A dedicated room with
restricted access
Electrically grounded
and
mechanically stable rack
, with
physical clearance
for
unrestricted air flow and servicing: approx. 650 mm [25”] in front of rack, 770 mm
[30”] in the back of rack
Clean,
dust-free
, and
stable
1
ambient temperature
not to exceed 35°C [95°F].
Virtually free of
EMC noise
Access to a reliable
grounded power outlet
Sufficiently dimensioned
power supply circuitry
, to prevent overloading of circuits.
The use of a regulating
UPS
(Uninterruptible Power Supply) is recommended.
Next Steps:
before
familiarizing yourself with the procedure for the
.
2.3
Rack Mounting: SAFETY
.
Before installing VelaSync in the fully extended rails, or before extending the unit
from the rack, ensure that the rack is stable enough to support the weight of the
fully extended unit. If you are using a standalone rack, it may be necessary to install
stabilizers to the rack.
Always extend only one unit at a time.
Install heavier servers near the bottom of the rack.
The unit weighs approximately 24 lbs (11 kg). Depending on your chosen installation
location, it may be advisable to lift the unit with two persons.
2.4
Rack Installation
Note:
We recommend that you read this Chapter in its entirety before you
begin with the installation.
1
An environment where a constant temperature can be maintained during operation, to allow for the best possible timing
accuracy.
2.3 Rack Mounting: SAFETY
CHAPTER
2
•
VelaSync 1232 User Manual Rev. 4
25
Содержание Spectracom VelaSync 1232
Страница 2: ......
Страница 4: ...Blank page II VelaSync 1232 User Manual...
Страница 12: ...BLANK PAGE X VelaSync 1232 User Manual TABLE OF CONTENTS...
Страница 28: ...16 CHAPTER 1 VelaSync 1232 User Manual Rev 4 1 7 The VelaSync Web UI...
Страница 34: ...BLANK PAGE 1 9 Regulatory Compliance 22 CHAPTER 1 VelaSync 1232 User Manual Rev 4...
Страница 264: ...BLANK PAGE 252 VelaSync 1232 User Manual...