Adding user ID cards and access codes
(The PIN number can be any 4-6 digit number in the
range 0000-999999 except for the code "1234").
Add a card in the same way as in card mode or code mode (302#).
Press
*
to enter programming mode.
Then assign a PIN code to the card according to the scheme:
* Read card 1234 # PIN code # PIN code #
Changing the PIN access code (can be done out of programming mode, without the involvement of the system administrator)
Method 1
Note: this operation must be performed out of the
programming mode so that the user can do it
themselves.
* Read card Old PIN code # New PIN code # New PIN code #
Method 2
Note: this operation must be performed out of the
programming mode so that the user can do it
themselves.
* ID Number # Old PIN code # New PIN code # New PIN code #
Deleting PIN code and ID card (simply delete only the
card from the system)
2 ID Number #
Adding and deleting users in card-only mode (proximity tag) 300#
Adding or deleting users
Proceed in the same way as in the card or code mode (302#)
Deleting
all users
Delete
all users
. Note: this function is irreversible. Please
think twice before performing it.
2 0000 #
Door opening
It is possible to program the code lock to operate in one of two relay activation modes: monostable and bistable.
Monostable mode
4 time from 01 to 99 seconds #
This is the mode set by default. When a valid card (proximity tag) is placed close to the reader or a
valid access code is entered, the output relay's latch is released for a pre-programmed time period
and then locked again until a valid card (proximity tag) is brought close again or a valid access code
is entered. The factory setting is 6 seconds. You can enter a value between 1 and 99 seconds.
Bistable mode
4 0 #
In this mode, when a valid proximity card (proximity tag) is brought close to the reader or a valid
access code is entered, the exit relay bolt is released and remains in this state until a valid ID card
is brought close again or a valid access code is entered (the card/code alternately releases and
locks to the premises).
Alarm setting
Alarm duration adjustment (1-3minutes)
Factory setting is 3 minutes.
5 0
~
3 #
Door opening detector setting
To use the function, connect the open door detector
(contracton) to the magnetic lock and then select one of
the sequences in the programming mode:
6 0
0 #
deactivation of the function (factory setting)
6 0
1 #
deactivation of the function
There are 2 programming functions that operate in this mode.
a. If the door is not closed when opened, the keypad buzzer will operate.
b. If the door has been forcibly opened, the keypad buzzer will operate and the alarm
will sound
Security function setting
There are two options for securing the device's keypad:
7 0 1 # reading of 10 invalid cards or entering consecutively 4 wrong access codes
(PIN) locks the keypad for 10 minutes
7 0 2 # reading of 10 invalid cards or entering consecutively 4 wrong passwords
triggers the keypad buzzer and activates the alarm signal
Deactivation of function
7 0 0 # Factory setting, does not delete users
Reset the device to factory settings
To reset the device, press and hold the * button on the keypad and connect to the power supply. You will hear three beeps (two short and one
long) which will indicate that the device has been reset correctly. A long beep will sound when the button is released.
Resetting the device does not delete the users but deletes the MASTER CODE.