3-3. Link Controller Initialization
11/98
3-7
U3-1021
Westinghouse Proprietary Class 2C
3-3.2. Procedure 2
LC Module Not Containing DOS 5.0, or LC Module with a Corrupted RAM Disk
It is recommended that all LC initialization and file operations be performed from
a floppy disk using the following procedure (which assumes that “C” is the PC hard
drive and “A” is the PC floppy disk drive):
Note
While communicating with the LC, only one disk
drive on the personal computer will be accessible. All
desired files must be on that drive.
1. Copy the following files to Drive C on the PC:
— RLCFLASH.EXE program (on RLC10A disk)
— RLCEXTPC.EXE program (on RLC 20A disk)
— Any applicable LC executable programs
— Any applicable configuration files
2. Place the LC module (Personality and Electronics) in an appropriate Base Unit
in an Ovation I/O cabinet (if necessary, refer to “Planning and Installing Your
Ovation System” (U3-1000)).
3. Connect an applicable cable from the LC module (J1 Programming Port) to the
personal computer (COM1 or COM2). (See Section 2 for additional
information on the cable to be used.)
4. Format a floppy disk as a DOS (5.0) bootable floppy by doing the following:
Place the disk into a floppy drive at the PC and type the following command
(assuming the disk is in Drive
A
):
C:\>FORMAT A: /S