hycocon HTZ Now in sert the immersion sensor into the immersion po cket part 10 illustr 5 1 installed in the supply pipe and fix it with the screw Please observe that the capillary must not be kinked or flattened When mounting the control unit inside a cabinet please observe paragraph 4 2 Dimensions Con nection size DANGER The supply at the control unit...

Страница 11: ...l of the temperature controller control range 20 50 C 7 3 Correction factors for mixtures of water and glycol The correction factors of the manufacturers of the an tifreeze liquids have to be considered when setting the flow rate 8 Accessories The Oventrop ball valves 1406383 DN 20 G 3 4 F x G 1 M 1406384 DN 25 G 1 F x G 1 M can be screwed onto the control unit for the isolation of the supply and ...

Страница 12: ...ocon HTZ Pressure loss p mbar Flow rate V l s Pressure loss p mbar Flow rate V l s Pressure loss p Pascal P deviation Pressure loss p Pascal Fluid water Reference temperature 50 C 6 channels primary side 7 channels secundary side Pressure loss p mbar Flow rate qm l s Pressure loss p Pascal Turns ...

Страница 13: ... la propriété intellectuelle La présente notice d installation et d utilisation est protégée par le droit de la propriété intellectuelle 1 4 Signification des symboles Les consignes de sécurité sont identifiées par des symboles Ces consignes doivent être respectées pour éviter des accidents des dégâts matériels et des dysfonctionnements Contenu 1 Généralités 13 2 Consignes de sécurité 14 3 Transpo...

Страница 14: ...ingestion Stocker et installer l ensem ble de réglage hors de portée des enfants Allergies Risque de santé Ne pas toucher l ensemble de réglage en cas d allergies aux matériaux utilisés 3 Transport stockage et emballage 3 1 Inspection après transport Examiner la livraison immédiatement après réception pour vérifier l absence de dommages dus au trans port Si des dommages ou d autres défauts sont co...

Страница 15: ...à chape plombable 7 Vase d expansion à membrane 8 Fixation vase d expansion à membrane 9 Soupape de sécurité à membrane 10 Douille plongeuse 12 Circulateur Fig 5 1 Vue d ensemble Regufloor HX L ensemble de réglage Regufloor HX est utilisé pour le maintien d une température de départ constante dans des installations de surfaces chauffantes et pour la séparation du système de chauffage circuit pri m...

Страница 16: ... de température pièce 3 fig 6 1 sur le robinet de réglage Hycocon HTZ In troduire la sonde dans la douille plongeuse montée sur l aller du côté primaire pièce 10 fig 5 1 et la fixer à l aide de la vis en veillant à ce que le tuyau capillaire ne soit ni plié ni aplati Merci de prendre en compte le paragraphe 4 2 En combrements Cotes de raccordement lors du mon tage de l ensemble de réglage DANGER L...

Страница 17: ...égulateur de température plage de réglage 20 50 C 7 3 Facteurs de correction pour mélanges eau glycol Les facteurs de correction du fabricant de l antigel sont à respecter lors du réglage du débit 8 Accessoires Pour fermer l aller et le retour les robinets à tournant sphérique Oventrop suivants 1406383 DN 20 G 3 4 F x G 1 M 1406384 DN 25 G 1 F x G 1 M peuvent être montés sur l ensemble de réglage ...

Страница 18: ... Hycocon HTZ Perte de charge p mbar Débit V l h Perte de charge p mbar Débit V l h Perte de charge p Pascal Ecart P Perte de charge p Pascal Fluide Eau Température de référence 50 C 6 canaux côté primaire 7 canaux côté secondaire Perte de charge p mbar Débit qm kg h Perte de charge p Pascal Tours ...

Страница 19: ...e dell im pianto per poter essere consultate in caso di bisogno 1 3 Tutela dei diritti d autore Le istruzioni di montaggio e di funzionamento sono protette dai diritti d autore 1 4 Simboli Le avvertenze riguardanti la sicurezza sono contras segnati da simboli Questi avvisi devono essere ri spettati per evitare infortuni danni materiali e guasti Indice 1 Note generali 7 2 Avvisi di sicurezza 8 3 Tr...

Страница 20: ...ta dei bambini Allergie Pericolo per la salute In presenza di allergie ai materiali utilizzati non toccare il Gruppo di rego lazione ed evitare qualsiasi contatto 3 Trasporto stoccaggio e imbal laggio 3 1 Verifica del materiale consegnato Al ricevimento della fornitura e prima del montaggio verificarne la completezza ed eventuali danni causati dal trasporto Se sono rilevabili vizi di questo tipo o...

Страница 21: ...rana 8 Supporto vaso di espansione a membrana 9 Valvola di sicurezza a membrana 10 Pozzetto 11 Pompa Fig 5 1 Dettaglio del gruppo Regufloor HX Il Gruppo di regolazione Regufloor HX è impiegato per la regolazione costante della temperatura di man data per impianti di riscaldamento a superfici radianti e con l aiuto di uno scambiatore di calore permette una separazione del sistema di riscaldamento c...

Страница 22: ... incasso Avvitare il regolatore di temperatura Parte 3 Fig 6 1 sulla valvola di regolazione Hycocon HTZ e inserire il sensore nel pozzetto installato nella man data del lato primario Parte10 Fig 5 1 e fissarlo con la vite Accertarsi che il tubo capillare non sia piegato o schiacciato Per il montaggio del Gruppo di regolazione in una cassetta ad incasso rispettare le dimensioni misure di collegamen...

Страница 23: ... di mandata per il circuito secondario campo di regolazione regolatore 20 50 C 7 3 Fattori correttivi per miscele acqua glicole Nella regolazione della portata è necessario tenere in considerazione i fattori correttivi indicati dai produttori di refrigeranti 8 Accessori Per intercettare la mandata e il ritorno è possibile montare sul Gruppo di regolazione le valvole a sfera Oventrop 1406383 DN 20 ...

Страница 24: ...ressione p mbar Portata V l h Perdita di pression p mbar Portata V l h Perdita di pressione p Pascal Scostamento P Perdita di pressione p Pascal Mezzo acqua Temperatura di riferimento 50 C 6 canali circuito primario 7 canali circuito secondario Perdita di pressione p mbar Volume qm kg h Perdita di pressione p Pascal Giri ...

Отзывы: