POSITIONING THE SMOKE ALARM
For the smoke alarm to give an early warning, it needs to be installed where the fire occurs. Housegard
therefore recommends that you install a smoke alarm in every room and on all floors.
»
Install a smoke alarm in all separate bedrooms and in rooms commonly occupied.
»
In homes with several storeys, a smoke alarm should be installed at the top of every staircase between
each storey.
»
In the basement, a smoke alarm should be installed on the ceiling at the foot of the stairs.
»
In bedrooms where people sleep with closed doors, there should always be a smoke alarm fitted in the
bedroom.
»
Install a smoke alarm in every room where there is a potential risk of fire.
»
Install a smoke alarm at each end of corridors, if they are longer than 9 metres.
»
Install the smoke alarm in the middle of the ceiling. If this is not possible, install the smoke alarm on
the wall at least 0.5 m from any corner and at least 10–15 cm from the ceiling. (Wall-mounting is not
recommended).
KEY:
Minimal protection
Recommended/more substantial protection
Smoke alarms with a pause function are recommended
SMOKE ALARMS SHOULD NOT BE PLACED
IN THE FOLLOWING LOCATIONS
»
In the kitchen, near the cooker, where smoke from cooking could cause false alarms.
»
In areas of high air humidity, such as bathrooms or near dishwashers or washing machines, where
steam and moisture could cause false alarms.
»
Near fans and ventilation ducts, where air flows may prevent smoke from reaching the smoke alarm.
»
Near light sources and electrical equipment that emit an electromagnetic field.
»
Near a fireplace or stove with an open fire.
»
At the top of a V-shaped ceiling, where air pockets could stop the smoke from reaching the smoke
alarm.
»
In a garage, where exhaust fumes could cause false alarms.
»
In dusty and dirty areas, where the dust and dirt could damage the smoke alarm.
»
In rooms where the temperature may fall below 5 °C or rise above 45 °C, or in rooms with large tem-
perature variations.
WARNING: Incorrect positioning may lead to reduced reliability and false alarms.