49
TECHNICAL DATA /
TEKNISKA DATA
See below for explanation of Sound pressure level. / Se nedan för förklaring av ljudtrycksnivå.
SAU 125 C1 EC
SAU 200 B3 EC
SAU 250 B3 EC
Voltage/
Spänning
V
230
400
400
Voltage range/
Spänningsintervall
V
220-240
Frequency/
Frekvens
Hz
50
Phase
/Fas
~
1
Current fan/
Fläktström
A
0.85
Current electric heater/
Ström elwärmare
A
8.7
Current total /
Totalström
A
9.6
Power fan /
Fläkteffekt
W
101
Power electric heater/
Effekt elwärmare
W
2000
Power total/
Total effekt
W
2110
Speed
/Varvtal
Rpm
3540
Sound pressure level/
Ljudtrycksnivå
LpA
45
Weight/
Vikt
kg
20.4
380-415
50
3
0.95
12.5
12.5
122
5000
5130
2860
46
26.0
380-415
50
3
1.37
12
.
5
12.5
166
5000
5180
2970
42
36.1
Wiring diagram
/Kopplingsschema
4040206
4040207
4040207
Duct connection/
Kanalanslutning
mm
Ø125
Ø200
Ø250
Ljuddata har framtagits med följande standarder för ljudmätning:
Tryck och flöde: SS-ISO 5801. Bestämning av ljudeffektnivå i kanal: SS-ISO 5136.
Bestämning av ljudeffektnivå i efterklangsrum: SS-EN ISO 3741.
F Ö R K L A R I N G A R
Ljuddata visar total A-vägd ljudeffektnivå,
LwA
,
samt denna uppdelad i oktavband i
dB(A) (ref 10
-12
W). I ”Tekniska Data”, återfinns total ljudtrycksnivå,
LpA
,
i dB(A) (ref 20 x
10
-6
Pa) beräknat på den totala ljudeffektnivån för aggregatljud vid 230 V.
Relationen mellan ljudtryck och ljudeffekt är
LpA
=
LwA
+ 10 x log
+
där
Q
är riktningsfaktor,
r
är avstånd från aggregatet och
AEkv
är ekvivalent absorbtions-
area. Vid beräkning av
LpA
har det antagits att
Q
=2,
r
=3 m och
AEkv
=20 m
2
, vilket
ger att
LpA
»
LwA
- 7.
Q 4
4
p
r
2
AEkv
( )
The sound data have been compiled by means of sound measurement methods as
follows: Pressure and flow: SS-ISO 5801.Determination of acoustic sound power level in
duct: SS-ISO 5136.Determination of acoustic sound power level in reverberation room:
SS-EN ISO 3741.
D E S I G N A T I O N S
The sound data present the total A-weighted sound power level,
LwA
,
as well as in
octave bands in dB(A) (ref 10
-12
W).
In the ”Technical Data”, the total sound pressure,
LpA
,
calculated from the total surroun-
ding sound power level,
LwA
, at 230 V is presented in dB(A) (ref 20 x 10
-6
Pa).
The relationen between sound pressure and sound power is
LpA
=
LwA
+ 10 x log
+
where
Q
is the propagation factor,
r
is the distance from the unit and
AEkv
is the equi-
valent absorbtion area.
When calculationg the
LpA
it has been assumed that
Q
=2,
r
=3 m and
AEkv
=20 m
2
,
which gives
LpA
»
LwA
- 7.
Q 4
4
p
r
2
AEkv
( )
1270431_utg1_SAU_EC_sv_en.indd 49
2019-01-11 12:53:25
Содержание SAU 125 EC
Страница 7: ...7 REGLERSCHEMAN SAU EC som visar samtliga givare ...
Страница 29: ...29 CONTROL DIAGRAMS SAU EC that shows all sensors ...
Страница 46: ...46 ...
Страница 48: ...48 DIMENSIONS MÅTTSKISSER mm SAU 125 EC SAU 200 EC SAU 250 EC ...
Страница 54: ...54 WIRING DIAGRAM KOPPLINGSSCHEMA 4040206 SAU 125 C1 EC ...