IMPORTANT

READ CAREFULLY BEFORE USE
SAVE FOR FUTURE REFERENCE

EL 160 Eco & EL 500 Eco 

 

– Our new generation of electric boilers with touchscreen 

Installation and Operating Instructions

Osby Parca 

Tel. no.: +46 (0)479 177 00 | [email protected] | www.osbyparca.se | Box 93, 283 22 Osby, SWEDEN

The Professional’s Choice Since 1935

MADE IN
SWEDEN

Содержание 7700130-01-31

Страница 1: ...E REFERENCE EL 160 Eco EL 500 Eco Our new generation of electric boilers with touchscreen Installation and Operating Instructions Osby Parca Tel no 46 0 479 177 00 sales osbyparca se www osbyparca se...

Страница 2: ......

Страница 3: ...____________________ 28 8 1 Factory set values __________________________ 28 9 Menu overview _______________________ 29 10 Detailed menu descriptions____________ 35 10 1 Home screen __________________...

Страница 4: ...4 EL 160 Eco EL 500 Eco...

Страница 5: ...nstaller This will enable the electric boiler to function in good condition for a long time It will then produce the heat you need at the lowest total cost for many years to come Contact info service...

Страница 6: ...re performing any work on the product Please note that the boiler requires both 400 V supply along with 230 V supply for the control system The product may not be rinsed with water When handling the p...

Страница 7: ...r water However the addition of glycol reduces the heat capacity of the water i e to gain full output the flow must be increased There are different types of glycol but as a rule of thumb the followin...

Страница 8: ...rician NOTE The boiler s electrics must not be put into operation until the water system is full and the boiler has been bled 1 3 Installation Ventilation The electric boiler must be placed in an area...

Страница 9: ...iler s contactors and release the circuit breakers The max thermostat is reset at about 70 C Before the boiler has cooled down it is not possible to reset the circuit breaker and acknowledge the alarm...

Страница 10: ...ventual warranty claim The control system s service timer assists with keeping track of servicing intervals provided the correct values have been set Work in the boiler s electrical system may only be...

Страница 11: ...fication of image on p 12 NOTE Applies to both models even if only shown in the Instructions for re tightening for EL 160 Eco Date Set value IR A Signature Charateristics recommended set value is 1 re...

Страница 12: ...structional images for re tightening 9 10 Contactores AF52 4 Nm AF38 2 5 Nm AF26 2 5 Nm AF12 1 5 Nm AF09 1 5 Nm 12 Immersion heaters 1 8 Nm Magnification circuit breaker NOTE Important 2b 8 Nm 3 8 Nm...

Страница 13: ...ructions for re tightening Osby Parca EL 500 Eco 3 2 8 Nm 4 Immersion heaters 1 8 Nm 2 0 8 Nm 7 8 Contactores AF52 4 Nm AF65 4 Nm 6 8 Nm 1 50 95 mm2 20 Nm 120 300 mm2 45 Nm 5 Against rail 20 Nm 10 26...

Страница 14: ...se for control circuit 230 V 16 A 5 Technical Data 5 1 Technical data EL 160 Eco 72 156 kW 5 1 1 Design data EL 160 Eco 5 1 2 Pressure drop Water resistance EL 160 Eco Art No Output 1 st Step Steps Vo...

Страница 15: ...he ceiling should not be less than 900 mm 5 1 3 Dimensions Connections EL 160 Eco S safety valve being discontinued on std versions 1 Supply flow conn 50 ext thread 2 Return flow conn 50 ext thread 3...

Страница 16: ...1 0 0 0 30 3 32 30 1 1 0 0 0 43 4 45 42 0 1 1 0 0 61 5 55 51 1 1 1 0 0 74 6 68 63 0 1 1 1 0 91 7 77 72 1 1 1 1 0 104 8 90 84 0 1 1 1 1 121 9 100 93 1 1 1 1 1 134 7700130 03 33 Kw 9 21 21 21 42 R 1 R...

Страница 17: ...1 1 165 12 93 126 0 1 1 1 1 182 13 100 135 1 1 1 1 1 195 7700130 05 35 Kw 9 21 42 42 42 R 1 R 2 R 3 R 4 R 5 CURRENT Step kW K1 K2 K3 K4 K5 A 1 6 9 1 0 0 0 0 13 2 13 21 0 1 0 0 0 30 3 19 30 1 1 0 0 0 4...

Страница 18: ...00 V 310 380 7700151 02 32 252 21 12 400 V 382 380 7700151 03 33 315 21 15 400 V 477 390 7700151 04 34 378 21 18 400 V 573 400 7700151 05 35 441 21 21 400 V 668 405 7700151 06 36 504 21 24 400 V 763 4...

Страница 19: ...welding conn 2 Return flow DN100 welding conn 3 Drainage R1 ext 4 Connection slot 4 x PG11 5 Flange opening 1 pc FL 21 6 Safety valve 6 bar DN 25 32 Only in S Minimum distance of 900 mm between boile...

Страница 20: ...1 105 0 0 1 1 0 9 59 120 1 0 1 1 0 10 62 126 0 1 1 1 0 11 69 141 1 1 1 1 0 12 82 168 0 0 1 1 1 13 90 183 1 0 1 1 1 14 93 189 0 1 1 1 1 15 100 204 1 1 1 1 1 7700151 02 32 El 500 Eco 252 kW 400 V 3 phas...

Страница 21: ...0 1 1 1 1 14 93 294 0 1 1 1 1 1 15 100 315 1 1 1 1 1 1 7700151 04 34 El 500 Eco 378 kW 400 V 3 phase kW 21 42 63 63 63 63 63 Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Relay 7 Steg kW K1 K2 K3 K4...

Страница 22: ...0 4 19 84 1 0 1 0 0 0 0 0 5 24 105 0 1 1 0 0 0 0 0 6 29 126 0 0 1 1 0 0 0 0 7 33 147 1 0 1 1 0 0 0 0 8 38 168 0 1 1 1 0 0 0 0 9 43 189 0 0 1 1 1 0 0 0 10 48 210 1 0 1 1 1 0 0 0 11 52 231 0 1 1 1 1 0 0...

Страница 23: ...0 0 6 25 126 0 0 1 1 0 0 0 0 0 7 29 147 1 0 1 1 0 0 0 0 0 8 33 168 0 1 1 1 0 0 0 0 0 9 38 189 0 0 1 1 1 0 0 0 0 10 42 210 1 0 1 1 1 0 0 0 0 11 46 231 0 1 1 1 1 0 0 0 0 12 50 252 0 0 1 1 1 1 0 0 0 13 5...

Страница 24: ...24 EL 160 Eco EL 500 Eco 5 2 5 Example of power limitation...

Страница 25: ...n Max thermostat 3 1 204 504 kW Safety valve DN 25 32 6 bar 1 Pressure transmitter DN 15 1 Overheating protection Max thermostat 3 1 6 1 Design Design in accordance with this description as well as SS...

Страница 26: ...nsmitter with an outgoing signal of 4 20 mA and a relay controlling that the pressure is within stated range The protection closes a contact in the safety loop if the pressure is within valid range If...

Страница 27: ...Alarm Battery powered 584196401 2 Outdoor temperature sensor incl 15 m cable 585513301 3 BMS Internet module 1118404 01 4 3 current sensors for secondary measurement Max 5A Excl current transformer 33...

Страница 28: ...in the Eco series come with factory set values as standard These are monitored by the control system which constantly ensures optimal functionality and economical operation These values can be easily...

Страница 29: ...29 EL 160 Eco EL 500 Eco 9 Menu overview Home screen Advanced settings menu Operating time energy calculator and highest boiler temperature menu Alarm menu Alarm Alarm Missing Missing Missing...

Страница 30: ...30 EL 160 Eco EL 500 Eco Advanced settings menu Time date and language menu Settings menu Define system menu Quick start menu...

Страница 31: ...31 EL 160 Eco EL 500 Eco Setting type menu BMS communication menu...

Страница 32: ...32 EL 160 Eco EL 500 Eco Service menu...

Страница 33: ...33 EL 160 Eco EL 500 Eco Alarm menu Alarm description menu Operating history menu Graph and chart menu Alarm Alarm Missing Missing Missing B T O T F T...

Страница 34: ...34 EL 160 Eco EL 500 Eco Define system menu...

Страница 35: ...trol panel The large icons function as buttons on the touchscreen Operational and temperature information is also displayed here You can easily access the different menus to view operational informati...

Страница 36: ...disruptions are indicated by the alarm icon flashing red When the icon is pressed the menu displaying the active alarm is opened The arrows can be used to highlight the alarm you wish to investigate...

Страница 37: ...d is the primary flow temperature Blue is the boiler temperature 10 5 Advanced B T O T F T This menu contains five submenus Time Language Settings Define System Service and Quick Start Also displayed...

Страница 38: ...Absolute over temp limit 0 105 C Heating curve inclination 30 60 C Heating curve adjustment 10 10 C Max boiler temperature 40 100 C Mains fuse size 16 2000A Main current margin 0 50A BMS communication...

Страница 39: ...transformer ratio 1 10 1000 Sec current transformer ratio 2 5 fixed value BMS connection active disabled Heat exchanger used yes no Tariff active closed contact disabled External control Start Stop a...

Страница 40: ...to the main menu Inputs 230 V Safety circuit Tariff Outdoor sensor Room sensor external Start Stop Boiler temp sensor Internal temp sensor relay board External set point Phase current L1 Phase current...

Страница 41: ...umber of produced kWh and shows a reset prompt Pressing OK resets the calculator to zero PIN code is required to access the menu 10 10 6 Reset history The menu shows a reset history prompt Pressing OK...

Страница 42: ...low value U16 R Always displays 2015 6 Serial no high value U16 R 7 Serial no low value U16 R 8 Operating time high value U16 kh R Max 64 Mh 7 300 years 9 Operating time low value U16 0 1 h R 10 Highe...

Страница 43: ...Outdoor Compensation UTK Once an existing sensor has been defined the outdoor temperature will be displayed in the main menu The heating curve defines the starting value for the boiler temperature Th...

Страница 44: ...en set to 55 C The lowest temperature is 27 C summertime compensation or systems unable to tolerate very high temperatures 10 11 1 Heating curve ascension inclination The curve can be set between 30 a...

Страница 45: ...load section Stage duration Stage duration can be increased in the Settings menu NOTE Initial stage duration cannot be adjusted or changed It is fixed at 16 seconds 10 13 Delta T deadband The function...

Страница 46: ...changes the regulator follows the signal and shifts up every 16 seconds 10 16 Output control 10 17 Current limitation If necessary the output of the boiler can be limited when for example the current...

Страница 47: ...ed E05 Outdoor temp sensor E06 External control signal deviation E07 Safety circuit tripped E08 Boiler temperature too high E09 Communication error relay board E10 Communication error BMS E11 Phase L1...

Страница 48: ...20 27100 15 33540 10 41800 5 52400 0 66200 5 84750 10 108000 15 139000 20 181000 25 238000 Boiler temp sensor NTC 22 Temperature C NTC 22 Resistance k 70 32 65 37 60 43 55 51 50 60 45 72 40 85 35 102...

Страница 49: ...2000 14 1 Immersion heater 21 kW 400 V 2 thread 900 7616507 01 O ring EPDM 70 g peroxide Air filter fan control system Boiler model Art no Designation EL 160 Eco 3381 0302 Replacement filters EFA200 5...

Страница 50: ...with Direktiven 2014 30 EU EMC direktivet och 2014 35 EU L gsp nningsdirektivet Directive 2014 30 EU EMC directive and 2014 35 EU Low Voltage Directive Ecodesign 811 2013 EU labelling and 813 814 2013...

Страница 51: ...ktiven 2014 30 EU EMC direktivet och 2014 35 EU L gsp nningsdirektivet Directive 2014 30 EU EMC directive and 2014 35 EU Low Voltage Directive Ecodesign 811 2013 EU labelling and 813 814 2013 EU Commi...

Страница 52: ...AB Osby Parca div Tel no 46 0 479 177 00 sales osbyparca se www osbyparca se Box 93 SE 283 22 Osby SWEDEN Subject to errors or updates made after this edition 14 Appendices Circuit diagram Warranty d...