LOCATION OF THE UNIT

Energy Recovery Ventilators

MODEL

 

OD

-ERV 150AC

Instruction Manual

1-888-543-6473
1-888-541-6474

13376 Comber Way 

Surrey BC V3W 5V9

[email protected] 
www.ortechindustries.com

375 Admiral Blvd

 

Missis

s

auga

ON L5T 2N1

Select a location so that:

The fresh air inlet from the outside is placed a minimum of 10 feet from any other exhaust vent

The two ducts to the outside are as short and straight as possible for the best system performance

The door can be opened to clean the core and filters conveniently. Provide clearance at front of unit for service access to the  

blowers, filters and energy exchange core (minimum 20-1/8" for full door swing, 14-1/4" for door removal from hinges)

The exhaust outlet to the outside and fresh air inlet from the outside of the building should be at least ten feet apart to 

avoid cross-contamination. The exhaust duct should be about the same length as the fresh air duct

The exhaust outlet should NOT dump air into an enclosed space or into any other structure

Th

e preferred mounting location for the unit is on a concrete foundation wall because the foundation wall isolates any blower 

vibration. If a basement area is not available or practical, use other mechanical room space such as a closet, garage, storage, or 
accessible attic or crawl space.

** If you locate the unit in an attic or other unconditioned space, all of the unit's ductwork that is located in the attic MUST be

** 

insulated.

 Use at least R-6 insulation

INSTALLATION GUIDE

CAUTION!

RISK OF INJURY WHEN LIFTING AND INSTALLING UNIT OVERHEAD:

Get a helper and wear eye protection and gloves.

Locate the unit for the simplest duct layout and connections. 

Note that the door is equipped with hinges. For the 

homeowner's convenience, it is helpful to locate the unit so that 

the door does not drop off when it is unlatched.

Unit Installation

Installation A

a1) Mount the 4 brackets to the unit as illustrated at right,

a1) 

using two screws provided for each bracket through

a1) 

2 appropriate holes. Unit may be installed in any orientation.

a1) 

Be careful as condensation could be present when outdoor

a1) 

temperature is low

a2) Secure the unit to the truss by screws provided through the

a2) 

smaller hole of the brackets

Installation B

b1) Trace a level line on both trusses, at 1-1/16" from the bottom

b1) 

(based on the ceiling sizes is 1/2", if not this size, needs to be

b1) 

adjusted properly), for the unit bracket location.

b1) 

On one truss, screw half way on level line two provided screws,

b1)

 leaving 24-7/8" between each other

b2) Mount the 4 brackets to the unit as illustrated on the right,

b2)

 using 2 screws provided for each bracket through 2 appropriate holes.

b2)

 Screw half way the screws to allow adjustment between trusses within

b2)

 23" and 21-1/4" (left shows the minimum distance and right the

b2)

 maximum distance)

24-7/8" (632mm)

24-7/8" (632mm)

1-1/16"

(27mm)

Содержание OD-ERV 150AC

Страница 1: ...rces of hazardous air such as auto exhausts 8 Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment is located take steps to assure that combustion air supply is not affected Follow the heating equipment manufacturer s requirements and the combustion air supply requirements of applicable codes and standards 9 When cutting or drill...

Страница 2: ...he energy exchange core stays clean even if the core faces are covered with dust CAUTION DO NOT WASH THE ENERGY EXCHANGE CORE The energy exchange core can be replaced but is expensive The core is secured to the unit by the core latch when the unit is installed as installation B If the core latch is disengaged the core can fall out causing damage or injury if not prepared after the door swinging do...

Страница 3: ... check cycle The orange L2 LED indicator light will illuminate continuously The check cycle will run the RA fan for 5 minutes at full speed every 15 minutes 25 of every hour in order to minimize frost on the core and meet code requirements The OA fan will not run during this check cycle The HVAC AHU blower if connected will NOT run during this check cycle to prevent cycling The MOS will still boos...

Страница 4: ...tion of the HVAC system in a residence the speed controls should be re calibrated for optimum performance If the residence undergoes significant structural changes such as an addition to the home the unit should also be re calibrated If optional MERV 13 filters are installed recalibration is also required The unit provide the ability to deliver completely balanced airflows or to modify them as des...

Страница 5: ...nit in an attic or other unconditioned space all of the unit s ductwork that is located in the attic MUST be insulated Use at least R 6 insulation INSTALLATION GUIDE CAUTION RISK OF INJURY WHEN LIFTING AND INSTALLING UNIT OVERHEAD Get a helper and wear eye protection and gloves Locate the unit for the simplest duct layout and connections Note that the door is equipped with hinges For the homeowner...

Страница 6: ...a hallway or stairway rather than in a sitting area If you want to get fresh air into specific room with high occupancy you can split up the fresh air supply For Houses WITH Forced air Heating and Cooling Systems see Fig 1 Fig 3 and Fig4 Most units are installed with the fresh air duct connected directly to a return duct for the main heating and cooling system Make sure to connect the fresh air du...

Страница 7: ...mneys furnace and water heater exhausts or other sources of contamination or carbon monoxide NEVER locate the fresh air inlet inside a structure Installing Return Air RA Ducts All the stale air returns are connected by ducts to the unit Generally empty stud cavities are used for returns as is often done with cold air returns for the furnace using standard duct boots to connect to six inch pipe at ...

Страница 8: ...he HVAC AHU 24V AC dry contact relay to the terminal block so that when the ERV is operating the HVAC AHU blower operates to help distribute the fresh air through the existing ductwork if needed The unit has an optional terminal block for a MANUAL OVERRIDE SWITCH MOS connection Connect an ON OFF switch to the terminal block to manually switch the unit to high speed When the switch is off the unit ...

Отзывы: