6. Menu
SETPOINTS
IPR96D Ground Protection Relay
6.1
Instruction Manual: IPR96D GBM 24/11/2020
6.
Menu SETPOINTS
Before carrying out the programming of the unit, it is necessary to read and understand the indications provided by the Constructor.
All the programming must be carried out by qualified personnel with adequate knowledge of the operation of the unit and of the
content of this manual.
6.1 Setpoints: SETPOINT ACCESS
Setpoint Access
ORION ITALIA
IPR96DX F.V. X.XX
IPR96D model and the firmware version.
Press
ENTER
, insert and/or modify the First-Level password (PSW1).
See [Main Menu, Autoscroll and Pop-Up Functions: 3.5 PASSWORD
MANAGEMENT].
6.2 Setpoints: SYSTEM SETUP
This section indicates the parameters for system setup.
System Setup
System
Frequency
Value
50 Hz
RANGE: 50; 60 Hz
Enter the nominal power system frequency. This value will set the optimal digital
sampling rate.
System Setup
Ground CT Primary
Value
50 A
RANGE: 5
5000
STEPS: 5
Enter the primary current rating of the ground CT being used.
System Setup
Command
Value
RS485
RANGE: RS485, LOCAL, RS485+BLE, BLE
Choose the enabled command source and with this, disable all commands sent
by any other available communication methods or options.
The local HMI always remains enabled.
System Setup
Out of Service Relay
Value
None
RANGE: None, Aux2
Select AUX2 to perform the SERVICE function
Once the power is applied, the relay will make AUX2 react and the related contact
will be opened. In case of fault of the relay (STATUS
led “On”) or of loss of power
supply, AUX2 will pass to safe state position and exchange its contacts.
If the fault disappears, the IPR96D will get back to normal operation; the Out of
Service relay will remain latched in safe state position (local HMI reset required).
See Wiring Diagram [Figure 2.3].
Setpoints
Setpoint Access
System Setup
Date & Time
Ground Protect.
Digital Input
Output Relay
Event Recorder
Modbus Comm.
Bluetooth
Firmware Update
Calibration Mode
Содержание IPR96D
Страница 2: ......
Страница 14: ......
Страница 16: ......
Страница 18: ......
Страница 28: ......
Страница 30: ......
Страница 32: ......
Страница 34: ......
Страница 36: ......
Страница 38: ......
Страница 39: ......
Страница 40: ...ORION ITALIA srl Via G Orsi 35 29122 Piacenza PC Italia Phone 39 0523 591161 www orionitalia com ...