Global Settings Menu Mode cont...
2. Touch
MENU
(SELECT) to select the “Return Default” screen. The Display Screen should resemble the
following illustration:
3. Touch
ADD
(YES) to return to factory default; touch
SUB
(NO),
MENU
(BACK), or
BACK
(BACK) if no change
is to be made. Factory Default Settings are:
•
All sensors On
•
Null values reset
•
Cal values reset
•
Faults reset
•
Last day nulled reset
•
Last day called reset
•
Sensor addresses set to 1, 2, 3, and 4 (respectively)
•
Network I.D. set to 5
•
Background: O2 High set to 22.0; O2 Low set to 19.0; all other gases set to 4% of full scale
•
Set to the value that the autocal will cal to: O2 is 25; all other gases set to 50% of full scale
•
Cal method set as manual (except for IR sensors, which must be set as autocal)
4. After a selection has been made, touch
ADD
(NEXT) to continue to the next screen.
5. From the final Global Settings Menu Mode screen, select one of the following options:
•
Touch
ADD
(NEXT) to advance to the Sensor Settings Menu Mode.
•
Touch
MENU
(SELECT) or
BACK
(BACK) to return to the first Global Settings Menu Mode
screen.
•
Touch
SUB
(PREV) to return to the previous Global Settings Menu Mode setting: Return to Factory
Default Setting.
18