Do not install a radiant floor heating system on a noninsulated or poorly
insulated subfloor, or over a crawl space.
The efficiency of this type of primary room heating system will depend on
factors such as available surface of the room to be covered with heating cable
(or sufficient percentage of the surface to be heated), heat conductivity of
the floor covering, insulation on outside walls, etc. We recommend that you
verify these points and seek professional advice before investing time and
money.
3.3 Typical Floor Coverings
The thermal resistance of the floor covering must not exceed R = 1.40
(RSI = 0.246). There is no such limit for the subfloor.
Table 3.3 Thermal resistance values for floor coverings
* The floor covering highlighted in grey is prohibited.
For engineered wood floorings, laminated hardwood flooring, vinyl cove-
rings, and linoleum glued to a concrete surface, consult your floor covering
manufacturer to ensure they are compatible with floor heating systems.
11
IMPORTANT!
IMPORTANT!
Typical floor covering
Thermal resistance
R
RSI
Vinyl tiles
0.20
0.035
Linoleum
0.22
0.039
Ceramic
0.25
0.044
Low-pile carpet
0.70
0.123
Parquet flooring
0.70
0.123
Floating floor 10 mm to 16 mm (3/8” to 5/8”)
0.70
0.123
Wood on lathes (strapping)*
2.10
0.368