IG-262-EN versión 02; 26/04/2018
7
General instructions
pfu
for large-sized applications
Normal service conditions
4. Normal service conditions
The
pfu
is designed for use in normal service conditions in
accordance with Standard IEC 62271-1.
In the enclosure, it is understood that normal indoor service
conditions in accordance with Standard IEC 62271-1 prevail.
Installation
Outdoor
Solar radiation
1000 W/m
2
Pollution due to corrosive and/or flammable gases
Level II (medium)
Vibrations due to seismic movements or caused by
external causes
Negligible
Wind speed
< 34 m/s
Table 4.1.
Normal service conditions