6. Menu 

SETPOINTS

 

 

VFR Voltage Frequency Relay 

 

 

6.2 

 

Instruction Manual: VFR GBM 06/10/2021

 

System Setup 

df/dt Cycles 

Value 

(*) 

RANGE: 4; 5; 6 
STEPS: 1 
Specify the number of cycles for the frequency and df/dt calculation 
 

 

 

System Setup 

df/dt Dropout 

Value 

80% 

(*) 

RANGE: 50 

 90 

STEPS: 1 
Select  the  percentage  value  of  the  setpoint  df/dt,  below  whose  level  the  df/dt 
protection  function  restarts  the  counter  accumulation  time.  See  [

6.5  Setpoints: 

FREQUENCY PROTECTION: df/dt section

]. 

If  the  counter  accumulation  time  restarts,  the  failure  condition  will  cause  the 
intervention of the protection only after the selected delay time. See [

6.5 Setpoints: 

FREQUENCY PROTECTION: df/dt Delay]

 

 

 

System Setup 

Command 

Value 

RS485+BLE 

 

RANGE: Local; RS485+BLE; BLE; RS485 
Choose the enabled command source. 
The local HMI always remains enabled. 

 

 

System Setup 

Out of Service Relay 

Value 

None 

 

RANGE: None; Aux8 
Enable or disable the Out of Service function on AUX8. 
If enabled, the AUX8 output relay will be forced as latched and energized; it’s 
state will change only in case of internal fault, power supply loss. 
If enabled, do not associate the AUX8 in an of the protection functions, a 
discrepancy condition will occur.

 

 

 

6.3  Setpoints: DATE & TIME 

Date & Time 

2018. Jan. 9 

16:54:02:00 

 

Press 

ENTER

 to modify.

 

 

 

Date & Time 

2018. Jan. 9 
16:54:02:00  

Enter Password 

- - - - 

 

Insert the First-Level password (PSW1) to set or modify Date and Time. 

To store new Date and Time: 
1. 

Insert the correct password, if required, using 

▲ and ▼ 

2. 

If the password is correct, the year will blink. 

 

 

Date & Time 

2018. Jan. 9 
16:54:02:00 

Value 
 

2018. Jan. 9 

 

 

16:54:02:00 

 

3. 

Select the year using 

▲ and ▼ and press 

ENTER

4. 

Repeat steps 2 and 3 for month, day, hour, minutes, and seconds. 

5. 

Press 

ENTER

 to store the new date and time. 

Note: press 

ENTER

, the decimals of the seconds will begin from zero (0). 

 

 
 
 
 
 
 
 

Содержание VFR-1001

Страница 1: ...O R I O N I T A L I A I N S T R U C T I O N M A N U A L VFR Voltage Frequency Relay Firmware version 1 29 Via G Orsi 35 29122 Piacenza PC Italia Phone 39 0523 591161 www orionitalia com...

Страница 2: ......

Страница 3: ...d in the Chapter GENERAL INFORMATION High voltage live parts disconnect the unit before carrying out any insulation tests on the installation Do not carry out any installation maintenance operations r...

Страница 4: ...RELAY STATUS 4 1 4 1 RELAY STATUS 4 1 5 Menu ACTUAL VALUES 5 1 5 1 Actual values LINE VOLTAGES 5 1 5 2 Actual values PHASE VOLTAGES 5 1 5 3 Actual values PHASE SEQUENCE 5 1 5 4 Actual values VOLTAGE A...

Страница 5: ...l input functions o Remote TRIP o Remote RESET 1 5 APPLICABILITY Systems Wye or Delta three phase Frequency 60 Hz Voltage up to 277 480Vac direct measure or up to 65kV with external VT 1 6 COMMUNICATI...

Страница 6: ...ps 1 Delay time 0 1s 600s Steps 0 01s from 0 1s to 1s 0 1s from 1s to 10s 1s from 10s to 600s Phases Any one any two all three programmable Minimum Operation level 0 50 of Vn Accuracy See Voltage Inpu...

Страница 7: ...RDS Low voltage directive IEC 60255 27 IEC 60255 5 EMC directive IEC 60255 26 FIRMWARE UPGRADE via RS 485 Serial Port Depending on VFR version Depending on Voltage connection type 1 10 ORDER CODE Mete...

Страница 8: ......

Страница 9: ...nd inform ORION ITALIA of any damage If reshipment is required the original container and packing should be used 2 3 MOUNTING The mounting should be carried out as follows 1 Install the relay in a pla...

Страница 10: ...efore carrying out the installation of the unit it is necessary to read and understand the indications provided by the Constructor All the installation operations must be carried out by qualified pers...

Страница 11: ...S Vn 277 480Vac AUX8 AUX7 AUX6 A B C voltage transformers connection DELTA a 32 b 33 c 34 LOW VOLTAGE THREE PHASE SYSTEM B A AUXILIARY POWER 80 115 230 300 Vac Vdc 24Vdc 48Vdc n u N 51 52 53 54 55 56...

Страница 12: ...wire is BELDEN 9841 AWG 24 which is shielded and with a characteristic impedance of 120 Ground the shield only at one point Figure 2 5 For the RS 485 port a maximum of 35 relays can be daisy chained t...

Страница 13: ...em and functions EVENTS visualize the last events stored and possibly clear them all RESET reset the VFR Below you can find the representation of the complete structure consisting of the Relay Main Me...

Страница 14: ...rough some of the options in the Calibration Mode menu APPENDIX A How to Set or Modify a First Level password DEFAULT FIRST LEVEL PASSWORD 1111 Setpoint Access ORION ITALIA VFR F V X XX To modify the...

Страница 15: ...ated Secondary 100 3 V VT Rated Primary 1 0 3 kV To modify the VT Rated Secondary value press ENTER The VFR will ask the user to insert a password System Setup VT Rated Secondary 100 3 V Enter Passwor...

Страница 16: ...XT This figure on the left represents the relay display This screen only appears if the statement on the left is applied Main Menu option SECTION If x x Symbol Select among the elements on the list Se...

Страница 17: ...ive Protection Check Events This section provides information on the Relay Status For example the display could indicate protection interventions internal faults and or setpoint discrepancies In the p...

Страница 18: ......

Страница 19: ...e in case of phase loss or insufficient voltage ABC Direct sequence ACB Inverse sequence 5 4 Actual values VOLTAGE AVG UNB THD Voltage Avg Unb THD Voltage Avg 0 00 V Voltage Unb 0 0 THD 0 0 Average of...

Страница 20: ...ARMONICS View the 11 Harmonics related to the phase voltage or line voltage if Delta is selected in 6 2 Setpoints SYSTEM SETUP VT Connection Vcn Harmonics Vcn2nd 0 0 Vcn11th 0 0 Vcn Harmonics percenta...

Страница 21: ...and or modify the First Level password PSW1 See Main Menu Autoscroll and Pop Up Functions 3 5 PASSWORD MANAGEMENT 6 2 Setpoints SYSTEM SETUP This section indicates the parameters for system setup Syst...

Страница 22: ...ns enabled System Setup Out of Service Relay Value None RANGE None Aux8 Enable or disable the Out of Service function on AUX8 If enabled the AUX8 output relay will be forced as latched and energized i...

Страница 23: ...button 6 4 Setpoints VOLTAGE PROTECT If UnderVoltage1 Relay NONE Voltage Protect UnderVoltage1 Delay Value 0 50 s RANGE 0 10 600 STEPS 0 01 0 1 1 Enter the UnderVoltage1 protection intervention delay...

Страница 24: ...lected the protection Phase Reversal will be disabled The protection will activate when the relay detects the voltage sequence as inverse 6 5 Setpoints FREQUENCY PROTECTION Frequency Protect UnderFreq...

Страница 25: ...nts FREQUENCY PROT If UnderFrequency2 Relay NONE Frequency Protect UnderFrequency3 Relay Value RANGE NONE ANY COMBINATION OF AUX1 AUX2 AUX3 AUX4 AUX5 AUX6 AUX7 OR AUX8 When NONE is selected the protec...

Страница 26: ...RANGE NONE ANY COMBINATION OF AUX1 AUX2 AUX3 AUX4 AUX5 AUX6 AUX7 OR AUX8 When NONE is selected the protection UnderFrequency5 will be disabled Frequency Protect UnderFrequency5 Level Value 59 0 Hz RA...

Страница 27: ...Frequency Protect UnderFrequency7 Level Value 59 0 Hz RANGE 47 0 59 9 STEPS 0 1 Enter the UnderFrequency7 intervention level The protection will activate when the frequency drops below this value for...

Страница 28: ...ctivate when the frequency exceeds this level for a period OverFrequency2 Delay value 6 5 Setpoints FREQUENCY PROT If OverFrequency2 Relay NONE Frequency Protect OverFrequency2 Reset Value 60 5 Hz RAN...

Страница 29: ...of change of frequency exceeds this level for a period df dt 1 Delay value 6 5 Setpoints FREQUENCY PROT If df dt 1 Relay NONE Frequency Protect df dt 1 Startup Value 59 8 Hz RANGE 48 0 60 0 STEPS 0 1...

Страница 30: ...has intervened the Aux1 output relay will function in Operating State When the fault condition ceases it is necessary to manually RESET Output Relay Aux2 Output Relay Value LATCHED RANGE LATCHED LATCH...

Страница 31: ...essors as specified on Figure 2 4 and its note 6 7 Setpoints DIGITAL INPUT Digital Input Digital Input 1 Function NONE RANGE NONE Rem Trip Rem Reset Digital Input D I 1 Remote Trip Relays Value RANGE...

Страница 32: ...cy Protect Events Value ENABLED RANGE ENABLED DISABLED 6 9 Setpoints MODBUS COMMUNICATION This section contains the settings that allow the VFR communication with other devices Modbus Comm Modbus Addr...

Страница 33: ...nd press ENTER Insert the Second Level password PSW2 to authorize the upgrade BLE Update only for manufacturer use Firmware Update Ready to be Updated The VFR is waiting to receive the update Once the...

Страница 34: ...ing the test the chosen relay s will remain energized for five 5 seconds and the navigation will be disabled throughout this time Calibration Mode Device ID Value 63aDedRt2f4 A code like the example o...

Страница 35: ...Vcn 0 00 V Phase Voltages will be displayed if 6 2 Setpoints SYSTEM SETUP VT Connection Wye Otherwise line Voltages will be displayed if 6 2 Setpoints SYSTEM SETUP VT Connection Delta Event X Frequen...

Страница 36: ......

Страница 37: ...oes not cancel any acquired data Events instead it resets a fault condition including Trip if it is no longer present and or eliminates the notification of a previously stored fault condition Reset Re...

Страница 38: ......

Страница 39: ...ON 0 3s OFF Check that all setpoints are not out of range with respect to the memory map o Check that UnderVoltage Reset is not UnderVoltage Level o Check that OverVoltage Reset is not OverVoltage Lev...

Страница 40: ......

Страница 41: ...talia Notes Reset Relay X X X X Clear Events X X X Factory Default X K Calibration K TV Events will remain the same Auto Calibration X K Calibration relay X K Calibration TV X X Upgrade Firmware X X U...

Страница 42: ......

Страница 43: ...hreshold reached UnderFrequency 4 Active protection for underfrequency4 threshold reached UnderFrequency 5 Active protection for underfrequency5 threshold reached UnderFrequency 6 Active protection fo...

Страница 44: ......

Страница 45: ...rgized to de energized Aux8 De Energized The output Aux8 status was changed from energized to de energized Aux1 Energized The output Aux1 status was changed from de energized to energized Aux2 Energiz...

Страница 46: ...values set by the user in the Setpoint section generated a discrepancy e g verify the values of Threshold and Reset that could generate a protection malfunction Reset Level Threshold Level in Overvol...

Страница 47: ......

Страница 48: ...ORION ITALIA srl Via G Orsi 35 29122 Piacenza PC Italia Phone 39 0523 591161 www orionitalia com...

Отзывы: