background image

Radian-Class Inverter Data Stream 

 

12 

900-0137-01-00 Rev

 A

 

 

EXAMPLE

A grid-interactive inverter has a 

SellRE

 setting of 51.2 Vdc and 10 amps 

(1200 watts) of AC output load on L1.  DC sources contribute 480 watts to 
the battery.  The inverter maintains the battery at 51.2 Vdc by converting 
the excess 480 watts of DC power to AC.  The inverter mode displays 

Support

 with the 

Inverter Current

 meter showing 4 amps (480 watts) of 

production.  The

 Buy Current

 would show 6 amps (720 watts), for 600 

watts of total AC load current.  If the AC load was removed, the inverter 
would have

 Sell Enabled

 as the mode and show 4 amps of 

Sell Current

  

Error Codes

:  This is an ASCII expression of an 8-bit binary string, displayed in values ranging from 000 to 255.  

Each bit represents a different error as shown in Table 10.  If more than one error occurs, the values are additive.  
For example, an overtemp error and backfeed error would return an ASCII value of 132 (a binary value of 
1000100).

  

 

AC Mode

:  This represents the status of the AC input.  The range is 00 to 

99, but only three states are in use.  

No AC

 means that no AC source has 

been detected by the inverter.  

AC Drop

 means that AC is present but the 

inverter is not allowed to accept it.  

AC Use

 means AC is present and 

valid, and the inverter will utilize it. 

 

 

Battery Voltage

:  The DC voltage as measured at the inverter’s battery 

terminals.  The range is 000 to 999, incorporating one decimal place.  For 
example, a 24.8 Vdc battery voltage will be sent as ‘248’.  The resolution 
of battery voltage is 0.1 Vdc for 12-volt systems, 0.2 Vdc for 24-volt 
systems, and 0.4 Vdc for 48-volt systems.

 

 

 

Misc Byte

:  This is an ASCII expression of an 8-bit binary string, displayed 

in values ranging from 000 to 255.  Only certain bits are in use at this 
time.  Each bit represents a different condition.  Bit 7 indicates the priority 
of the inverter’s two AC inputs.  Bit 8 indicates the Radian inverter’s 
nominal output voltage.

 

 

 

 

 

 

 

Warning Codes

:  This is an ASCII expression of an 8-bit binary string,  

displayed in values ranging from 000 to 255.  Each bit represents a 
different warning as shown in Table 13.  If more than one warning occurs, 
the values are additive.  For example, a low AC input voltage and low AC 
input frequency would return an ASCII value of 010 (a binary value of 
00001010).

  

 

 

 

Checksum

:  This is a simple additive checksum of the decimal values of 

the data stream.  Range is 000 to 999.  

EXAMPLE

 

 

00,6,00,00,00,00,119,000,119,00,00,00,00,121,000,121,04,000,02,554,128,000,067 

 

0+0+6+0+0+0+0+0+0+0+0+1+1+9+0+0+0+1+1+9+0+0+0+0+0+0+0+0+1+2+1+0+0+0+1+2+1+0+4+0+0
+0+0+2+5+5+4+1+2+8+0+0+0=067 

 

Table 10  Radian Error Codes 

Bit Value 

Error 

Low Vac Output 

2 2  Stacking 

Error 

3 4 

Over 

Temp. 

4 8 

Low 

Battery 

5 16 

Phase 

Loss 

6 32 

High 

Battery 

7 64  Shorted 

Output 

8 128 

Backfeed 

Table 11  Radian AC Modes 

Value Mode 

00 No 

AC 

01 AC 

Drop 

02 AC 

Use 

Table 12   Radian Misc 

Bit Value 

Error 

1 1 

Reserved by inverter

2 2 

Reserved by inverter

3 4 

Reserved by inverter

4 8 

60 Hz Output 

5 16 

AUX output ON 

6 32 

Relay output ON 

7 64 

1 = AC 1 selected 
0 = AC 2 selected 

8 128 

1 = 230 Vac inverter
0 = 120 Vac inverter

Table 13 Radian Warning Codes

Bit Value 

Warning 

AC Input Freq High 

AC Input Freq Low 

Input Vac High 

Input Vac Low 

16 

Buy Amps > Input size

32 

Temp Sensor Failed 

7 64 

Comm 

Error 

8 128 

Fan 

Failure 

Содержание MATE3

Страница 1: ...7 124 9 107 5 7 A b uD h a b i U A E E ma i l s o l a r e mi r a t e s g r e e n c o m We b w w w e mi r a t e s g r e e n a e E mi r a t e s G r e e n E mi r a t e s G r e e nE l e c t r i c a l Me c...

Страница 2: ...MATE3 USB Card Owner s Manual...

Страница 3: ...WRITING OUTBACK POWER TECHNOLOGIES a MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION b ASSUMES NO...

Страница 4: ...ol 4 FX Class Inverter Data Stream 5 Definition of Data Stream Items for the FX Class Inverter 6 Radian Class Inverter Data Stream 9 Definition of Data Stream Items for the Radian Class Inverter 11 Ch...

Страница 5: ...ers 9 Table 8 Data Stream Definitions for Radian Class Inverters 10 Table 9 Radian Inverter Operating Mode 11 Table 10 Radian Error Codes 12 Table 11 Radian AC Modes 12 Table 12 Radian Misc 12 Table 1...

Страница 6: ...card must be installed for this function to work see next page The MATE3 s Serial Data Stream menu item must be set to Enabled in order for it to send data streams See the MATE3 System Display and Co...

Страница 7: ...sed from the personal computer to an OutBack device using the MATE3 The data streams sent from an inverter have a different content then those from a charge controller or FLEXnet DC battery monitor ho...

Страница 8: ...y current 39 Tenths digit of battery voltage 14 Units digit of Buy current 40 Comma ASCII 44 Used as a data separator 15 Comma ASCII 44 Used as a data separator 41 High byte of inverter Misc 16 Hundre...

Страница 9: ...es are shown in Table 2 Inverter Off The user has turned the inverting mode off and no other functions are active Search The inverter is using the Search function of the inverting mode Inverter On The...

Страница 10: ...e values are additive For example an overtemp error and backfeed error would return an ASCII value of 132 a binary value of 10000100 AC Modes This represents the status of the AC input The range is 00...

Страница 11: ...rs the values are additive For example a low AC input voltage and low AC input frequency would return an ASCII value of 10 a binary value of 00001010 Checksum This is a simple additive checksum of the...

Страница 12: ...id input voltage separator L1 Generator input voltage separator L1 output voltage separator Error modes separator L2 Charger current separator L1 Charger current separator L2 Sell Current ASCII code 1...

Страница 13: ...s a data separator 58 High digit of inverter Error code 19 Hundreds digit of AC input voltage on grid L1 59 Middle digit of inverter Error code 20 Tens digit of AC input voltage on grid L1 60 Low digi...

Страница 14: ...to 99 in 1 ampere increments Inverter Operating Modes Reports any of a variety of functions that can be performed by the inverter The range is 00 to 99 although not all items are in use Items and corr...

Страница 15: ...dc for 24 volt systems and 0 4 Vdc for 48 volt systems Misc Byte This is an ASCII expression of an 8 bit binary string displayed in values ranging from 000 to 255 Only certain bits are in use at this...

Страница 16: ...current 40 Comma ASCII 44 Used as a data separator 15 Comma ASCII 44 Used as a data separator 41 Thousands digit of daily amp hour accumulation 16 Hundreds digit of PV input voltage 42 Hundreds digit...

Страница 17: ...255 Each bit represents a different fault as shown in Table 16 For example a shorted battery sensor would return an ASCII value of 32 a binary value of 00100000 Only certain bits are used In MX60 con...

Страница 18: ...f Shunt B current 39 Enable flag for Shunt A 14 Units digit of Shunt B current 40 Enable flag for Shunt B 15 Tenths digit of Shunt B current 41 Enable flag for Shunt C 16 Comma ASCII 44 Used as a data...

Страница 19: ...tate of 0 or closed a state of 1 Relay State indicates whether the function has been set to manual mode a state of 0 or automatic mode a state of 1 EXAMPLE A returned value of 009 would indicate that...

Страница 20: ...rt Modbus Interface is recommended The AXS Port however can only send individual commands and not universal ones Table 21 Command Response Definitions Command Response INV 0 Inverter Off INV 1 Search...

Страница 21: ...ements inverter s AC2 input limit amps AC2INLM Returns inverter s AC2 input limit amps AC2INLM nn BULK 1 Starts system wide bulk charge all ports BULK 2 Stops system wide bulk charge ie goto float all...

Страница 22: ...lowatt hours CC 14 Data Stream FLEXmax CC 13 FLEXnet DC Battery Monitor 15 FX Class Inverter 5 Radian Class Inverter 9 Data Stream Definitions FLEXmax CC Aux Mode 14 Battery Voltage 14 Charger Current...

Страница 23: ...rrent 11 Sell Enabled 11 Warning Codes 12 Device Type CC 14 FNDC 16 FX 6 Radian 11 E Error Codes FX 7 Radian 12 External Connections 4 Extra Data Identifier FNDC 16 F Fault Codes CC 14 G Generator Inp...

Страница 24: ...NOTES...

Страница 25: ...900 0137 01 00 Rev A Corporate Headquarters 5917 195th St NE Arlington WA 98223 USA 1 360 435 6030 European Office Hansastrasse 8 D 91126 Schwabach Germany 49 9122 79889 0...

Отзывы: