INVERTER DEFAULT VALUES (subject to change with upgrades)
24 VDC System
DEFAULT
MINIMUM
MAXIMUM
Float Voltage
27.4 Vdc
24 Vdc
30 Vdc
Absorb Voltage
29.4 Vdc
26 Vdc
32 Vdc
EQ Voltage
28.8 V
28 Vdc
34 Vdc
ReFloat
25 Vdc
22 Vdc
26 Vdc
LBCO
21 Vdc
18 Vdc
24 Vdc
Absorb Time
2.0 hours
0.0 hours
24.0 hours
EQ Time
1.0 hours
0.0 hours
24.0 hours
Float Time
1.0 hours
0.0 hours
24.0 hours
Charger Draw
5 Aac
0 Aac
7 Aac
AC1/Grid Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
AC2/Gen Transfer Delay
60 AC cycles
0 AC cycles
240 AC cycles
Grid Lower Limit
108 Vac
40 Vac
115 Vac
Grid Upper Limit
140 Vac
130 Vac
150 Vac
Grid Connect Delay
0.5 min
0.2 min
15.0 min
Gen Lower Limit
108 Vac
40 Vac
115 Vac
Gen Upper Limit
140 Vac
130 Vac
150 Vac
AC DROP or USE
USE
N/A
N/A
Charger OFF/AUTO/ON
AUTO
N/A
N/A
Search Threshold
6 watts
0 watts
50 watts
Search Pulses
8
2
20
Search Pulse Spacing
60 AC cycles
4 AC cycles
120 AC cycles
Stacking Phase
1 or 2 phase
N/A
N/A
InPut Select
Gen
N/A
N/A
Grid Input Settings
28 Aac
5 Aac
30 Aac
Gen Input Settings
28 Aac
2 Aac
30 Aac
Set Output Voltage
120 Vac
115 Vac
125 Vac