18
Standby mode
UPS is powered off without output power,
but the battery still can be charged.
Fault mode
The UPS is in fault mode when no output
power is supplied from the UPS and the
fault icon flashes on the LCD display,
although the information of UPS can be
displayed in the screen.
3-7. Faults Reference Code
Fault event
Fault code Icon Fault event
Fault code Icon
Bus start fail
01
x
Inverter voltage Low
13
x
Bus over
02
x
Inverter output short
14
Bus under
03
x
Battery voltage too high 27
Bus unbalance
04
x
Battery voltage too low
28
Bus short circuited
05
x
Over temperature
41
x
Inverter soft start fail
11
x
Over load
43
Inverter voltage high
12
x
3-8. Warning indicator
Warning Icon
(flashing)
Alarm
Low Battery
Sounding every second
Overload
Sounding twice every second
Battery is not connected
Sounding every second
Over Charge
Sounding every second
Site Fault
Sounding every second
EPO enable
Sounding every second
Over temperature
Sounding every second
Charger failure
Sounding every second
Battery fault
Sounding every second
Out of bypass voltage range
Sounding every second
Bypass frequency unstable
Sounding every second
EEPROM error
Sounding every second