38
SERVICE MENU: “MAX TEMPERATURE”:
Setting the
Max temperature
. This gives a max´ temperature of electrical heater, supply air limit and
temperature in the week timer. The factory setting is 30°C. Possible to change the max temperature to 40°C.
Press in order to go forward from the Service Menu. Press again and then in order to choose
the desired
Max temperatur
(15-40°C). Confirm with .
SERVICE MENU: “ALARM”
In this menu alarm limits is set for
Filter timer, Low temperature
and setting for
Fire sensor, Automatic reset
and
Alarm indication
to the alarm port.
”
Filter timer
” can be set from
”Off”/”6-12 months”
and generates alarm for filter change.
Filter timer can not be used in combination with another filter measurement, see "Filter measurement"menu.
Filter change is recommend at least once a year.
To restart the filter timer press “
Reset
” with the -key.
ENTER
ENTER
UP
UP
DOWN
DOWN
ENTER
i
ENTER
a
ENTER
i
UP
UP
DOWN
DOWN
.
ENTER
-
DOWN
DOWN
ENTER
ENTER
UP
UP
DOWN
DOWN
ENTER
ENTER
BACK
Alarm limits for ”
Low temperature
”.
Alarm limit A
: +2 till +10ºC but must be lower than ”Alarm limit B -1°C”.
The unit is stopped and alarm "Low supply temperature" is displayed when the temperature in supply air duct
(GT7) is lower than set value.
Alarm limit B
: Can be set from +5 to +12ºC but have to be higher than ”Alarm limit A +1°C”.
If the temperature in supply air duct (GT7) is lower than set value the Boost is disable, if activated.
In menu ”
Fire sensor
” type of installed fire sensor is set.
Choose ”Normally open” NO or ”Normally closed” NC depending on the type of smoke detector.
”Automatic reset”
allows a automatic restart of the unit after the fire alarm is restored to normal (NO, NC).
In the menu
”Alarm indication”
, the alarm can be associated to the alarm port at the control board (NO,NC).
If all is selected this is indicated by
”All”
. If only one or more is selected this is indicated by
”Selected”
.
ENTER
UP
UP
DOWN
DOWN
ENTER
UP
UP
DOWN
DOWN
ENTER
ENTER
UP
UP
DOWN
DOWN
ENTER
UP
UP
DOWN
DOWN
ENTER
ENTER
UP
UP
DOWN
DOWN
ENTER
UP
UP
DOWN
DOWN
ENTER
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
1270431_utg1_SAU_EC_sv_en.indd 38
2019-01-11 12:53:19
Содержание SAU 125 EC
Страница 7: ...7 REGLERSCHEMAN SAU EC som visar samtliga givare ...
Страница 29: ...29 CONTROL DIAGRAMS SAU EC that shows all sensors ...
Страница 46: ...46 ...
Страница 48: ...48 DIMENSIONS MÅTTSKISSER mm SAU 125 EC SAU 200 EC SAU 250 EC ...
Страница 54: ...54 WIRING DIAGRAM KOPPLINGSSCHEMA 4040206 SAU 125 C1 EC ...