S E R V I C E M E N U : “ F L O W D I R E C T I O N ”
Make settings if the supply air and extract air are connected on the right or left hand.
Supply air and extract air have to be connected on the same side of the unit.
Note: If HERU is fitted with built-in electrical heater, this can not be done.
Press again and then in order to choose
Left
or
Right
.
S E R V I C E M E N U : “ F R E E Z E P R O T E C T I O N ”
Setting of limit value when freeze protection sensor is installed. The sensor (GT5) is installed at the return pipe
on the heating coil. When 3°C/37°F higher than set point the valve opens completely. If the temperature continues
to fall to set point the unit will stop, but the valve remains open and the pump output remains active.
Press again and then in order to choose
Limit
: (5°C-10°C/41-50°F).
Press again and then in order to choose 'InOutDiff'
:
(1-10°C/34-50°F),
Extract HI:
(19-26°C/66-79°F)
and
Extract LO:
(18-24°C/64-75°F).
S E R V I C E M E N U : “ S U M M E R C O O L I N G ”
If
”Summer Cooling” ”On”
is chosen, the Summer cooling is activated when the extract air temperature is
higher than ”Extract HI” (19-26°C/66-79°F) and outside air is colder than ”Extract - ‘In OutDiff’ (1-10°C/34-50°F
difference between the temperature outside and extract air)".
Summer cooling is deactivated when exhaust air temperature is lower than ”Extract LO” (18-24°C/64-75°F)
or when the outside temperature is warmer than "Extract air - 'InO 1ºC/34°F' ".
If Summer Cooling is activated, water cooling is disabled.
Press again and then in order to choose
On
or
Off
. In order to go forward in “Summer Cooling” press .
Cont.
Cont. next line.