background image

 

The company reserve the right to alter size, shape and specification without prior notice 

TMS-UT-0804-Z01-4

  

 

page 17 

Continuation... 

Display of external temperature 

Press key (6) 

down 

and release to see external temperature. 

The  Display  shows  the  external  temperature.  The  value  is  shown  for  5  s,  after 
which display reverts to show actual temperature of water in the boiler. 

Offset of currently selected heating curve (see part 3.5.3 page 13) 

Press key (6) 

down

 and hold for 5 seconds to enter offset curve selection menu  

LED  display  will  show  current  offset  in  ˚C.  Offset  doesn’t  affect  maximal  or 
minimal temperature, they are set in absolute values 
By pressing the key (6) up or down it is possible to change offset in steps of 1˚C. 

Factory setting is 0˚C. 
Offset range is from –9 to +20˚C. 

If there is no pressure on the key for more than 5s shown value of offset in ˚C is 
saved. 

Setting the minimum primary temperature inside boiler

 

Press  key  (6) 

down

  and  hold  for  10  seconds  to  select  minimum  primary 

temperature inside boiler. 
Minimum primary temperature starts to blink. 

Factory setting is 45°C for radiator heating. 
Factory setting is 30°C for under floor heating. 

By pressing the key up or down user can select desired primary temperature in 
range  from  10  to  50°C.  Temperature  changes  in  1°C  steps.  If  there  is  no 
pressure on the key for more than 5s the value from the display is saved as the 
desired minimim primary temperature.

 

Displaying software version and factory reset

 

>5 sec

  0

- 1

>5 sec

>10 sec

>5 sec

20

32

>5 sec

<5 sec

>15 sec

1.4

 

Press  key  (6) 

down

  and  hold  for  15  seconds,  LED  will  show  software  version 

and factory reset of central heating parameters will occur. 
 

 
 
 
 

Содержание OSO TERMO PLUS-E

Страница 1: ...The company reserve the right to alter size shape and specification without prior notice TMS UT 0804 Z01 4 page 1 TERMO ELECTRIC BOILER INSTALLATION MANUAL OSO TERMO PLUS E...

Страница 2: ...4 6 CONNECTION PLATE FOR CONTROL EQUIPMENT TEMPERATURE SENSOR PUMP 10 4 6 1 CONNECT ROOM THERMOSTAT PROGRAMMER 10 4 6 2 FIT EXTERNAL TEMPERATURE SENSOR 10 5 SETTING UP BOILERS 11 5 1 CONTROL PANEL INC...

Страница 3: ...nge of heat curves built into its software Once correctly set the heat curve need never be altered Heat curves are set according to the insulation levels of the property A poorly insulated house will...

Страница 4: ...ow 2 Primary return 3 External boiler jacket 4 Boiler 5 Armaflex insulation 6 Electrical heaters 7 Control panel 8 Cable entry point 9 Contactors 10 Expansion vessel 11 Circulation pump 12 Safety valv...

Страница 5: ...A 330 B 930 C 230 D 100 E 65 F 320 34 5 0 25 2 5 240V N 50 60 Hz 2 2 Expansion Vessel Characteristics Volume of Expansion Vessel L Maximum Expansion Vessel Pressure MPa bar Pre charge Pressure MPa ba...

Страница 6: ...ts that may considered hazardous to health and safety Control of Substances Hazardous to Health COSHH 1988 Glues paints and sealants are used in the manufacture of this product and present no known ha...

Страница 7: ...see page 12 No 3 to the wall using suitable plastic plugs and M8 or M10 screws not supplied Decide the position of the bottom of the boiler giving due consideration to the recommended minimum clearan...

Страница 8: ...ncillary components If the capacity of the in built expansion vessel on Plus E is not sufficient for the heating system indicated by pressure increase of 0 6bar when system is heated an additional exp...

Страница 9: ...ol equipment programmer timer thermostats etc MUST be supplied with power from the boiler connections plate see section 4 6 DO NOT supply with power directly from the mains supply In order to connect...

Страница 10: ...vice room thermostat and or programmer is used remove this link Switched live from room thermostat and water heater thermostat must be connected to 4 CH ON 4 6 2 Fit external temperature sensor The ex...

Страница 11: ...many heating elements are active 3 Led diode OK air in boiler If there is no air in the boiler the diode lights green If air appears in the boiler the diode lights red and the boiler shuts down Upon d...

Страница 12: ...ontrol panel Re fit panel protector Re fit the boiler front cover 1 4 2 3 ON OFF Function Pin 1 ON Set heating type to under floor curves from 0 1 to 0 9 are active minimum boiler temperature is set t...

Страница 13: ...oss control units With central heating programmer Honeywell ST6400 Danfoss TP 9 7 day programmer or similar it is possible to program separate periods of central heating from periods for domestic wate...

Страница 14: ...f 0 1 see the diagram on the front plate If there is no pressure on the key for more than 5 seconds the curve displayed is saved Construction date Radiator curve under floor curve Pre 1970 2 0 0 9 197...

Страница 15: ...t lower temperatures when required When setting variable temperatures please be aware that the heating system will take some time to heat up from cold and similarly will remain hot for some time after...

Страница 16: ...re than 5 seconds the curve displayed is saved Limiting maximum power of boiler manually deactivating 1 or more immersion elements Press key 6 up and hold for 10 seconds to limit power level By pressi...

Страница 17: ...ory setting is 0 C Offset range is from 9 to 20 C If there is no pressure on the key for more than 5s shown value of offset in C is saved Setting the minimum primary temperature inside boiler Press ke...

Страница 18: ...heater switch relay is faulty Does DISPLAY show temperature inside boiler NO NO YES Is the temperature of water same as desired YES Wait for boiler to heat up NO Is the room thermostat switched ON YES...

Страница 19: ...ow YES YES Is the operating thermostat defective NO NO Replace the operating thermostat with new YES Please check the following before going through fault finding flowchart Check the installation is c...

Страница 20: ...mmersion heaters change the heaters YES Please check the following before going through fault finding chart Check the installation is correct All isolating valves are open The system is full of water...

Страница 21: ...ater UK Ltd E15 Marquis Court Team Valley Tarding Estate Gateshead Tyne Wear NE11 0RU Tel 0191 482 0800 Fax 0191 491 3655 www oso hotwater com technical uk oso hotwater com sales uk oso hotwater com s...

Страница 22: ...size shape and specification without prior notice TMS UT 0804 Z01 4 page 22 BASIC USAGE SAMPLE FOR CENTRAL HEATING With Termo Plus E electric boiler up to 14 4kw N 50 60Hz and up to 36 kw 415V 3 N 50...

Отзывы: