background image

6

6. Electrical installation 

- all wiring must conform to current IEE regulations

6.1 Immersion heater Thermostat

The immersion heater is designed as an auxiliary heater as an emergency back-up. Power to immersion heaters 

should not be switched on until the unit is filled with water. All units are fitted with one 3 kW immersion heater which is

located behind the electrical box. Alternative thermostats should not be used, regulations require immersion heaters on

unvented cylinders to be connected with a thermal cut-out. Follow the wiring instructions below connecting the live, 

neutral and earth as indicated. 

The unit must be connected to a minimum 16 amp dedicated permanent supply complying with current I.E.E Wiring regula-

tions, isolation is required via a minimum 20 amp double pole isolation switch with a minimum 3 mm separation required. 

All electrical wiring should be carried out by a competent electrician, using a heat resistant cable (minimum 85°C), and be 

in accordance with the latest I.E.E Wiring Regulations.

Each immersion heater has a working thermostat adjustable be

-

tween 18°C - 70°C (+/- 5°C). A safety cut-out is also incorporated within the thermostat and will operate at 87°C (± 7°C). 

Should this happen, check reasons for thermal cut-out button being released and when satisfied press the reset button.

N

L

Sensor pocket

Immersion

Element

Thermostat

IP21

OSO Hotwater (UK) Limited can not be held respon-

sible if alternative wiring plans are used.

Important: Before resetting the safety cutout or al-

tering the thermostat setting isolate electrical sup-

ply to the unit before removal of the lid. Ensure the 

lid to the electrical box is replaced.

The thermostat must never be dismantled or 

opened. This will compromize its function and may 

cause risk of overheating. Guarantee will cease.

Wiring diagram

Содержание Delta Coil DC 300

Страница 1: ...r AS Industriveien 1 3300 Hokksund Norway Tel 47 32 25 00 00 Fax 47 32 25 00 90 E mail oso oso no www osohotwater com Delta Coil DC VIP 120 150 180 210 250 300 l UK SAFETY INFORMATION O M INFORMATION...

Страница 2: ...ywhere open to frost attack The unit should be placed on a stable flat surface capable of withstanding the weight of the cylinder when full see technical data on page 10 and access must be allowed for...

Страница 3: ...see Table 2 11 Hot Water Outlet 3 4 BSP 12 Elbow Drain Cock 250445 13 Discharge Pipe Not supplied 14 Motorised Valve Not factory fitted 92000 15 Expansion Vessel AX12 18 or 24 Size Length of tube 22...

Страница 4: ...see 3 1 5 above to include a Tee piece if a secondary return is required 3 1 7 Fit the Multibloc 3 to the top of the copper tube see 3 1 6 above 3 1 8 Connect 15mm copper tube from the expansion reli...

Страница 5: ...e unit will drain Draining process may be speeded up by opening the temperature and pressure relief valve An internal 18 mm hose can be applied to lead the water to a gully sink or similar 5 2 System...

Страница 6: ...tch with a minimum 3 mm separation required All electrical wiring should be carried out by a competent electrician using a heat resistant cable minimum 85 C and be in accordance with the latest I E E...

Страница 7: ...valve which will act as a positive energy cut out should the safety cut out operate The motorised valve will also control the temperature of the domestic stored water via the cylinder thermostat which...

Страница 8: ...Pocket is provided see below to se cure the sensor on the Delta Coil cylin der The probe is run through a channel from base of cylinder to the immersion housing The supplied motorised valve must be us...

Страница 9: ...rge from the tundish occurs when water is being heated In this situation maintenance must be car ried out by competent person and the precharge pressure must be restored to the original value An annua...

Страница 10: ...ed on 1 Check and switch on 2 Immersion heater thermal cut out has operated 2 Check and reset button see thermostat diagram page 8 and safety cut out on page 5 of installation manual 3 Programmer set...

Страница 11: ...Max operating temperature on the solar heating coil C 99 99 99 99 99 99 Expansion solution Aquasystem 3 Bar Aquasystem 3 Bar Aquasystem 3 Bar Aquasystem 3 Bar Aquasystem 3 Bar Aquasystem 3 Bar Expansi...

Страница 12: ...12 All replacement parts should be supplied by OSO HOTWATER UK LIMITED For spare parts visit www oso spares co uk www oso hotwater com Delta Product Fiche...

Страница 13: ...Regulations 3 Failure to install and commission this appliance to the manufacturer s instructions may invalidate the guarantee The above does not affect your statutory rights For full details on the H...

Страница 14: ...rdance with European Council Directive 98 83 EC or revised version at the date of installation and is not fed with water from a private supply Particular Chloride content Max 250 mg l Sulphate content...

Страница 15: ...HARGE TESTED IS PRIMARY ENERGY SOURCE CUT OUT FITTED NORMALLY 2 PORT VALVE WHAT IS THE PRESSURE REDUCING VALVE SETTING IF FITTED WHERE IS OPERATING PRESSURE REDUCING VALVE SITUATED NO YES NO YES NO ba...

Страница 16: ...ENTS SIGNATURE DATE ENGINEER NAME SERVICE 5 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 7 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 9 COMPANY NAME TEL No...

Отзывы: