10

8. OSO Fault Finding Guide

Alternative Discharge

Discharge pipes should be in metal and 

dedicated to the unvented cylinder. The pipe 

should have a continuous fall and should terminate 

in a safe and visible place.

Downward discharges at low level, i.e. up to 100 mm above 

external surfaces such as car parks, hard standings, grassed 

areas etc. are acceptable providing that where children may 

play or otherwise come into contact with discharges, 

a wire cage or similar guard is positioned to prevent 

contact, whilst maintaining visibility.

Discharge at high level, i.e. into a metal hopper and metal 

down pipe with the end of the discharge pipe clearly visible (tundish visible or not) 

or onto a roof capable of withstanding high temperature discharges of water and 

3 m from any plastics guttering system that would collect such discharges 

(tundish visible).

Where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited to 

not more than 6 systems so that any installation discharging can be traced reasonably easily. The single common dis

-

charge pipe should be at least one pipe size larger than the largest individual discharge pipe to be connected. For further 

information contact your Building Control Office.

Important - note:

 Disconnect electrical supply before removing any electrical equipment covers.

FAULT   

 

POSSIBLE CAUSE 

 

 

          SOLUTION

No water flow from hot taps.

  1. Mains supply off. 

1. Check and open stopcock.

 

2. Strainer blocked. 

2. Turn off water supply. Remove strainer and clean (see 

 

 

    Servicing Procedure page 10).

Water from hot taps is cold.

  1. Immersion heaters not switched on. 

1. Check and switch on.

 

2. Immersion heater thermal cut-out has operated 

2. Check and reset button (see thermostat diagram page 8

 

 

    and safety cut-out on page 5 of installation manual).

 

3. Programmer set to central heating or not switched on. 

3. Check and set to hot water.

 

4. Boiler not working. 

4. Check boiler operation. If fault suspected consult installer

 

 

    or boiler manufacturer.

 

5. Cylinder thermal cut-out has operated (indirect units only).  5. As at No. 2.

 

6. Motorised valve not operating correctly. 

6. Check wiring and/or plumbing connections to motorised

 

 

    valve (see pages 6 - 9 of the installation manual).

Intermittent water discharge.

  1. Reduced expansion vessel charge. 

1. Follow instruction page 10: “Intermittent or slow water 

 

 

   discharge from tundish”.

Continous water discharge.

  1. Thermal control failure (Note: Water will be hot).  

1. Switch off power to immersion heater(s) and boiler supply

 

 

    to the unit. When discharge has stopped, check thermal

 

 

    controls, replace if faulty. Contact a competent person.

 

2. Cold water inlet Pressure Reducing Valve not working.  

2. Check pressure from valve, if greater than 3 bar replace 

 

 

    (see page 10 of installation manual).

 

3. Temperature and pressure relief valve faulty. 

3. Drain 10 litres from cylinder and replace valve.

 

4. Expansion relief valve not working properly. 

4. Check and replace if faulty (see page 6 of installation manual).

 

 

Minimum size of 

Maximum resistance allowed,  

 

Minimum size of 

discharge pipe D2*  expressed as a lenght of straight  Resistance created by

Valve outlet size  discharge pipe D1*  from tundish 

pipe (i.e. no elbows or bends) 

each elbow or bend

 

 

22 mm 

up to   9 m 

0.8 m

G1/2 

15 mm 

28 mm 

up to 18 m 

1.0 m

 

 

35 mm 

up to 27 m 

1.4 m

 

 

28 mm 

up to   9 m 

1.0 m

G3/4 

22 mm 

35 mm 

up to 18 m 

1.4 m

 

 

42 mm 

up to 27 m 

1.7 m

 

 

35 mm 

up to   9 m 

1.4 m

G1 

28 mm 

42 mm 

up to 18 m 

1.7 m

 

 

54 mm 

up to 27 m 

2.3 m

Table D

Содержание Delta Coil DC 300

Страница 1: ...r AS Industriveien 1 3300 Hokksund Norway Tel 47 32 25 00 00 Fax 47 32 25 00 90 E mail oso oso no www osohotwater com Delta Coil DC VIP 120 150 180 210 250 300 l UK SAFETY INFORMATION O M INFORMATION...

Страница 2: ...ywhere open to frost attack The unit should be placed on a stable flat surface capable of withstanding the weight of the cylinder when full see technical data on page 10 and access must be allowed for...

Страница 3: ...see Table 2 11 Hot Water Outlet 3 4 BSP 12 Elbow Drain Cock 250445 13 Discharge Pipe Not supplied 14 Motorised Valve Not factory fitted 92000 15 Expansion Vessel AX12 18 or 24 Size Length of tube 22...

Страница 4: ...see 3 1 5 above to include a Tee piece if a secondary return is required 3 1 7 Fit the Multibloc 3 to the top of the copper tube see 3 1 6 above 3 1 8 Connect 15mm copper tube from the expansion reli...

Страница 5: ...e unit will drain Draining process may be speeded up by opening the temperature and pressure relief valve An internal 18 mm hose can be applied to lead the water to a gully sink or similar 5 2 System...

Страница 6: ...tch with a minimum 3 mm separation required All electrical wiring should be carried out by a competent electrician using a heat resistant cable minimum 85 C and be in accordance with the latest I E E...

Страница 7: ...valve which will act as a positive energy cut out should the safety cut out operate The motorised valve will also control the temperature of the domestic stored water via the cylinder thermostat which...

Страница 8: ...Pocket is provided see below to se cure the sensor on the Delta Coil cylin der The probe is run through a channel from base of cylinder to the immersion housing The supplied motorised valve must be us...

Страница 9: ...rge from the tundish occurs when water is being heated In this situation maintenance must be car ried out by competent person and the precharge pressure must be restored to the original value An annua...

Страница 10: ...ed on 1 Check and switch on 2 Immersion heater thermal cut out has operated 2 Check and reset button see thermostat diagram page 8 and safety cut out on page 5 of installation manual 3 Programmer set...

Страница 11: ...Max operating temperature on the solar heating coil C 99 99 99 99 99 99 Expansion solution Aquasystem 3 Bar Aquasystem 3 Bar Aquasystem 3 Bar Aquasystem 3 Bar Aquasystem 3 Bar Aquasystem 3 Bar Expansi...

Страница 12: ...12 All replacement parts should be supplied by OSO HOTWATER UK LIMITED For spare parts visit www oso spares co uk www oso hotwater com Delta Product Fiche...

Страница 13: ...Regulations 3 Failure to install and commission this appliance to the manufacturer s instructions may invalidate the guarantee The above does not affect your statutory rights For full details on the H...

Страница 14: ...rdance with European Council Directive 98 83 EC or revised version at the date of installation and is not fed with water from a private supply Particular Chloride content Max 250 mg l Sulphate content...

Страница 15: ...HARGE TESTED IS PRIMARY ENERGY SOURCE CUT OUT FITTED NORMALLY 2 PORT VALVE WHAT IS THE PRESSURE REDUCING VALVE SETTING IF FITTED WHERE IS OPERATING PRESSURE REDUCING VALVE SITUATED NO YES NO YES NO ba...

Страница 16: ...ENTS SIGNATURE DATE ENGINEER NAME SERVICE 5 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 7 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 9 COMPANY NAME TEL No...

Отзывы: