2-4. Interface Connections
U3-1021
2-6
2/99
Westinghouse Proprietary Class 2C
2-4. Interface Connections
2-4.1. Terminal Block Wiring Information
The field connection to the LC module can be made either at the nine pin J2
connector of the personality module or at the terminal block of the base unit. It is
common for RS-422 and RS-485 communication, because the cable length is
typically longer, for the connection to be made as field wiring rather than as a pre-
manufactured cable. The terminal block connection is convenient for these cases.
Each Personality module has a simplified wiring diagram label on its side, which
appears above the terminal block. This diagram (see Figure 2-2) indicates how the
wiring from the field is to be connected to the terminal block in the base unit. The
following table lists and defines the abbreviations used in the diagram.
Abbreviation
Definition
BAU
Programming port baud rate select jumper
BT.
Link Controller boot-up option select jumper
COM *
Applications port signal common reference
CTS *
RS-232 Clear To Send (Input)
DCD *
RS-232 Data Carrier Detect (Input)
DSR *
RS-232 Data Set Ready (Input)
DTR *
RS-232 Data Terminal Ready (Output)
Earth GND *
Application port cable assembly shield connection (for locally grounded shields).
Connects to the Base Unit DIN rail.
RES
A14 = RS-485/RS-422 receive data termination resistor (tie to RX+ (A15) if used)
B14 = RS-485/RS-422 transmit data termination resistor (tie to TX+ (B15) if used)
RI *
RS-232 Ring Indicator (Input)
RTS *
RS-232 Request To Send (Output)
RX/ *
RS-232 Receive Data (Input)
RX+ *
RS-485/RS-422 Receive Data (Input)
RX- *
RS-485/RS-422 Receive Data (Input)
SEL
B8 = Programming port baud rate select jumper
C8 = Link Controller boot-up option select jumper