background image

Requirements and Warnings

The OutBack FW-IOB-D-120VAC is intended as a system compo-

nent and is included in a listing by ETL as indoor enclosures to UL 

standard UL 508A Industrial Control Panels.

This enclosure is intended for battery circuits confi gured for 12 to 

48 volts nominal.

Grounding Instructions – Each enclosure should be connected to 

a grounded, permanent wiring system. For most installations, the 

negative battery conductor should be bonded to the grounding 

system at one (and only one) point in the DC system. All instal-

lations must comply with all national and local codes and ordi-

nances. System grounding as required by the National Electric 

Code, ANSI /NFPA 70-1996, is the responsibility of the system 

installer.

The equipment ground is marked with this symbol:

2

Содержание Power Systems FW-IOB-D-120VAC

Страница 1: ...FW IOB D 120VAC Input Output Bypass Assembly Installation Instructions T M...

Страница 2: ...D 120VAC Installation Instructions Copyright 2006 All rights reserved Disclaimer UNLESS SPECIFICALLY AGREED TO IN WRITING OUTBACK POWER SYSTEMS a MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SU...

Страница 3: ...unding Instructions Each enclosure should be connected to a grounded permanent wiring system For most installations the negative battery conductor should be bonded to the grounding system at one and o...

Страница 4: ...IOB D 120VAC Ground Conductor Neutral Conductor Positive Conductor Green White Black Hardware Kit AC Breakers Breaker Label Set Black Terminal Bus Bar Insulators White Terminal Bus Bar Insulators Bus...

Страница 5: ...self tapping stainless steel fasteners to secure this hardware Figure 2 Placement of Bus Bars GROUND BUS BAR AC NEUTRAL INPUT AND OUTPUT WHITE INSULATORS AC OUT HOT LEG 1 BLACK INSULATORS AC IN HOT LE...

Страница 6: ...Figure 3 Sample Wiring Diagram 5...

Страница 7: ...aker bracket loosely against the breakers on the din rail move the breakers as needed so they line up with the openings in the breaker bracket With the breakers positioned properly lock the yellow tab...

Страница 8: ...per IOB kit 2 Install AC Breaker Bypass Slide Plate and fasteners as shown in Figure 5 3 Do not over tighten the Nylock nuts Overtightening can cause the AC Breaker Bypass Slide Plate to bind Install...