2  Alarms

Ouflex M requests confirmation before deleting alarm history.

See following page.

A GSM modem can be connected to the Ouflex M for alarm sending a text 
message to the alarm team. The alarms are sent to correct team according to 
alarm routing schedule. When alarm is activated, the controller sends alarm 
messages automatically to phone numbers defined in team. If the alarm isn’t 
acknowledged within 5 minutes, the alarm message will be re-sent to same 
recipients and also to backup number. The Ouflex M sends max. 100 within 
one day.

1. Phone number

+ 3 5 8

4 0 8 4 0 0

Alarm receivers

Team 1

Team 2
Team 3

Entering the telephone numbers:

>

>
>

Alarm receivers

Reset alarm history

Reset alarm history

ACTIVE ALARMS

Every active alarm is shown in a separate row, where you can see 
when the alarm has become active. Press   to get more information 
about the alarm.

In the alarm menu of Ouflex M device, you can check the active 

alarms and what alarms have been active. The number of active 

alarms will be shown in the right corner of the main view. 

Send message: Active alarms

The controller sends a message with information about 

all active alarms. The message is for informational pur-

poses. 

Alarms

Active alarms

Alarm history 
Acknowledge all alarms 
Reset alarm history

Routing schedule 
Alarm receivers 
Alarm sound                 On

>

>
>
>

>
>
>

2

Active alarms

07.12.2016 12:24:52 Risk 

 08.01.2017 01:12:40 Sen

>

>

2

Risk of freeze

PR 1  GROUP 1
Pump has stopped=0
Received: 06.11.2017
 02:27:33

Active alarms

You can acknowledge all alarms by pressing OK.

Acknowledge all alarms

An exclamation mark in front of the date shows that the alarm has not 
been acknowledged.

The reason for the alarm is shown in the heading.
You can also see, what is the alarm priority (1 = Emergency, 2=Danger, 3=Fault, 

4= Service, 5=Info) and what alarm group it belongs to (Group 1 has urgent 

alarms, group 2 malfunction alarms and group 3 service alarms).
Source of the alarm.

Time the alarm was received

Alarm history

02.02.2017 10:11:42  Sen

17.12.2016 11:22:40 Sen

>

>

2

ALARM HISTORY

The reason, source and inactivation time (02.02.2017 10:11:42) is shown for 
every alarm in alarm history. The last 10 alarms can be seen in inactive alarms.

Send message: Alarm history

The controller sends a message with information about 

the 10 most recent alarms. The message is for informa-

tional purposes. 

Alarm history

1.  Browse by using 

 or -

knob. Press   to accept a number/sign.

2.  Press   to move to the next square. 

Press Esc to return to the previous square. OK

3.  Press   for a number of seconds to accept the number. Press Esc for a 

number of seconds to cancel 

Approve: Press and hold OK 
Cancel: Press and hold ESC

Alarm sound

Alarm sound

Off

On

You can take the alarm sound off, if you want.

Содержание Ouflex M

Страница 1: ...pplication to the controller by using SD card M OUFLEX USER MANUAL Ouflex M is a DIN rail attachable monitoring controlling and regulating device Ouflex M can be as a master device and slave device in...

Страница 2: ...he beeper stops The beeper can be turned off with active alarms present by pressing the ESC button When you do so the window with details of the most recent alarm on the screen will close To view acti...

Страница 3: ...isplay settings 9 1 5 Type information 9 1 6 Lock code 9 1 7 Restore settings and updates 10 2 Alarms 11 3 Point info 13 3 1 Wiring info 13 3 2 Bus points 13 3 3 Time programs 13 4 Settings 15 5 Measu...

Страница 4: ...vings and leap years into account automatically The clock has a backup for power outages lasting at least three days 1 Set hours and press to accept 2 Set minutes and press to accept 3 To exit without...

Страница 5: ...S e g TC01 IN PUTS Signal strength Signal strength is expressed with the following descriptions Excellent Good Moderate Low Very low and Initialization failed If signal strength indicates No network t...

Страница 6: ...rt RJ 45 located in the side of the controller The maximum length of the RJ45 ethernet cable between Ouflex M and Oulink is 10m and all 4 pairs must be con nected SMS PIN Approve Press and hold OK Can...

Страница 7: ...have the same bus address All devices in the bus should be set to the same setting value of the baud rate data bits stopbitteihin and parity System settings Network settings Modbus TCP IP If the Ouma...

Страница 8: ...billing information to the Ouman system and activates the service based on the serial number of the Oulink After that you have to activate the ACCESS service from the device OUMAN ACCESS device can be...

Страница 9: ...Network settings Display settings Type info Lock code Not in use Lock code In use Not in use Give lock code 0 0 0 0 Approve Press and hold OK Cancel Press and hold ESC When lock code is taken in use...

Страница 10: ...microSD memory card from Ouflex M 2 Wait until error message Memory card error is shown in the display 3 Insert new microSD memory card which includes new software to Ouflex M 4 Ouflex M asks if you...

Страница 11: ...t alarm history Routing schedule Alarm receivers Alarm sound On 2 Active alarms 07 12 2016 12 24 52 Risk 08 01 2017 01 12 40 Sen 2 Risk of freeze PR 1 GROUP 1 Pump has stopped 0 Received 06 11 2017 02...

Страница 12: ...Adding a new switch time 1 Press at the Add new row 2 Press Set the switch time for alarm routing set hours and mi nutes separately and press 3 Press OK and then turn the control knob to set the alarm...

Страница 13: ...rcuit board temperature The outputs have a Sounder selection which allows you to set the alarm sound off if you want In the bus points menu you can see those devices which are con nected to the bus By...

Страница 14: ...ng mode Weekly schedule 0 3 6 9 12 15 18 21 24 MO TU WE Exception schedule Point info Time programs Exception schedule You can easily make changes that differ from normal routine use by using the exce...

Страница 15: ...s You can hide show these settings by pressing OK for a few se conds When visible these settings are shown slightly indented Settings that require maintenance code There is a symbol in front of these...

Страница 16: ...prove Press and hold OK Cancel Press and hold ESC A t Name of room 1 6 Naming Huoneiden valinta Huoneen 1 nimi Huone 1 Huoneen 2 nimi Huone 2 r m Automatic control is the mode that is normally used If...

Страница 17: ...write the key word using capital or small letters Write only one key word per message Store the key words into your phone s memory If a GSM modem is connected to the Ouflex M you can communicate with...

Страница 18: ...dem Do not pull the slot out of the modem without pres sing the SIM card release button first Insert SIM card into the slot and make sure it settles properly Push the slot back to its place Set the SI...

Страница 19: ...M3 26 GND 27 M4 28 GND 29 M5 30 GND 41 M6 42 GND 43 M7 44 GND 45 M8 46 GND 47 M9 48 GND 49 M10 50 GND 3 Detachable strip connectors passive sensors active sensors and digital inputs 51 M11 52 GND 53 M...

Страница 20: ...M11 M15 5 pcs active sensors 0 10 V M11 M15 from HW ver 1 0 Analog outputs Y1 Y4 4 pcs Output voltage range 0 10 V Output current max 10 mA output PWM output 1 piece that works in parallel with the Y1...

Отзывы: