background image

Blinking                       On continuously

The controller is         The valve is competely open.
 increasing the heat.     Not enough heat in the boiler.
(Valve is opening)
 The controller is       The valve is closed. In  the
decreasing the heat    summer  when no heat is
(Valve is closing)        needed this lamp may always
                                    be on.

                                    The unit is operating.

For example, read control curve C as follows:

CONTROL CURVES

*  If the room temperature is always too cool, turn knob
    B in the +  direction.

* If the room temperature is always too warm, turn
    knob B in the - direction.

One step of the scale of knob B changes the outgoing
water temperature by 4°C, corresponding to about 1°C
in the room temperature.

Select a house-specific control curve
with knob A.
Set the basic setting according to the
table below.

BOILER OR
 ACCU-
MULATOR

HEATING
NETWORK

BOILER OR
ACCU-
MULATOR

HEATING
NETWORK

Heating characteristics of the building

Position of knob A

Well-insulated house (radiator heating)

C...D

House with poor heating characteristics

E... F

House with a floor heating system

A... B

C

B

D

E

A

F

Curve C  is selected in this example. If the room
temperature goes down when the weather gets cold,
select a steeper curve. If the room temperature goes up,
select a lower curve. A suitable curve for your house may
be between the plotted curves.

If the room temperature is even, but
it is too cool or warm, make a fine
adjustment with knob B.

+

NOTE ! Changes in the settings are felt quite slowly.
Wait a few hours before making additional adjustments.

Knob B raises and
lowers the selected
curve.

Select the steepness of
the curve with knob A

C

B

D

E

A

F

The OUMAN controller contains a wide range of
control curves that are designed to respond to very
different kinds of heating conditions. It also has low
curves suitable for houses with floor heating.

C

80

100

60

40

20

Outgoing water temperature

Outdoor temperature

20

10

0

-10

-20

-30

°C

When it is  -20°C, the outgoing water is 50°C
When it is 10°C, the outgoing water is 44°C
When it is  0°C, the outgoing water is 37°C

INDICATOR LAMPS

MANUAL OPERATION

+

A

+

ON

LED

If the green ON indicator lamp is not on, check that
the transformer is plugged in and the transformer lead
is connected. Check the line voltage.

B

MIN  - MAX - LIMITS

The settings located behind the
instruction booklet under the clear
cover are usually set only when the
controller is taken into use the first time.

The minimum limit knob sets the lowest
allowable outgoing water temperature
(if sufficient heat is available).

The maximum limit knob sets the
highest allowable outgoing water
temperature. This is especially beneficial
in floor heating systems, where overly
hot water may cause damages.

O U M A N

O U M A N

O U M A N

O U M A N

O U M A N

O U M A N

O U M A N

O U M A N

OUMAN automatically adjusts the
temperature of the water entering the
network. The heat requirement varies 

according to the outdoor 

When the weather gets cooler, OUMAN
releases just enough heat into the network

to maintain an even room 
temperature.    

OPERATING PRINCIPLE

The OUMAN 80 can also be used manually. Unplug the
transformer to disconnect the operating voltage. Press
the button on the bottom right all the way down while
turning the valve to the desired position with the manual
control lever.

NOTE ! If you wish to disconnect the controller for a
longer period (e.g., in summer), disconnect the operating
voltage (13 VAC) connector from the controller. The
clock battery will also be disconnected to avoid unnecessary
battery drainage (battery life = about 180 days). The
battery is a backup power supply for the clock and
programming during power shortages.

FINE ADJUSTMENT

BASIC SETTING

E H - 8 0

BASIC SETTING, KNOB A

If the room temperature goes down when the
weather gets colder, select a steeper curve
and vice versa.

C
B

D

E

A

F

80

100

60

40

20

Outdoor temperature

20

10

0

-10

-20

-30

°C

OPERATING INSTRUCTIONS

E H - 8 0

E H - 8 0

FINE ADJUSTMENT, KNOB B

If the room temperature is always too cool or
warm, turn knob B in the desired direction;
+ raises, - lowers the temperature.

Outgoing water temperature

E H - 8 0

E H - 8 0

E H - 8 0

E H - 8 0

E H - 8 0

Отзывы: