background image

 

The company reserve the right to alter size, shape and specification without prior notice 

TMS-UT-0804-Z01-4

  

 

page 15 

Conditions experienced 

Curve selection 

Offset 

(radiator heating) 

Offset 

(UFH heating) 

Room temperature is too low

 if the external 

temperature is 

above + 5 

o

C

 

Lower curve by 0.1 

Add with offset 

+ 6 

o

Add with offset 

+ 4 

o

Room temperature is too low

 if the external 

temperature is 

b 5 

o

C and - 5 

o

C

 

Leave the curve 

Add with offset 

+ 3 

o

Add with offset 

+ 2 

o

Room temperature is too low

 if the external 

temperature is 

under - 5 

o

C

 

Higher curve by 0.1 

Leave offset 

o

C  

Leave offset 

o

C  

Room temperature is too high

 if the external 

temperature is 

above + 5 

o

C

 

Higher curve by 0.1 

Lower with offset  

- 6 

o

Lower with offset  

- 4 

o

Room temperature is too high 

if the external 

temperature is 

b 5 

o

C  - 5 

o

C

 

Leave the curve 

Lower with offset  

- 3 

o

Lower with offset  

- 2 

o

Room temperature is too high

 if the external 

temperature is 

under- 5 

o

C

 

Lower curve by 0.1 

Leave offset 

o

C  

Leave offset 

o

C  

 
 
 
5.3.4 Programmable room thermostats & setting variable internal temperatures.  

Central heating is controlled by the heating curve programmed into the Termo E boiler and fine tuned by a room 
thermostat.  
With modern central heating controls such as a programmable room thermostat it is possible to set different room 
temperatures at different times of the day. e.g. to have a lower temperature set during the night. If this system is 
used the heating curve selection is unchanged and the offset of the heating curve should be set to the highest 
room temperature required during the day. (See paragraph above). The programmable room thermostat is then 
set according to the manufacturers instructions to set lower temperatures when required. 

When setting variable temperatures please be aware that the heating system will take some time to heat up from cold and 
similarly will remain hot for some time after the temperatures are reduced or the system is switched off. To optimize comfort 
levels and minimize energy consumption it is suggested to activate the boiler 30 minutes before the set temperature in heating 
system is required and to reduce temperature or switch off 30 minutes before the lower temperature is desired.

 

 

 

 

 

5.5 Protection from freezing  

 
To protect the entire central heating system from freezing (if a building is to be left empty for an extended period 
of time during cold weather), set the boiler to standby mode. The room thermostat or central heating programmer 
must be set to freezing protection mode (usually 5 to 7˚C, depending from room thermostat manufacturer), this 
will allow pump to circulate heated medium through central heating system.  
 

 

 

6. Recommended annual checks (all boilers) 

The safety valve should be checked annually, preferably before the heating season to ensure correct operation 
and avoid accumulation of lime scale. It is not recommended to annually drain the system to protect the system 
from freezing as refilling with fresh water will increase the risk of limescale attack  
We recommend inspection of the boiler once a year by an authorized service engineer. This service is not 
included in the guarantee. During the inspection all electric and water connections should be tightened, the 
system should be vented and – if necessary – filled up, valves and general functionality of the device and safety 
valves should be checked. 
When cleaning the product do not use an aggressive liquid as e.g. gasoline, kerosene or solvent. For the external 
shell and decorative cover, liquid for cleaning plastics or dish washing media may be used. Control panel should 
be cleaned with dry or moist cloth (not wet). 

Содержание OSO TERMO PLUS-E

Страница 1: ...The company reserve the right to alter size shape and specification without prior notice TMS UT 0804 Z01 4 page 1 TERMO ELECTRIC BOILER INSTALLATION MANUAL OSO TERMO PLUS E...

Страница 2: ...4 6 CONNECTION PLATE FOR CONTROL EQUIPMENT TEMPERATURE SENSOR PUMP 10 4 6 1 CONNECT ROOM THERMOSTAT PROGRAMMER 10 4 6 2 FIT EXTERNAL TEMPERATURE SENSOR 10 5 SETTING UP BOILERS 11 5 1 CONTROL PANEL INC...

Страница 3: ...nge of heat curves built into its software Once correctly set the heat curve need never be altered Heat curves are set according to the insulation levels of the property A poorly insulated house will...

Страница 4: ...ow 2 Primary return 3 External boiler jacket 4 Boiler 5 Armaflex insulation 6 Electrical heaters 7 Control panel 8 Cable entry point 9 Contactors 10 Expansion vessel 11 Circulation pump 12 Safety valv...

Страница 5: ...A 330 B 930 C 230 D 100 E 65 F 320 34 5 0 25 2 5 240V N 50 60 Hz 2 2 Expansion Vessel Characteristics Volume of Expansion Vessel L Maximum Expansion Vessel Pressure MPa bar Pre charge Pressure MPa ba...

Страница 6: ...ts that may considered hazardous to health and safety Control of Substances Hazardous to Health COSHH 1988 Glues paints and sealants are used in the manufacture of this product and present no known ha...

Страница 7: ...see page 12 No 3 to the wall using suitable plastic plugs and M8 or M10 screws not supplied Decide the position of the bottom of the boiler giving due consideration to the recommended minimum clearan...

Страница 8: ...ncillary components If the capacity of the in built expansion vessel on Plus E is not sufficient for the heating system indicated by pressure increase of 0 6bar when system is heated an additional exp...

Страница 9: ...ol equipment programmer timer thermostats etc MUST be supplied with power from the boiler connections plate see section 4 6 DO NOT supply with power directly from the mains supply In order to connect...

Страница 10: ...vice room thermostat and or programmer is used remove this link Switched live from room thermostat and water heater thermostat must be connected to 4 CH ON 4 6 2 Fit external temperature sensor The ex...

Страница 11: ...many heating elements are active 3 Led diode OK air in boiler If there is no air in the boiler the diode lights green If air appears in the boiler the diode lights red and the boiler shuts down Upon d...

Страница 12: ...ontrol panel Re fit panel protector Re fit the boiler front cover 1 4 2 3 ON OFF Function Pin 1 ON Set heating type to under floor curves from 0 1 to 0 9 are active minimum boiler temperature is set t...

Страница 13: ...oss control units With central heating programmer Honeywell ST6400 Danfoss TP 9 7 day programmer or similar it is possible to program separate periods of central heating from periods for domestic wate...

Страница 14: ...f 0 1 see the diagram on the front plate If there is no pressure on the key for more than 5 seconds the curve displayed is saved Construction date Radiator curve under floor curve Pre 1970 2 0 0 9 197...

Страница 15: ...t lower temperatures when required When setting variable temperatures please be aware that the heating system will take some time to heat up from cold and similarly will remain hot for some time after...

Страница 16: ...re than 5 seconds the curve displayed is saved Limiting maximum power of boiler manually deactivating 1 or more immersion elements Press key 6 up and hold for 10 seconds to limit power level By pressi...

Страница 17: ...ory setting is 0 C Offset range is from 9 to 20 C If there is no pressure on the key for more than 5s shown value of offset in C is saved Setting the minimum primary temperature inside boiler Press ke...

Страница 18: ...heater switch relay is faulty Does DISPLAY show temperature inside boiler NO NO YES Is the temperature of water same as desired YES Wait for boiler to heat up NO Is the room thermostat switched ON YES...

Страница 19: ...ow YES YES Is the operating thermostat defective NO NO Replace the operating thermostat with new YES Please check the following before going through fault finding flowchart Check the installation is c...

Страница 20: ...mmersion heaters change the heaters YES Please check the following before going through fault finding chart Check the installation is correct All isolating valves are open The system is full of water...

Страница 21: ...ater UK Ltd E15 Marquis Court Team Valley Tarding Estate Gateshead Tyne Wear NE11 0RU Tel 0191 482 0800 Fax 0191 491 3655 www oso hotwater com technical uk oso hotwater com sales uk oso hotwater com s...

Страница 22: ...size shape and specification without prior notice TMS UT 0804 Z01 4 page 22 BASIC USAGE SAMPLE FOR CENTRAL HEATING With Termo Plus E electric boiler up to 14 4kw N 50 60Hz and up to 36 kw 415V 3 N 50...

Отзывы: