NB!

 

Always break current before working with the fan.

•   Before service, maintenance or repair, disconnect 
  power and wait until the impeller has stopped.
•   When cleaning and maintaining the fan always have 
  to be secured when open, so it can’t fall down and 
  cause bodily injury. 
•  The fan must be cleaned regularly, at least once 
  per year to maintain the capacity and to avoid 
  unbalance which may cause unnecessary damage 
  to the bearings.
•   No special tools needed when cleaning. 
•  The fan bearings are maintenance-free and should 
  be replaced only when necessary.
•  When cleaning the fan, high-pressure cleaning or 
  strong dissolvent must not be used. 
•  Cleaning should be done without displacing or 
  damaging the impeller

.

•   The capacitor in the single-phase fans has finite life-
  time and should be exchanged after 45.000 hours of 
  operation (about 5 years) to secure maximum func-
  tion. Defective capacitor can cause damage.

•  Notice the weight of the fan when closing after 
 inspection/cleaning. 
•   Mount back all details in reverse order. Check that 
  the fan is closed and locked before starting.
•   Make sure that there is no noise from the fan.

F A U L T   D E T E C T I O N

13

E N G L I S H

M A I N T E N A N C E

Attention, look out for sharp edges and corners.

Loosen the screws (4x M8), 
open the fan and 
secure so it can’t fall down.

1.  Make sure that the power is connected to the fan.
2. Disconnect the power and verify that the impeller 
  is not blocked.
3. For fans with EC motor, check the LED flashing 
  code. For more information see page 15-16.

4. If the previous steps doesn´t solve the problem,
  contact your fan supplier.
5. If the fan is returned to the supplier, it must be 
  cleaned, the motor cable must be undamaged and a 
  detailed fault desription must be enclosed.

W A R R A N T Y

The warranty is only valid under condition that the 
fan is used according to this “Directions for  use” and 
a regular maintenance has been made and record. The 
warrantor is responsible only for the operation if app-

roved accessories are used. The warranty does not cover 
product failures caused by accessories/equipment from 
other manufacturers.

1270366_utg5_TKV_TKH_SV_EN.indd   13

2020-01-07   11:06:16

1270366_utg5_TKV_TKH_SV_EN.pdf   13

1270366_utg5_TKV_TKH_SV_EN.pdf   13

2020-01-07   11:11:04

2020-01-07   11:11:04

Содержание TKH 560

Страница 1: ...or use Takfl ktar TKV TKH Roof fans TKV TKH SVENSK ENGLISH VERSION 1270366_utg5_TKV_TKH_SV_EN indd 1 2020 01 07 11 05 17 1270366_utg5_TKV_TKH_SV_EN pdf 1 1270366_utg5_TKV_TKH_SV_EN pdf 1 2020 01 07 11...

Страница 2: ...r transport av brand och explo sionsfarliga mnen slipdamm sot o dyl F r maximal livsl ngd vid installation i fuktig eller kall milj b r TKV TKH vara i kontinuerlig drift Fl kten f r ej vara i drift i...

Страница 3: ...an utf ras Fl kten ska monteras s att ev vibrationer ej kan verf ras till kanalsystem och byggnadsstomme Anv nd t ex dukstos f r detta Beakta fl ktarnas vikt vid montering TKV TKH utom TKV TKH 560 A1...

Страница 4: ...ddsjord h ll sladden kort och med s lite induktans som m jligt Se till att det r till r ckligt avst nd mellan elledningar och motorns styrkablar f r att undvika st rningar OBS S kerst ll r tt polarite...

Страница 5: ...g erfordras vid reng ring Fl ktens lager r underh llsfria och ska endast bytas vid behov Vidreng ring av fl kten f r h gtryckstv tt eller starka l sningsmedel ej anv ndas Reng ring m ste ske p ett s d...

Страница 6: ...fr n skador stiger moduleringen propor kylning av sluten orsakade av alltf r h ga inre tempera tionellt igen regulatorn turer Vid en temperatur kning ver gr nsv rdet reduceras kontrollniv n proportion...

Страница 7: ...men 6 x Rel ej draget IGBT Fel EC enheten st ngs av anslutning Kortslutning mot jord eller kortslut nya f rs k till omstart efter 11 14 ning i motorlindning ca 60 sek Kod 9 bruten Slutgiltig avst ngni...

Страница 8: ...er x EN 61000 6 1 2007 Elektromagnetisk kompatibilitet EMC Generella fordringar Immunitet hos utrustning i bost der kontor butiker och liknande milj er x EN 61000 6 2 2005 Elektromagnetisk kompatibili...

Страница 9: ...andards x EN 61000 6 1 2007 Electromagnetic compatibility EMC Generic standards Immunity for residential commercial and light industrial environments x EN 61000 6 2 2005 Electromagnetic compatibility...

Страница 10: ...by per sons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given super vision or instruction concerning use of the a...

Страница 11: ...n mounting and installation NB Do not start the fan before mounted Before starting the fan the installation must be in spected Consider the placement so there is enough space when open the fan for cle...

Страница 12: ...ro tective ground keep cable short and with as little inductance as possible Pay attention to sufficient distance from power lines and motor wires to pre vent interferences Attention Ensure correct po...

Страница 13: ...is closed and locked before starting Make sure that there is no noise from the fan F A U L T D E T E C T I O N 13 E N G L I S H M A I N T E N A N C E Attention look out for sharp edges and corners Lo...

Страница 14: ...bridged 2 x Energized Active temperature monitoring terminals The device has an active temperature At sinking temperature the Check cooling 11 14 monitoring to protect it from damage modulation rises...

Страница 15: ...ower supply 6 x De energized IGBT Fault EC Controller switches off renewed terminals Shortcut earth or shortcut of motor attempt to start after about 60 sec 11 14 winding Code 9 Final shutoff if inter...

Страница 16: ...dustrigatan 2 Avesta Tel 46 226 860 00 Fax 46 226 860 05 E mail info ostberg com www ostberg com 1270366_utg5_TKV_TKH_SV_EN indd 16 2020 01 07 11 06 17 1270366_utg5_TKV_TKH_SV_EN pdf 16 1270366_utg5_T...

Отзывы: