background image

FLEXnet DC Data Stream

 

16 

900-0137-01-00 Rev

 A

 

 

Definition of Data Stream Items for the FLEXnet DC 

Port Number

:  Indicates the designation of the OutBack HUB port used by the FLEXnet DC.   The addresses will 

be 01 to 10 and will correspond to the appropriate numbered port.   

 

 

Device Type

:  Indicates the presence of a FLEXnet DC battery monitor.  This device type is always 4. 

 

 

Shunt Current

:  Measures the DC current delivered across a specified shunt.  The range is 0009 to 9999, 

incorporating one decimal place.  For example, a  current of 112.3 amps will be sent as ‘1123’.   Separate 
character strings report the status of up to three shunts (A, B, and C), if present). 

 

 

Extra Data Identifier:

  This is an ASCII 

expression of an 8-bit binary string, 
displayed in values ranging from 000 to 
255.  Bit 1 through 7 are the only bits 
used in the string.  The 8th bit is not 
used.  The full range of numbers is also 
not used.

  

 

FLEXnet DC Battery Voltage

:  The DC 

voltage as measured at the batteries by 
the FLEXnet DC’s sense wires.  The range 
is 000’ to 999, incorporating one decimal 
place.  For example, a voltage of 24.8 Vdc 
will be sent as ‘248’.

 

 

 

Battery State of Charge

:  The state of 

charge as determined by the 
programmed parameters of the FLEXnet 
DC.  The range is 0 to 100 percent.

 

 

 

Shunt Enable Flags

:  Indicates whether 

shunts A through C are enabled (a state 
of 1) or disabled (a state of 0).   

 

 

Status Flags

:  This is an ASCII expression 

of an 8-bit binary string, displayed in 
values ranging from 000 to 255.  Each bit 
is a flag for a different function  
as shown in Table 20.  

Relay Mode

 indicates whether the  

AUX relay is open (a state of 0) or closed (a state of 1).  

Relay State

 indicates whether the function has been set to 

manual mode (a state of 0) or automatic mode (a state of 1).

 

 

 

EXAMPLE

:  A returned value of 009 would indicate that the 

FLEXnet DC charge parameters have been met and that the 
values are negative for Shunt 1. 

Battery Temperature

:  The temperature of the batteries as 

reported by the Remote Temperature Sensor (RTS).  The range 
is 00 to 70.  This represents a range of degrees Celsius that is ten  
less than the value shown.  The result is a range of –10°C to 60°C.   
A value of 99 indicates that no RTS is installed.

 

 

 

Checksum

: ‘000’ to ‘999’ This is a simple additive checksum of the decimal values of the Status page.

  

 

EXAMPLE: 

 

 

00,4,0000,0126,0000,02,00023,287,099,001,00,33,062 

 

0+0+4+0+0+0+0+0+1+2+6+0+0+0+0+0+2+0+0+0+2+3+2+8+7+0+9+9+0+0+1+0+0+3+3=062 

 

Table 19

Extra Data Identifier for FNDC

Bit: 7 

extra data numeric sign 

0: positive 

value 

1: negative 

value 

Bits: 1-6 

 

0: Accumulated 

AH

1

 shunt ‘A’ 

1: Accumulated 

kWH

2

 shunt ‘A’ 

2: 

Accumulated AH shunt ‘B’ 

3: Accumulated 

kWH

2

 shunt ‘B’ 

4: 

Accumulated AH shunt ‘C’ 

5: Accumulated 

kWH

2

 shunt ‘C’ 

6: 

Days since full

3

 

7: 

Today’s minimum SOC

4

 

8: 

Today’s net input AH

1

 

9: 

Today’s net output AH

1

 

10: 

Today’s net input kWH

2

 

11: 

Today’s net output KWH

2

 

12: 

5

Charge factor corrected Net battery AH

1

 

13: 

5

Charge factor corrected Net battery kWH

2

 

14-35: Reserved 

 

 

 

1

AH values: 

00000 to 65535 (0 to 65535 amp-hours) 

2

kWH values: 

00000 to 65535 (000.00 to 655.35 kilowatt-hrs.) 

3

Days since full output: 

00000 to 09999 (0.0 to 999.9) 

4

Minimum SOC output: 

00000 to 00100 (0 to 100 percent) 

5

MATE version 4.04 and above 

Table 20  Status Flag 

Bit Value 

Status 

Charge parms met 

2 2 

Relay 

Mode 

3 4 

Relay 

State 

Shunt A values are negative 

16 

Shunt B values are negative 

32 

Shunt C values are negative 

Содержание MATE3

Страница 1: ...7 124 9 107 5 7 A b uD h a b i U A E E ma i l s o l a r e mi r a t e s g r e e n c o m We b w w w e mi r a t e s g r e e n a e E mi r a t e s G r e e n E mi r a t e s G r e e nE l e c t r i c a l Me c...

Страница 2: ...MATE3 USB Card Owner s Manual...

Страница 3: ...WRITING OUTBACK POWER TECHNOLOGIES a MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION b ASSUMES NO...

Страница 4: ...ol 4 FX Class Inverter Data Stream 5 Definition of Data Stream Items for the FX Class Inverter 6 Radian Class Inverter Data Stream 9 Definition of Data Stream Items for the Radian Class Inverter 11 Ch...

Страница 5: ...ers 9 Table 8 Data Stream Definitions for Radian Class Inverters 10 Table 9 Radian Inverter Operating Mode 11 Table 10 Radian Error Codes 12 Table 11 Radian AC Modes 12 Table 12 Radian Misc 12 Table 1...

Страница 6: ...card must be installed for this function to work see next page The MATE3 s Serial Data Stream menu item must be set to Enabled in order for it to send data streams See the MATE3 System Display and Co...

Страница 7: ...sed from the personal computer to an OutBack device using the MATE3 The data streams sent from an inverter have a different content then those from a charge controller or FLEXnet DC battery monitor ho...

Страница 8: ...y current 39 Tenths digit of battery voltage 14 Units digit of Buy current 40 Comma ASCII 44 Used as a data separator 15 Comma ASCII 44 Used as a data separator 41 High byte of inverter Misc 16 Hundre...

Страница 9: ...es are shown in Table 2 Inverter Off The user has turned the inverting mode off and no other functions are active Search The inverter is using the Search function of the inverting mode Inverter On The...

Страница 10: ...e values are additive For example an overtemp error and backfeed error would return an ASCII value of 132 a binary value of 10000100 AC Modes This represents the status of the AC input The range is 00...

Страница 11: ...rs the values are additive For example a low AC input voltage and low AC input frequency would return an ASCII value of 10 a binary value of 00001010 Checksum This is a simple additive checksum of the...

Страница 12: ...id input voltage separator L1 Generator input voltage separator L1 output voltage separator Error modes separator L2 Charger current separator L1 Charger current separator L2 Sell Current ASCII code 1...

Страница 13: ...s a data separator 58 High digit of inverter Error code 19 Hundreds digit of AC input voltage on grid L1 59 Middle digit of inverter Error code 20 Tens digit of AC input voltage on grid L1 60 Low digi...

Страница 14: ...to 99 in 1 ampere increments Inverter Operating Modes Reports any of a variety of functions that can be performed by the inverter The range is 00 to 99 although not all items are in use Items and corr...

Страница 15: ...dc for 24 volt systems and 0 4 Vdc for 48 volt systems Misc Byte This is an ASCII expression of an 8 bit binary string displayed in values ranging from 000 to 255 Only certain bits are in use at this...

Страница 16: ...current 40 Comma ASCII 44 Used as a data separator 15 Comma ASCII 44 Used as a data separator 41 Thousands digit of daily amp hour accumulation 16 Hundreds digit of PV input voltage 42 Hundreds digit...

Страница 17: ...255 Each bit represents a different fault as shown in Table 16 For example a shorted battery sensor would return an ASCII value of 32 a binary value of 00100000 Only certain bits are used In MX60 con...

Страница 18: ...f Shunt B current 39 Enable flag for Shunt A 14 Units digit of Shunt B current 40 Enable flag for Shunt B 15 Tenths digit of Shunt B current 41 Enable flag for Shunt C 16 Comma ASCII 44 Used as a data...

Страница 19: ...tate of 0 or closed a state of 1 Relay State indicates whether the function has been set to manual mode a state of 0 or automatic mode a state of 1 EXAMPLE A returned value of 009 would indicate that...

Страница 20: ...rt Modbus Interface is recommended The AXS Port however can only send individual commands and not universal ones Table 21 Command Response Definitions Command Response INV 0 Inverter Off INV 1 Search...

Страница 21: ...ements inverter s AC2 input limit amps AC2INLM Returns inverter s AC2 input limit amps AC2INLM nn BULK 1 Starts system wide bulk charge all ports BULK 2 Stops system wide bulk charge ie goto float all...

Страница 22: ...lowatt hours CC 14 Data Stream FLEXmax CC 13 FLEXnet DC Battery Monitor 15 FX Class Inverter 5 Radian Class Inverter 9 Data Stream Definitions FLEXmax CC Aux Mode 14 Battery Voltage 14 Charger Current...

Страница 23: ...rrent 11 Sell Enabled 11 Warning Codes 12 Device Type CC 14 FNDC 16 FX 6 Radian 11 E Error Codes FX 7 Radian 12 External Connections 4 Extra Data Identifier FNDC 16 F Fault Codes CC 14 G Generator Inp...

Страница 24: ...NOTES...

Страница 25: ...900 0137 01 00 Rev A Corporate Headquarters 5917 195th St NE Arlington WA 98223 USA 1 360 435 6030 European Office Hansastrasse 8 D 91126 Schwabach Germany 49 9122 79889 0...

Отзывы: