6.
If interconnection is desired, connect yellow wire from connector to interconnect wire between CO alarms. See section
INTERCONNECTING CO ALARMS.
NOTE:
If this will be used as a single-station CO alarm, cover yellow wire with electrical tape and tuck it into junction box.
7.
Lift open battery pocket door.
8.
Connect new 9-volt battery to battery connector inside battery pocket. Be sure battery is securely connected. CO alarm
may beep briefly when battery is installed.
9.
Close battery pocket door, snapping it into place.
10.
Attach connector plug to pins on back of CO alarm. Plug will only fit one way and will snap into place.
11.
Gently tug connector to be sure it is attached securely.
12.
Position CO alarm to mounting plate and turn clockwise to lock into place. To engage tamper-resist feature, insert pin into
notch on edge of CO alarm after alarm is properly positioned in base.
NOTE:
CO alarm will not mount to plate if battery is not installed.
13.
Turn on power at main fuse box or circuit breaker.
14.
Push test button to test CO alarm. See
TESTING THE CO ALARM
.
INTERCONNECTING SMOKE ALARMS
For interconnecting line, only use #14-#18 AWG minimum solid or stranded wire. When being
interconnected, maximum wire length between any two alarms is 1500 feet for #18 AWG or
4000 feet for #14 AWG (20 OHMS loop resistance). This CO alarm can be interconnected with
as many as 40 other DC or AC ORIENTALERT s CO alarms and/or smoke/heat alarms. Do not
connect to any other type or model CO alarms except the ones we specify. And this CO alarm is
powered by 220-240V AC 50Hz and with 9V DC Battery back-up.
OPERATING YOUR CO ALARM
Normal Operation
When the CO alarm is under normal working operation in the clean air, the green LED will be on when mains power is
correctly connected and is also an indication that your alarm is in normal function. The green LED will flash every one minute
when mains power is cut off.
Alarm Condition
When the unit detects dangerous levels of CO, Red LED flashes rapidly and alarm sounds loudly (repeating 4 beeps,
pause).This will continue as long as there is a dangerous level of CO present. Should the CO levels return to normal, the unit
will stop beeping.
CO
LEVEL
(PPM)
RESPONSE
TIME
(MIN)