17
3-4. LCD Display Wordings Index
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
ON
ON
OK
OK
EP
EPO
AO
Active open
AC
Active close
TP
Temperature
CH
Charger
RAC
Rack display
TOE
Tower display
SF
Site Fault
EE
EEPROM error
BR
Battery Replacement
3-5. UPS Setting
Parameter 3
Parameter 1
Parameter 2
There are two parameters to set up the
UPS.
Parameter 1: It’s f
or program
alternatives. Refer to below table for
details.
Parameter 2: It’s setting options or
values for each program.
⚫
01: Output voltage setting
Interface
Setting
For 208/220/230/240 VAC models, you may choose the
following output voltage:
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
For 110/115/120/127 VAC models, you may choose the
following output voltage:
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac (Default)
127: presents output voltage is 127Vac