background image

3/4

DNA:  

TeliaSonera:

Elisa:           

Saunalahti:  

Tele Finland:

+358447983500

+358405202000

+358508771010

+358451100100

+358405202330

Products: 

EH-60 and EH-686

Products: 

EH-200, EH-105, 

Lämpöässä and-

Geopro

Detailed instructions for commencing use of the text 

message connection are presented in the ”GSM modem 

installation” and ”Protection” sections of the user manual.

Message Centre number:

Change the message centre number to +358447983500.

The message centre number can be changed using either 

the EH-686 configuration program or a text message. If 

you change it using a text message, send the message to 

the control device as follows:

  

EH01 0000 HÄL.NUMEROT: nro5: SANOMA358447983500

(EH01=device code, 0000=service code. Note the spaces in the message, 
and that the codes for the device may have changed.)

As of version 2.4.9, the default for the EH-60 device is the DNA message 
centre number.

PIN code:

The PIN code for all program versions of the EH-686 is 

0000. For the EH-60, the PIN code used to be 0000, but 

has changed to 1234 as of version 2.4.9 (sold after 1 

March 2008).

The PIN code for the SIM card in the GSM modem must 

be the same as the device PIN code. If necessary, first 

change the SIM card PIN code to 0000. The PIN code can 

be changed by using the card in a GSM phone.

For security reasons, the PIN code should be changed 

after the GSM modem has been installed. This is done by 

sending the following text message to the EH-60/EH-686:

 EH01 0000 SUOJAUS  

The regulator will send a reply message showing the 

device ID, service code and PIN code. Edit the reply by 

replacing the old code with a new one and send it back to 

the control device. Then make the PIN code of the GSM 

modem’s SIM card identical by using the SIM card in a 

GSM phone.

EH-60/EH-686 device switches

The factory default positions of switches on the EH-60 

and EH-686 devices are correct. If the EH-686 has been 

configured using a PC, the switch positions may have been 

changed. In this case, check the switch positions:

Switch is in the 

BOTTOM position

Communication mode is 

MODEM + SMS

Required settings for regulator/control device

Go to special regulator maintenance and the

”Text message settings” section:

Message Centre number:

Check that the message centre number set for the regu-

lator is +358447983500.

PIN code:

The factory default PIN code setting for the SIM card is 

1234. We recommend changing the code for security 

reasons. First install the SIM card in a GSM phone. After 

changing the PIN code, transfer the SIM card to the mo-

dem. Set the same PIN code for the regulator as for the 

SIM card in the GSM modem.

Modem type:

On the regulator, select Nokia/Siemens as the modem 

type unless the selection includes Ouman/Fargo.

Perform start-up or modem initialization with the 

regulator so that it will begin to use the modem:

If the GSM modem is connected to an EH-200/Lämpöäs-

sä/Geopro regulator, perform the start-up function.

The start-up function is performed by going to the 

regulator’s Start section, pressing OK and exiting the 

start-up mode with ESC without changing any settings.

If the GSM modem is connected to an EH-105 regulator, 

perform modem initialization.

Initialization is performed by going to the regulator’s 

”modem initialization” section, pressing OK and exiting 

with ESC.

Message Centre number:

Содержание GSMMOD4

Страница 1: ...les you to contact the modem directly to the controller or the control device As a new model of the GSMMOD4 modem EVO has entered the market The cable that comes with the package is model based the internal connections of the blue cable of the EVO model are different than the connections of the black cable of the older version The package includes a network device power cable and moun ting accesso...

Страница 2: ... 60 EH 686 should be powered off after the modem is connected so that the device will recognize the modem Connecting the GSM modem to Ouman regulation and control devices Use a DIN rail to fasten the modem into place Attach the DIN rail to the wall The modem has a preattached plate that can be attached to the DIN rail Place the upper edge of the plate above the upper edge of the DIN rail Lower the...

Страница 3: ...e Edit the reply by replacing the old code with a new one and send it back to the control device Then make the PIN code of the GSM modem s SIM card identical by using the SIM card in a GSM phone EH 60 EH 686 device switches The factory default positions of switches on the EH 60 and EH 686 devices are correct If the EH 686 has been configured using a PC the switch positions may have been changed In...

Страница 4: ...ld waste at the end of its life span The product must be processed separately from other waste to prevent damage caused by uncontrolled waste disposal to the environment and the health of fellow human beings The users must contact the retailer responsible for having sold the product the supplier or a local environmental authority who will provide additional information on safe recycling opportunit...

Отзывы: