background image

Instruction Manual

1-888-543-6473
1-888-541-6474

13376 Comber Way 

Surrey BC V3W 5V9

[email protected] 
www.ortechindustries.com

375 Admiral Blvd

 

Missis

s

auga

ON L5T 2N1

Test Your Work

Why Perform This Test?

If you miswired a GFCI, it CANNOT be reset, the green indicator
LED will be ON, by which it may prevent personal injury or death
due to a ground fault (electrical shock)

INSTALLATION GUIDE

Receptacles

MODEL

 

MH

20

-ST

If you 

mistakenly connect the LINE wires to the LOAD

 

terminals, the

GFCI will NOT provide power to 

neither

 the outlet of the

 

GFCI 

n

or

the

 

load terminals fed through the GFCI

Procedure

a)

After finishing the connection of wires and supply the power,
press the RESET button fully and plug in a lamp or radio into the
GFCI to verify that the GFCI is wired correctly (and leave it
plugged-in) to verify that the power is ON. If the GFCI had been
wired properly, it can be reset and supply the power to the outlet
and the load terminals of the device.

b)

Press the TEST button in order to trip the device. This should stop
the flow of electricity, making the radio or lamp shut OFF. Note
that the RESET button will pop out. If the power stays ON, go to
Troubleshooting. If the power goes OFF, you have installed the
GFCI receptacle correctly. To restore power, press the RESET
button; the GREEN indicator LED will be on.

c)

If you installed your GFCI using step 

"Connecting the Wires B:

 

Two

cables (4 or 6 wires) entering the box", plug a lamp or radio

 

into

surrounding receptacles to see which one(s), in addition to

 

the

GFCI, lost power when you pressed the TEST button. DO NOT

 

plug

life saving devices into any receptacles that lost power. Place

 

a

"GFCI Protected" sticker on every receptacle that lost power.

d) The GFCI includes an end-of-life monitoring function.

d)

Once the

 

GFCI has been correctly wired and powered,

 the red LED

d)

will flash one time within 5 sec, and the internal self-testing circuit

d)

will launch every 1-10 min. When the GFCI displays an alarm during

d)

its operation, the red light will turn ON immediately, and it will no

d)

longer provide a ground fault circuit protection, reminding the user

d)

that the GFCI is end of life and MUST be replaced.

e) Press the TEST button (then RESET button) monthly to ensure a

e)

proper operation. If the GREEN LED goes OFF when tripped, it

e)

means that the GFCI can still offer a ground fault circuit protection,

e)

the testing circuit is connected to the end-of-life monitoring circuit in

e)

a GFCI. Press the TEST button and cut off the power within the

e)

predetermined time, then press the RESET button to connect with

e)

the testing circuit. If the GFCI can provide ground fault circuit

e)

protection, it can be reset and supply the power to the outlets and

e)

the load terminals. If it fails to be reset, it reminds the user that GFCI

e)

has reached its end of life and should be replaced by a new one.

1) A GFCI ends its life when it fails to supply power, although the Line and Load are wired correctly.

If it happened, press TEST button manually, force to trip and cut off the power and replace it by a new one

2) A GFCI has reached its end of life when it cannot be reset, although the Line and Load are wired correctly. Please replace it by an new one

TROUBLESHOOTING

Turn the power OFF and check the wire connections against the 
appropriate wiring diagram in step "Connecting the wires (choose A 
or B)". Make sure that there are no loose wires or loose connections.

Also, it is possible that you reversed the LINE and LOAD connections if 

the GFCI cannot be reset and there is no power at the receptacle. Start 

the test from the beginning of step "Test your work" if you rewired any 

connections to the GFCI.

ORTECH reserves the right to modify at any time, without notice,

 

any or all of our product's 

features, designs, components and specifications to meet market changes.

Содержание MH20-ST

Страница 1: ...l electrical codes 2 A GFCI receptacle does NOT protect against circuit overload short circuits or shocks 3 In the event of a ground fault a GFCI will trip and quickly stop the flow of electricity to prevent serious injury 4 You can still be shocked if you touch bare wires while standing on a non conducting surface such as an wooden floor 5 For installation in wet locations protect the GFCI recept...

Страница 2: ...tion A or B see the diagram below Procedure Box with Two Cables 4 6 wires a Detach one cable s white and hot wires from the receptacle and cap each one separately with a wire connector Make sure that they are from the same cable b Re install the receptacle in the electrical box attach the faceplate then turn the power ON at the service panel c Determine if power is flowing to the receptacle If so ...

Страница 3: ...e WHITE wire connects to the WHITE terminal Silver The BLACK wire connects to the HOT terminal Brass Connect the grounding wires only if there is a grounding wire Connect a 6 bare copper or GREEN 12 or 14AWG wire to the grounding terminal on the GFCI If the box has a grounding terminal also connect a similar wire to the grounding terminal on the box Connect the ends of these wires to the LINE and ...

Страница 4: ...red and powered the red LED d will flash one time within 5 sec and the internal self testing circuit d will launch every 1 10 min When the GFCI displays an alarm during d its operation the red light will turn ON immediately and it will no d longer provide a ground fault circuit protection reminding the user d that the GFCI is end of life and MUST be replaced e Press the TEST button then RESET butt...

Отзывы: