Page 28
Installation and Operation Manual - Matrix 2700 Insert
ENGLISH
9.1 Installation of a Combustible Mantel Shelf
It is possible to install a combustible shelf with a maximum
depth of 12" (305 mm) at a height of at least 12" (305 mm)
above the insert.
At a height of more than 12" (305 mm), the shelf must still
have a maximum depth of 12" (305 mm). The height of the
shelf is measured from the top of the faceplate, with or
without the projection kit.
9.2 Floor Protection
9.2.1 Without a projection kit
The standard configuration of the insert does not include any projection of the insert in front of
the fireplace opening.
It is necessary to have a floor protection made of non-combustible materials without R factor
respecting the measures indicated in the table below. This table may be used only if the masonry
hearth is raised at least 5"(127 mm) above the combustible floor.
Table 2 : Floor Protection
FLOOR PROTECTION
Canada
USA
B
13
18" (457 mm)
16" (406 mm)
M
8" (203 mm)
N/A
N
N/A
8" (203 mm)
N
M
B
DOOR
Figure 11: Floor Protection
To determine the need to add floor protection
(D)
beyond the hearth extension
(A)
, the following
calculation must be done using the data in
«Table 3 : Data for Floor Protection Calculation»
of
this section: D = B - G, where G = A-C.
13
From door opening. The depth of the hearth extension in front of the insert is included in the calculation of the floor protector’s dimensions.
12"
(305 mm)
MIN
.
12"
(305 mm)
MAX
.
Содержание MATRIX 2700 INSERT
Страница 2: ......
Страница 6: ...Page 6 Installation and Operation Manual Matrix 2700 Insert ENGLISH CERTIFICATION PLATE ...
Страница 50: ...Page 50 Installation and Operation Manual Matrix 2700 Insert ENGLISH 5 Remove the blower ...
Страница 57: ...Page 57 Installation and Operation Manual Matrix 2700 Insert ENGLISH NOTES ...
Страница 58: ...NOTES ...
Страница 59: ......