INSTALLATION 

 
Before 

connecting

 the boiler, perform the following operations: 

  Thoroughly  clean  all  the 

system  pipes

  in  order  to  remove  any  foreign  matter  that  could  affect  correct 

operation of the boiler; 

 

Check that the 

flue

 has an 

adequate draught

, that there is no narrowing of passages and that it is free 

from  debris;  also  check  that  other  appliances  do  not  discharge  into  the  flue  (unless  designed  to  serve 
several utilities). See the regulations in force.

 

 
 

4.1  BURNER 

 

Before installation you are advised to thoroughly clean the inside of all the fuel supply system pipes in order 
to  remove  any  foreign  matter  that  could  affect  correct  operation  of  the  boiler.  See  technical  specification 
tables and check the max pressure value inside the furnace. The value found on the table may also increase 
by 20% if heavy oil is used instead of gas or light oil; furthermore the following checks should also be carried 
out:

 

a)  Check the internal and external seal of the fuel supply system; 
b)  Regulate the fuel flow according to the power required by the boiler; 
c)  Check that the boiler is fired by the correct type of fuel; 
d)  Check that the fuel supply pressure is within the values specified on the burner rating plate; 
e)  Check that the fuel supply system is sized for the maximum flow rate necessary for the boiler and that it 

is provided with all control and safety devices provided for by the regulations referred to above; 

f)  Check  that  the  boiler  room  vents  are  sized  in  order  to  guarantee  the  air  flow  established  by  the 

regulations referred to above and that they are in any case sufficient to obtain perfect combustion. 

In particular, when using gas: 
g)  Check that the feeding line and the gas ramp comply with the regulations in force; 
h)  Check that all the gas connections are sealed; 
i)  Check that the gas pipes are not used as earth connections for electrical appliances. 
If the boiler is not going to be used for some time, close the fuel supply cock or cocks. 

 

IMPORTANT: verify that the spaces between the burner sleeve and the plug are suitable filled with flame-
resistant ceramic insulation (Fig. 1). 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

All details on the draught tube length (

P6

), the diameter of the burner hole (

Øb

) and the pressurization are included 

in the par. Technical  Specifications. 

 
 

    3 

 

Key: 

1.  Burner 
2.  Door 
3.  Insulating material 
4.  Flange 

 

P6 

Ø

b

 

Содержание SCP PLUS 3000

Страница 1: ...TECHNICAL MANUAL The above picture is only for reference SCP PLUS THREE PASS WET BACK HOT WATER BOILER ...

Страница 2: ...ions 3 2 2 Drawing 4 3 ACCESSORIES 5 3 1 THERMOSTATS 5 3 2 MANOMETER 5 3 3 THERMOMETER 5 4 INSTALLATION 6 4 1 BURNER 6 5 STARTING 7 5 1 PRELIMINARY CHECKS 7 5 2 WATER TREATMENT 7 5 3 FILLING THE SYSTEM 7 6 OPERATION 8 6 1 OPERATION CHECKS 8 6 2 CLEANING AND SERVICING 9 ...

Страница 3: ...ion code Rated thermal output in kW Types of fuels that can be used Max operating pressure IMPORTANT This boiler has been designed to heat hot water at a temperature inferior to the boiling temperature at atmospheric pressure and must be connected to a heating plant and or a domestic hot water plant within the limits of its performance and output ...

Страница 4: ...load 92 0 92 0 92 0 92 0 92 0 92 0 Efficiency 30 load 94 0 94 0 94 0 94 0 94 0 94 0 Gas flow rate G20 m h 345 403 472 575 690 805 Combustion and flue data Flue Gas Volume m min 130 5 152 2 178 3 217 4 260 9 304 4 Approx Flue Gas Temp ºC 181 181 182 181 181 181 Comb Chamber Resistance mbar 13 5 18 0 11 7 14 0 12 0 14 0 Water system Hydraulic Resistance 11k mbar 64 2 86 9 120 1 73 8 105 9 144 0 Hydr...

Страница 5: ... safety pressure switch not supplied N1 Flow N2 Return N3 Fitting for instruments N4 System filling drainage N5 Connections for safety valves N6 Bulb wells N8 Inspection well N11 Fitting for level minimum probe SCP PLUS 3000 7000 NOTE drawing legend and data refer to standard models For specific models please refer to the provided accessory drawing ...

Страница 6: ...te the second flame of the two stage burner The safety thermostat locks the burner at a fixed temperature value and sends out an alarm signal Restarting occurs only after the cause of the alarm has been removed and the system has be reset by operating the reset button on the switchboard 3 2 PRESSURE GAUGE The pressure gauge is Bourdon type consisting of a flat elliptical section metal tube bent to...

Страница 7: ...Check that the boiler is fired by the correct type of fuel d Check that the fuel supply pressure is within the values specified on the burner rating plate e Check that the fuel supply system is sized for the maximum flow rate necessary for the boiler and that it is provided with all control and safety devices provided for by the regulations referred to above f Check that the boiler room vents are ...

Страница 8: ...evel is to eliminate areas that overheat Scale creates an insulating layer which reduces the thermal transfer of the generator affecting system efficiency This means that the heat produced by burning the fuel is not fully exploited and is lost to the flue Scale diagram Key fuel not used mm mm of scale Corrosion on the water side Corrosion of the metal surfaces of the boiler on the water side is du...

Страница 9: ...rature CO Gas 10 190 C 0 20 ppm Gas oil 13 195 C 10 80 ppm Heavy oil 13 5 200 C 50 150 ppm A diagram is provided in which the system efficiency is obtained according to the flue gas temperature the ambient temperature and the percentage of carbon dioxide CO2 Dispersions through the boiler casings are not considered Example Fuel used GAS OIL CO2 13 Ambient temperature 20 C Efficiency 91 4 Key Tf Fl...

Страница 10: ... box while the burner is working Always wait few minutes after the burned has been switched off until the insulating parts are cooler 6 2 CLEANING AND SERVICING Close fuel supply and disconnect the electrical mains before starting any cleaning and servicing operations As economic running depends on cleaning of the exchange surfaces and regulation of the burner the following operations should be pe...

Страница 11: ...10 ...

Страница 12: ...t Street Halifax HX1 4DB Tel 01422 355651 Fax 01422 359636 The data reported are indicative only and are not binding Our company reserves the right to introduce alterations at any time as it deems fit and proper for the development of the product ...