Do not install a radiant floor heating system on a noninsulated or poorly
insulated subfloor, or over a crawl space.

The efficiency of this type of primary room heating system will depend on
factors such as available surface of the room to be covered with heating cable
(or sufficient percentage of the surface to be heated), heat conductivity of
the floor covering, insulation on outside walls, etc. We recommend that you
verify these points and seek professional advice before investing time and
money.

3.3 Typical Floor Coverings

The thermal resistance of the floor covering must not exceed R = 1.40
(RSI = 0.246). There is no such limit for the subfloor.

Table 3.3 Thermal resistance values for floor coverings

* The floor covering highlighted in grey is prohibited.

For engineered wood floorings, laminated hardwood flooring, vinyl cove-
rings, and linoleum glued to a concrete surface, consult your floor covering
manufacturer to ensure they are compatible with floor heating systems.

11

IMPORTANT!

IMPORTANT!

Typical floor covering

Thermal resistance

R

RSI

Vinyl tiles

0.20

0.035

Linoleum

0.22

0.039

Ceramic

0.25

0.044

Low-pile carpet

0.70

0.123

Parquet flooring

0.70

0.123

Floating floor 10 mm to 16 mm (3/8” to 5/8”)

0.70

0.123

Wood on lathes (strapping)*

2.10

0.368

IMPORTANT!

Содержание Therma Cable

Страница 1: ...INSTALLATION GUIDE October 2009 Edition...

Страница 2: ......

Страница 3: ...2 4 1 Planning Work 12 4 2 Preparing the Subfloor 13 4 3 Marking the Floor 13 4 4 Installing the Therma Cable Floor Heating System 14 4 5 Installing the Temperature Sensor 17 4 6 Applying Self Levelli...

Страница 4: ...racteristics The Therma Cable system can be installed under a shower floor only if the floor is ceramic or natural stone A waterproof membrane must be used to maintain the heating cables in a dry envi...

Страница 5: ...heating cable junction cold lead channel strapping cold lead plywood or concrete slab strapping heating cable self levelling cement cement glue floor covering aluminum sheath ground wire heating wire...

Страница 6: ...ating cable sets must inspect and remove damaged or defective heating cable sets before they are covered or concealed Installer of series heating cable sets must mark the appropriate circuit breaker r...

Страница 7: ...4 720 19 0 OTR0842 280 85 34 70 6 5 93 8 7 840 16 2 OTR0962 320 97 54 80 7 4 107 9 9 960 14 2 Product 240V 208V Length Surface12W sq ft Surface 9 W sq ft Power Resistance ft m sq ft sq m sq ft sq m Wa...

Страница 8: ...e been correctly noted A qualified electrician must measure the system s insulation resistance as follows Use a calibrated megohmeter only Measure insulation resistance at the free end of the cold lea...

Страница 9: ...easure the system s resistance as follows Use a calibrated multimeter only Measure resistance at the free end of the cold lead between the two phase conductors Write the reading in the measures table...

Страница 10: ...Warming This type of heating is designed to enhance comfort and or supplement the room s main heat source It helps keep the floor at a pleasant temperature at all times Installing this type of system...

Страница 11: ...he thermal resistance of the floor covering must not exceed R 1 40 RSI 0 246 There is no such limit for the subfloor Table 3 3 Thermal resistance values for floor coverings The floor covering highligh...

Страница 12: ...Room Layout and Corresponding Therma Cable Product Create a room layout plan to scale for maximum accuracy use the Ouellet Canada Inc form designed for this purpose Identify all stationary elements t...

Страница 13: ...ler only for self leveller The subfloor must be solidly fastened in place to prevent movement The application of a floor levelling product is recommended to prevent future damage to the ceramic caused...

Страница 14: ...placed under these stationary elements The floor temperature sensor must be centered between two parallel heating cables The ideal location is one where it is likely to be away from stationary objects...

Страница 15: ...sition during the pouring of self leveller this strapping is installed at the end after the lacing of the cable The cable can be installed under the ceramic tile of a shower or other wet surfaces the...

Страница 16: ...ing cable must not be shortened neither cut Avoid walking on the Therma Cable system If you must wear soft rubber soled shoes Always start the Therma Cable at least 50 mm 2 from the walls It is import...

Страница 17: ...lation sheath and a slightly larger diameter than the heating cable The sensor must be embedded in cement or an equivalent binder cement glue ceramic glue self levelling cement Glue the sensor to the...

Страница 18: ...BLACK must be exposed A small part top of the heating cable may be exposed at the surface of the self levelling cement ONLY IF a ceramic glue is used afterward AND embeds that part Level the subfloor...

Страница 19: ...208V connection 120V connection Line 1 Black Line Black Line 2 Red Neutral White Bare wire ground Bare wire ground Measure the cable s electrical resistance and record the readings on line 5 Upon inst...

Страница 20: ...be kept near the electrical service If this table is not duly completed the warranty may be annulled Warranty terms are set out in Section 8 4 9 Using the Therma Cable System The Therma Cable floor h...

Страница 21: ...refore a floor covering with greater temperature resistance must be used The room temperature control and floor temperature sensor must never be installed where they will be exposed to sunlight or air...

Страница 22: ...ft 130W sq m at 76 mm 3 spacing is the best watt density to optimize comfort and prevent floor overheating Therma Cable can also be installed with a 100 mm 4 spacing for a 9W sq ft 96W sq m Moreover...

Страница 23: ...carpet be installed over Therma Cable A 14 Yes if the system is completely embedded in self levelling cement You can install low pile carpet over the slab if the carpet s thermal resistance does not e...

Страница 24: ...glue tape 7 2 Floor Covering Tips It is strongly recommended to coat the subfloor with a sealer before spreading the self levelling cement which is very liquid This is to prevent any leaks under the...

Страница 25: ...chaser of the equipments as well as to the subsequent buyer of the building where it has been installed Terms of warranty The present warranties are subject to the compliance of the following terms i...

Отзывы: