Operation

 

900-0198-01-00 Rev A 

33

 

 

Settable 

AC Divert

 parameters include: 

 

Low and high DC voltage 

 

On and off delay 

 

During variable conditions, the AUX output is triggered no more than once per minute (if voltage conditions are still 
met).  This prevents rapid nuisance cycling of the AC load. 

 

AC Divert

 should not be used as the sole source of battery regulation.  If the inverter shuts down or fails, the batteries 

could suffer severe damage.  This function should be supported by an external regulator. 

 

If the inverter shuts down due to overload, the AUX output will also shut down.  If the inverter load exceeds 30 Aac, 
the AUX output will turn off to prevent an overload condition.   

 

If either the FETs or the capacitors become too hot, the AUX will turn off due to diminished inverter wattage. 

 

AC Drop

 activates the AUX output whenever the inverter disconnects from an AC source.  It can activate a light or 

alarm to show that the shore power is no longer present or that a generator has stopped.  Alternately, it could be 
used to show that the source has connected.

  

 

 

This function does not have settable parameters. 

 

Vent Fan

 activates the AUX output in response to a high DC (battery) voltage set point.  It can run a small fan to 

ventilate the battery compartment to eliminate gases that result from battery charging.  When the voltage falls 
below this set point for a settable delay period, the AUX output turns off.  This is the default selection.

  

 

Settable parameters include: 

 

High DC voltage 

 

Off delay

 

 

Fault 

activates the AUX output when the inverter shuts down due to an error condition.  (See page 40).  It can 

activate a light or alarm to show that the inverter has failed.  With the appropriate devices, it could send an alarm 
signal through a radio, pager, or telephone dialer.

  

 

 

This function does not have settable parameters. 

 

Gen Alert

 is used as a controller for an AC generator with a remote start feature, although it has limited 

functionality.  (The generator recharges batteries using the inverter’s battery charger.)   

 

The AUX output will activate to start the generator when the battery voltage falls to a low set point for a settable delay.  
The AUX output is deactivated, shutting off the generator, once the battery voltage rises to a high voltage setting for a 
settable delay period.

 

 

 

 

Settable 

Gen Alert

 parameters include: 

 

Low and high DC voltage 

 

On and off delay 

Gen Alert

 control logic is located in the inverter.  It has the advantage of functioning when the system display is 

removed.  However, it may not completely charge the batteries and does not have all the advantages of the Advanced 
Generator Start (

AGS

) function that is found in the system display.  For many users, the 

AGS

 function may prove more 

useful than 

Gen Alert

.  

Gen Alert

, however, could be used as a literal “Generator Alert”, a signal to the user to manually 

start a generator.

  

 

 

Load Shed

 can perform load management.  It is intended to turn off designated loads during low battery periods 

to conserve remaining battery power.

 

 

When battery voltage rises above a settable high voltage level, the AUX output is activated after a settable delay.  The 
AUX output is used to energize a larger external relay (normally open) which is connected to non-vital loads.  The AUX 
output will be deactivated once the battery voltage falls below a low voltage setting for a settable delay period.

 

 

 

Load Shed

 will turn off when the inverter enters a high-temperature condition or when the AC output voltage drops 

below a specific AC voltage for more than 3 seconds.  This limit is 15 volts below the setting of the inverter’s output 
voltage.  For the inverter’s default output voltage of 120 Vac, the limit is 105 Vac. 

 

 The limit is not otherwise settable.   

 

Load Shed

 will turn off if the input current exceeds the 

Input AC Limit

 setting while the inverter is using an AC source. 

 

Settable parameters include: 

 

Low and high DC voltage 

 

On and off delay 

Содержание FX Mobile Series

Страница 1: ...FX Inverter Charger FX and VFX Mobile Series Operator s Manual...

Страница 2: ...KES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION b ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR...

Страница 3: ...nput 15 AC Current Settings 16 AC Source Acceptance 16 Generator Input 17 Transfer 17 Battery Charging 18 Charge Current 18 Charge Cycle 19 Charging Steps 20 New Charging Cycle 22 Equalization 23 Batt...

Страница 4: ...ges 41 Disconnect Messages 42 Specifications 43 Electrical Specifications 43 Mechanical Specifications 46 Environmental Specifications 46 Regulatory Specifications 47 Listings 47 Summary of Operating...

Страница 5: ...lectrical Specifications for 36 Volt Mobile Models 45 Table 13 Electrical Specifications for 48 Volt Mobile Models 45 Table 14 Mechanical Specifications for Mobile Models 46 Table 15 Environmental Spe...

Страница 6: ...Example of Classic Series Stacking Arrangement 26 Figure 9 Example of OutBack Series Stacking Arrangement 27 Figure 10 Example of Parallel Stacking Arrangement Three Inverters 27 Figure 11 Example of...

Страница 7: ...dicates that the hazard could be harmful to human life CAUTION Hazard to Equipment This type of notation indicates that the hazard may cause damage to the equipment IMPORTANT This type of notation ind...

Страница 8: ...nd 48 volt models Uses the MATE MATE2 or MATE3 System Display and Controller or the AXS Port SunSpec Modbus Interface sold separately for user interface MATE3 must have firmware revision 003 007 xxx o...

Страница 9: ...control or interface Basic modes and settings are pre programmed at the factory See the menu tables beginning on page 48 However external communication devices such as the OutBack MATE3 can be used to...

Страница 10: ...ation The settings are stored in the nonvolatile memory of the FX inverter However it is highly recommended to install it as part of the system This provides the means to monitor system performance an...

Страница 11: ...0 Vdc or higher 33 3 Vdc or higher 37 5 Vdc or higher 50 0 Vdc or higher ACCEPTABLE YELLOW 11 5 to 12 4 Vdc 23 0 to 24 8 Vdc 30 6 to 33 0 Vdc 34 5 to 37 2 Vdc 46 0 to 49 6 Vdc MARGINAL RED 11 4 Vdc o...

Страница 12: ...l be providing power to the system See page 28 for a description of Power Save AC IN Yellow Solid The AC source is connected and providing power The FX inverter may or may not be charging the batterie...

Страница 13: ...r customized Other items are general topics or applications for the inverter These items may not have their own menus but their activity can still be influenced or optimized by changing certain settin...

Страница 14: ...also clear a low battery error Output Voltage The AC output voltage can be adjusted within a limited range NOTE The inverter s output frequency is 60 Hz This is not adjustable The inverter is also con...

Страница 15: ...o further adjustments are needed 5 If the inverter does not produce power and continues to sleep the sensitivity is set too high Turn the load off and lower the Sensitivity menu item Turn on the load...

Страница 16: ...ce The input source must meet the following specifications to be accepted Voltage 108 to 140 Vac Frequency 54 to 66 Hz See the menu tables which begin on page 48 for voltage programming information Wh...

Страница 17: ...m the input When it closes the input and output terminals become electrically common When the relay changes states the physical transfer delay is approximately 25 milliseconds CAUTION Equipment Damage...

Страница 18: ...nt into a usable AC figure divide the DC figure by the following number based on inverter voltage and round up The result can be used as a charger setting for the FX inverter 12 voltinverters Divide b...

Страница 19: ...bed beginning below The inverter s factory default settings are intended for three stage charging of lead acid batteries Charging Graphs When the charger is set to Auto using the system display the ch...

Страница 20: ...AC source but the charger has been turned off Bulk Stage This is the first stage in the three stage charge cycle It is a constant current stage which drives the battery voltage up This stage typically...

Страница 21: ...orb Time to zero will cause the charger to skip both the Bulk and Absorption stages and proceed directly to the constant current Refloat stage This may not be desired if the intent is to skip Absorpti...

Страница 22: ...Refloat or Float but will go directly to Silent The charger only spends time in Float stage if the timer is still running To skip this step Decreasing the Float Time setting to zero causes the invert...

Страница 23: ...s for equalization Battery Temperature Compensation Battery performance will change when the temperature varies above or below room temperature 77 F or 25 C Temperature compensation is a process that...

Страница 24: ...ower than the set points A 24 Vdc system with batteries at 40 C will compensate its charging to 0 9 Vdc lower than the set points A 32 Vdc system with batteries at 10 C will compensate its charging to...

Страница 25: ...e HUB4 or the HUB10 3 The inverter on each port must be programmed with a status and stacking value Different HUB products use different port assignments There are usually other specialized instructio...

Страница 26: ...ple of Classic Series Stacking Arrangement OutBack Series Stacking Dual Stack In OutBack s unique series stacking two inverters create two separate 120 Vac output phases in a split phase configuration...

Страница 27: ...e outputs are controlled directly by the master and cannot operate independently Slave inverters can go into Power Save mode when not in use The master will activate individual slaves based on load de...

Страница 28: ...f Series Parallel Stacking Arrangement Four Inverters Three Phase Stacking In three phase stacking inverters create three separate 120 Vac output phases in a wye configuration The output of each inver...

Страница 29: ...ng the MATE3 System Display It is advisable to use the MATE3 Configuration Wizard to set up Power Save Levels To set these items manually The system display uses Power Save Level selections to assign...

Страница 30: ...ave is used by the battery chargers of stacked systems with slave inverters Not all chargers are activated immediately Initially the master is the only active charger The batteries will absorb current...

Страница 31: ...ons at the bottom show how the inverters are activated in sequence as loads are applied The first line shows a load handled by the master alone The second line shows a total load of 15 Aac even though...

Страница 32: ...when the inverter reaches a high internal temperature It is intended to trigger a small external fan for additional cooling See the Warning Troubleshooting table on page 41 for a description of the fa...

Страница 33: ...troller for an AC generator with a remote start feature although it has limited functionality The generator recharges batteries using the inverter s battery charger The AUX output will activate to sta...

Страница 34: ...charge batteries Low Vdc High Vdc Low high Vdc On Off delay Load Shed Operates designated loads normally turns off loads in severe conditions High Vdc Low Vdc High temp Low output Vac High input Aac L...

Страница 35: ...ck inverters if present The Next soft key accesses the Battery screen Figure 17 Inverter Screens Screen items The upper left corner is the Inverter Mode see above When Charging is indicated the Charge...

Страница 36: ...time on the MATE3 screen Battery Screen The Next soft key brings up a screen showing charger status charger settings and battery voltage and temperature information Figure 18 Battery Screen Screen it...

Страница 37: ...ossible Cause Possible Remedy No AC output will not invert No DC voltage Use a DC voltmeter to check the voltage directly on the DC terminals If not present the problem is external If present the inve...

Страница 38: ...ed from AC MATE MATE2 or MATE3 system display only If activated prematurely check the system display s Grid Use Time settings and the clock settings HBX or another grid use function may also be active...

Страница 39: ...and turn inverter on Test the AC HOT and NEUTRAL OUT terminals with an AC voltmeter If voltage appears there contact OutBack Technical Support 4 Inverter clicks repeatedly AC output voltage rises or...

Страница 40: ...r add external cooling Low Battery V5 DC voltage is below low battery cut out set point usually due to battery discharge This occurs after 5 minutes at this voltage This error can be triggered by othe...

Страница 41: ...ction Check the AC source The inverter s acceptance range is adjustable NOTE Adjusting the range may accommodate a problematic AC source but it will not fix it Voltage Too Low The AC source is below t...

Страница 42: ...ong with an event message If a message says no or N it is not the cause of the disconnection See the system display literature for more instructions The system display may generate a concurrent event...

Страница 43: ...ch mode 6 watts 6 watts Power Consumption Off 3 watts 3 watts AC Input Voltage Range 80 to 150 Vac 80 to 150 Vac AC Input Frequency Range 54 to 66 Hz 54 to 66 Hz AC Input Current maximum continuous 30...

Страница 44: ...dc Table 11 Electrical Specifications for 32 Volt Mobile Models Specification FX2532MT VFX3232M Continuous Output Power at 25 C 2500 VA 3200 VA Continuous AC Output Current at 25 C 20 8 Aac 26 6 Aac A...

Страница 45: ...Range 80 to 150 Vac 80 to 150 Vac AC Input Frequency Range 54 to 66 Hz 54 to 66 Hz AC Input Current maximum continuous 30 Aac 30 Aac DC Input Voltage nominal 36 Vdc 36 Vdc DC Input Voltage Range 31 5...

Страница 46: ...Table 14 Mechanical Specifications for Mobile Models Specification FX2012MT FX2524MT FX2532MT FX2536MT FX3048MT VFX2812M FX2024M VFX3524M VFX3232M VFX3236M VFX3648M Inverter Dimensions H x W x D 13 8...

Страница 47: ...e high voltage low voltage and temperature The limits for these conditions are summarized in Table 16 See page 40 for more information on these conditions and the warning or error messages which accom...

Страница 48: ...5 Vac ac2 gen upper limit 140 Vac 130 Vac 150 Vac ac2 gen input limit 28 Aac 2 Aac 30 Aac ac2 gen transfer delay 60 AC cycles 0 AC cycles 240 AC cycles Auxiliary AUX aux output control AUTO ON OFF or...

Страница 49: ...140 Vac 130 Vac 150 Vac ac2 gen input limit 28 Aac 2 Aac 30 Aac ac2 gen transfer delay 60 AC cycles 0 AC cycles 240 AC cycles Auxiliary AUX aux output control AUTO ON OFF or AUTO aux output function...

Страница 50: ...140 Vac 130 Vac 150 Vac ac2 gen input limit 28 Aac 2 Aac 30 Aac ac2 gen transfer delay 60 AC cycles 0 AC cycles 240 AC cycles Auxiliary AUX aux output control AUTO ON OFF or AUTO aux output function C...

Страница 51: ...mit 140 Vac 130 Vac 150 Vac ac2 gen input limit 28 Aac 2 Aac 30 Aac ac2 gen transfer delay 60 AC cycles 0 AC cycles 240 AC cycles Auxiliary AUX aux output control AUTO ON OFF or AUTO aux output functi...

Страница 52: ...140 Vac 130 Vac 150 Vac ac2 gen input limit 28 Aac 2 Aac 30 Aac ac2 gen transfer delay 60 AC cycles 0 AC cycles 240 AC cycles Auxiliary AUX aux output control AUTO ON OFF or AUTO aux output function...

Страница 53: ...3 0 Vdc Battery Equalize Equalize Voltage 14 4 Vdc 14 0 Vdc 17 0 Vdc Equalize Time 1 0 hours 0 0 hours 24 0 hours Auxiliary Output Aux Control Auto Off Auto or On Aux Mode Cool Fan Cool Fan DivertDC D...

Страница 54: ...e 28 8 Vdc 28 Vdc 34 Vdc Equalize Time 1 0 hours 0 0 hours 24 0 hours Auxiliary Output Aux Control Auto Off Auto or On Aux Mode Cool Fan Cool Fan DivertDC DivertAC AC Drop Vent Fan Fault GenAlert Load...

Страница 55: ...38 Vdc 37 Vdc 44 9 Vdc Equalize Time 1 0 hours 0 0 hours 24 0 hours Auxiliary Output Aux Control Auto Off Auto or On Aux Mode Cool Fan Cool Fan DivertDC DivertAC AC Drop Vent Fan Fault GenAlert LoadS...

Страница 56: ...tage 43 2 Vdc 42 Vdc 51 Vdc Equalize Time 1 0 hours 0 0 hours 24 0 hours Auxiliary Output Aux Control Auto Off Auto or On Aux Mode Cool Fan Cool Fan DivertDC DivertAC AC Drop Vent Fan Fault GenAlert L...

Страница 57: ...e 57 6 Vdc 56 Vdc 34 Vdc Equalize Time 1 0 hours 0 0 hours 24 0 hours Auxiliary Output Aux Control Auto Off Auto or On Aux Mode Cool Fan Cool Fan DivertDC DivertAC AC Drop Vent Fan Fault GenAlert Load...

Страница 58: ...due to low voltage LED Light Emitting Diode refers to indicators used by the inverter and the system display Master An inverter which provides the primary output phase of a stacked system other stacke...

Страница 59: ...Battery Indicators 11 C Caution Symbol 7 Charging Absorption Stage 21 Current 18 Float 21 Float Stage 21 None 20 Refloat 21 Silent 21 Steps 20 22 Charging Current 19 30 Communications Manager 25 Stac...

Страница 60: ...tacking 26 Series Parallel Stacking 28 Settings MATE or MATE2 48 49 50 51 53 MATE3 54 55 56 57 58 Silent Charging 21 Power Save 29 Source Status 33 Specifications 12 volt 43 24 volt 43 32 volt 44 36 v...

Страница 61: ...Index 900 0198 01 00 Rev A 61 U UL458 8 47 V Vent Fan Control 33 W Warning Symbol 7 Warnings 41...

Страница 62: ...Index 62 900 0198 01 00 Rev A This page intentionally left blank...

Страница 63: ...Index 900 0198 01 00 Rev A 63 This page intentionally left blank...

Страница 64: ...A Masters of the Off Grid First Choice for the New Grid Corporate Headquarters 17825 59th Avenue N E Suite B Arlington WA 98223 USA 1 360 435 6030 European Office Hansastrasse 8 D 91126 Schwabach Germ...

Отзывы: