Pressurisation values should be included in the range given in the table of technical specifications.

 

 
 

WARNING 

The differential temperature between boiler flow and return must not exceed 25°C in order to prevent 
thermal  shock  to  the  boiler  structures.  The  temperature  of  the  return  water  must  be  above  55°C  in 
order to protect the boiler from corrosion due to condensation of the flue gases on cold surfaces; for 
this purpose it is useful to install a 3 or 4-way mixing valve. The guarantee does not cover damages 
caused by condensate. 
A  recirculation  pump  (anticondensate  pump)  must  be  installed  to  mix  the  cold  returns.  This  pump 
should have a minimum flow rate equal to approximately 5 m

3

/h or equal to 1/3 or 1/4 of the heating 

system pump flow rate. 
 

 
 

It is necessary to keep the burner switch always switched on in order to  maintain water temperature equal 
approximately to the value set through the thermostat.  
 

If the flue gas seal is poor in the front part of the boiler (manhole and burner plate) or the back part (smoke 
box), the closing tie rods of the individual parts must be adjusted; if this is not sufficient, the seals must be 
replaced.  

 

 

CAUTION 

Do not open the manhole and do not remove the smoke box while the burner is working. Always wait 
few minutes after the burned has been switched off until the insulating parts are cooler

 

 
 
 

6.2  CLEANING AND SERVICING 

 
Close fuel supply and disconnect the electrical mains before starting any cleaning and servicing operations. 
 
As  economic  running  depends  on  cleaning  of  the  exchange  surfaces  and  regulation  of  the  burner,  the 
following operations should be performed: 

Clean  the  tube  bundle  and  turbolators  with  the  appropriate  tube-brush  every  month  for  heavy  oil-fired 
boilers,  every  three  months  for  gas  oil-fired  boilers  and  once  a  year  for  gas-fired  boilers.  Cleaning 
schedule depends on plant features. 

Quick cleaning can be performed by opening the front manhole only, taking the turnolators out and cleaning 
the  tubes  with  a  tube-brush.  For  more  thorough  cleaning,  the  smokebox  must  be  removed  to  eliminated 
carbon deposits from the rear side. 

Have the burner calibration checked by professionally qualified personnel; 

Have  the  water  circulating  in  the  system  analysed  and  provide  for  adequate  treatment  to  avoid  the 
formation of scale which initially reduces the efficiency of the boiler and in the long term will permanently 
damage it, making it unserviceable; 

Check  that  the  refractory  castings  in  contact  with  the  flue  gases  are  in  perfect  condition  and  if  not, 
replace them; 

Periodically check the efficiency of the system regulation and safety instruments. 

Содержание SCP PLUS 3000

Страница 1: ...TECHNICAL MANUAL The above picture is only for reference SCP PLUS THREE PASS WET BACK HOT WATER BOILER ...

Страница 2: ...ions 3 2 2 Drawing 4 3 ACCESSORIES 5 3 1 THERMOSTATS 5 3 2 MANOMETER 5 3 3 THERMOMETER 5 4 INSTALLATION 6 4 1 BURNER 6 5 STARTING 7 5 1 PRELIMINARY CHECKS 7 5 2 WATER TREATMENT 7 5 3 FILLING THE SYSTEM 7 6 OPERATION 8 6 1 OPERATION CHECKS 8 6 2 CLEANING AND SERVICING 9 ...

Страница 3: ...ion code Rated thermal output in kW Types of fuels that can be used Max operating pressure IMPORTANT This boiler has been designed to heat hot water at a temperature inferior to the boiling temperature at atmospheric pressure and must be connected to a heating plant and or a domestic hot water plant within the limits of its performance and output ...

Страница 4: ...load 92 0 92 0 92 0 92 0 92 0 92 0 Efficiency 30 load 94 0 94 0 94 0 94 0 94 0 94 0 Gas flow rate G20 m h 345 403 472 575 690 805 Combustion and flue data Flue Gas Volume m min 130 5 152 2 178 3 217 4 260 9 304 4 Approx Flue Gas Temp ºC 181 181 182 181 181 181 Comb Chamber Resistance mbar 13 5 18 0 11 7 14 0 12 0 14 0 Water system Hydraulic Resistance 11k mbar 64 2 86 9 120 1 73 8 105 9 144 0 Hydr...

Страница 5: ... safety pressure switch not supplied N1 Flow N2 Return N3 Fitting for instruments N4 System filling drainage N5 Connections for safety valves N6 Bulb wells N8 Inspection well N11 Fitting for level minimum probe SCP PLUS 3000 7000 NOTE drawing legend and data refer to standard models For specific models please refer to the provided accessory drawing ...

Страница 6: ...te the second flame of the two stage burner The safety thermostat locks the burner at a fixed temperature value and sends out an alarm signal Restarting occurs only after the cause of the alarm has been removed and the system has be reset by operating the reset button on the switchboard 3 2 PRESSURE GAUGE The pressure gauge is Bourdon type consisting of a flat elliptical section metal tube bent to...

Страница 7: ...Check that the boiler is fired by the correct type of fuel d Check that the fuel supply pressure is within the values specified on the burner rating plate e Check that the fuel supply system is sized for the maximum flow rate necessary for the boiler and that it is provided with all control and safety devices provided for by the regulations referred to above f Check that the boiler room vents are ...

Страница 8: ...evel is to eliminate areas that overheat Scale creates an insulating layer which reduces the thermal transfer of the generator affecting system efficiency This means that the heat produced by burning the fuel is not fully exploited and is lost to the flue Scale diagram Key fuel not used mm mm of scale Corrosion on the water side Corrosion of the metal surfaces of the boiler on the water side is du...

Страница 9: ...rature CO Gas 10 190 C 0 20 ppm Gas oil 13 195 C 10 80 ppm Heavy oil 13 5 200 C 50 150 ppm A diagram is provided in which the system efficiency is obtained according to the flue gas temperature the ambient temperature and the percentage of carbon dioxide CO2 Dispersions through the boiler casings are not considered Example Fuel used GAS OIL CO2 13 Ambient temperature 20 C Efficiency 91 4 Key Tf Fl...

Страница 10: ... box while the burner is working Always wait few minutes after the burned has been switched off until the insulating parts are cooler 6 2 CLEANING AND SERVICING Close fuel supply and disconnect the electrical mains before starting any cleaning and servicing operations As economic running depends on cleaning of the exchange surfaces and regulation of the burner the following operations should be pe...

Страница 11: ...10 ...

Страница 12: ...t Street Halifax HX1 4DB Tel 01422 355651 Fax 01422 359636 The data reported are indicative only and are not binding Our company reserves the right to introduce alterations at any time as it deems fit and proper for the development of the product ...

Отзывы: