11
RECOMMENDATION
- The mains cable supplied should be used with fixed electric fittings by removing the plug for the
wall socket. (Heat-resistant)
- Mains cable for wall socket should be laid where it is not exposed to harmful contact.
-
For roducts with ≤ 2kW ca acity, a
> 10A fuse / > 1.5# wire should be used*.
For roducts with ≤ 3kW ca acity, a
> 16A fuse / > 2.5# wire should be used (230V).
3.6.4 Fitting instructions
3.6.5 Fitting recommendation
!
WARNING
!
The product should be filled with water before the power is switched on.
!
Fixed electric fittings should be used for installation in new homes or when changing an existing
electrical setup in accordance with regulations. A mains cable with plug for wall socket can be
used when replacing the product without changing the electrical setup.
!
Mains cable should withstand 90°C continuously. A strain reliever must be fitted.
!
CAUTION
!
The product must have a clearance for servicing of 40 cm in front of the cover / 10 cm under
the base plate where it is wall-mounted.
!
In case of damage to the mains cable and plug, it should be replaced with a specially adapted
mains cable from the manufacturer.
Содержание Wally W 100
Страница 67: ...3 1 1 1...
Страница 68: ...4 1 3 18 90 C 1 2 18 40 10...
Страница 71: ...7 3 4 25 40 10 40 10 25 40 3 3 2 7 25 3 4 8 7 7...
Страница 73: ...9 25 3 4 6 18 3 5 5 3 5 6 40 10 18...
Страница 75: ...11 2 10A 1 5 3 16A 2 5 230 3 6 4 3 6 5 90 C 40 10...
Страница 76: ...12 4 1 A B A 4 2 A 4 3 10 5 1 1 4 4 A B C 2 D 4 6 4 90 C 3 A B C 4 5 D 1 90 1 3 4 5 1 2...
Страница 78: ...14 6 1 6 OSO Hotwater AS 7 1 AX 1 5 2 a b c RESET 5 a b 2 3 c 75 C 5 OSO 75 C 5 a b c AX...
Страница 80: ...OSO Hotwater AS Industriveien 1 3300 Hokksund Norway 47 32 25 00 00 oso oso no www osohotwater com...