background image

I N S T A L L A T I O N

•  The fan must be installed according to the air direc-
  tion label on the fan.
•  The fan must be connected to duct or equipped with 

a safety grille.

•  The fan should be installed in a safe way and make

sure that no foreign objects are left behind.

•  The fan should be installed in a way that makes ser-
  vice and maintenance easy. N.B.! Consider the

weight and size of the fan.

•  The fan should be installed in a way that vibrations 

not can be transfused to duct or building. To provi-

  de this, use for example a flange.
•  Electrical installations must be made by an authori-
  zed electrician.
•  See Wiring diagram at the lid of the junction box.
•  Electrical installation must be connected to a local-
  ly situated isolator switch or by a lockable main
 switch.
•  Control that the fan is installed and connected elec-
  trically in the right way, grounded and with motor
 protection.
•  For single phase fans a residual current device i used 

(type A).

AC-MOTOR

•  For speed regulation of AC motor a transformer or

thyristor can be connected.

•  The AC motor has a built-in thermal contact.
• The capacitor (only for AC motor) has finite life-
  time and should be exchanged after 45.000 opera-
  tion hours (about 5 years of operation) to secure

maximum function. Defective capacitor can cause 

 damage.

EC-MOTOR

• Speed regulating of EC

motor can be done with
the built-in potentio-

  meter, 0-10 V. 
  An external potentio-
  meter can be connected 
  to the terminal if neces-
  sary. The internal poten-
   tiometer should then 

be disconnected. 

•  Some EC motors has tachometer output one pulse

per revolution.

• 

EMC-COMPATIBLE INSTALLATION OF EXTERNAL 
CONTROL LINES:

 The control cable must not be

longer than 30  m. Screened control cables must
be used when the cable length is longer than
20 m. When using a shielded cable connect the
shielding to one side only, i.e. only to the device
with the protective ground (keep cable short and
with as little inductance as possible!). Pay atten-

  tion to sufficient distance from power lines and 

motor wires to prevent interferences.  

Attention! 

Ensure correct polarity! Never apply 

line voltage to analog inputs!

•  The EC motor has electronically thermal-/over-

  voltage protection.

E N G L I S H