background image

18

 

Explanation Control display

 

For a more detailed description of how to operate the controller in the WTU, 
download the "Corrigo User Manual.pdf" at www.orcon.nl/wtu-etool.

 

 

Running through menus

 

The start screen is the beginning of the menu structure. You can use the up and 
down arrows to scroll through the menu options. Sometimes a menu item has a 
submenu. This is indicated by an arrow on the right of the screen. Clicking on the 
button with the right arrow opens the submenu. (You must have the appropriate 
rights to do this). By clicking on the left arrow, one returns to the previous menu 
level.

 

Posit

ion

Statement

1

Alarm button: gives access to the list of alarm messages

2

Alarm LED: indicates an alarm message by flashing red.

3

Input LED: indicates by flashing yellow that parameters can be set or changed.

4

OK button: Press this button to change or set parameters where possible. Also used to 

switch between parameters to be set in a dialogue box.

5

Cancel button: Used to cancel a change and return to the initial setting.

6

Left/Right  &  Up/Down  Arrows:  used  to  move  up,  down,  left  and  right  through the  menu 

structure. The up/down arrows are also used to increase/decrease values when setting or 

changing parameters.

1

2

6

3

4

5

Содержание WTU-1000-EC-E

Страница 1: ...Installation and user manual WTU EC E IE TA Heat recovery unit with EC motors Regin controller and external display...

Страница 2: ...2...

Страница 3: ...series 7 Installation 8 Connecting accessories 9 Display Installation of the operating display Explanation Control display Running through menus Start settings Changing access rights Changing operatin...

Страница 4: ...of power Install the WTU in an environment where the temperature is between 10 and 40 degrees Celsius and the relative humidity is less than 60 If condensation occurs preheat the fresh air with a CBR...

Страница 5: ...d the duct system is correctly connected to the WTU The diameter of the air ducts must be equal to or larger than the connection flanges of the WTU The air filters are clean and the air flow is not bl...

Страница 6: ...6 carried out...

Страница 7: ...73 76 75 75 Nominal flow rate 100Pa m3 h 200 440 800 1000 1200 1700 Maximum flow rate 0Pa m3 h 374 760 921 1425 2280 2780 Electrical input power at nominal air volume W 44 97 244 256 351 462 SFPint 1...

Страница 8: ...E 922 1130 344 200 499 700 46 WTU 800 EC E 1014 1214 410 250 589 760 51 WTU 1000 EC E 1294 1606 410 300 719 760 79 WTU 1500 EC E 1128 1807 552 355 623 800 97 WTU 2000 EC E 1428 1807 552 355 921 800 1...

Страница 9: ...ncy 1 82 82 82 Nominal flow rate 100Pa m3 h 500 750 1000 Maximum nominal 0 Pa m3 h 760 869 1288 Electrical input power at nominal air volume W 144 242 277 SFPint 1 W m3 s 7 4 9 6 7 0 Design flow rate...

Страница 10: ...are in millimetres The space needed to carry out maintenance is indicated by size S A B C D E S Weight kg WTU 600 EC TA 934 1325 355 200 499 700 64 WTU 800 EC TA 1024 1387 400 250 589 760 71 WTU 1000...

Страница 11: ...lles as far apart as possible so that the entire room is ventilated Place control valves in the ducts if multiple extraction grilles are installed All electrotechnical operations and connections must...

Страница 12: ...es can be attached to the housing of the WTU by using the using the same screws and the existing screw holes Prepare the threaded endsInstallation of the WTU Hang the WTU with the suspension brackets...

Страница 13: ...e system see diagram below Then fit the condensation drain hose into the hose connection the condensation drain must not be kinked Pour water into the drip tray to create a water trap and also check t...

Страница 14: ...red wire 24V to terminal 5 and connect the black wire GND to terminal 3 AGND of the WTU terminal strip After connecting the CO2 sensor it must be configured in the controller see page21 Connecting MTV...

Страница 15: ...of the controller The temperature sensor supply air temperature sensor connected to AI4 must first be disconnected from AI4 The AGND already connected on the controller should remain the new sensor s...

Страница 16: ...16 Note The connections shown in a box are optional Electrical Connections WTU EC E IE TA...

Страница 17: ...able connected to the Regin controller If required the 10m cable can be replaced by a cable up to 100m long Determine a suitable place for mounting the control panel control panel If necessary drill t...

Страница 18: ...iption 1 Mounting holes 2 Terminal block 3 Connection brown cable 4 Connection yellow cable 5 Connection white cable 6 Connection black cable Control panel dimensions Dimensions in mm A B C D E 115 94...

Страница 19: ...to do this By clicking on the left arrow one returns to the previous menu level Posit ion Statement 1 Alarm button gives access to the list of alarm messages 2 Alarm LED indicates an alarm message by...

Страница 20: ...r temperature see the Return air temp explanation Return air temperature below Measured C This is 21 C as standard log on to service level Desired 21 C code 2222 to change default setting Step 3 Check...

Страница 21: ...ay speed must be ventilated There can be 2 periods per Per 1 00 00 24 00 day Per 2 00 00 00 00 d Set the weekend and holiday schedule with the Half turns periods when the WTU is running at reduced spe...

Страница 22: ...cess rights Changing access rights By default the WTU is operated with the rights of Operator If you want to make some changes you have to log in as Service or Admin To do this go to Access rights Log...

Страница 23: ...0 min run Step7Press the down arrow to set the ppm values 1 2 turn 0ppm 1 1 speed 2000ppm Difference 30ppm Step8Set the rotation speeds for the supply and exhaust fan TV and AV to reduced 15 and norm...

Страница 24: ...connected it must be configured as follows Step1Log in as Admin code 1111 Step2Go to Configuration Inputs Outputs Analogue inputs AI3 Press OK Step3Change not used to CO2 Step4Go back to the Configur...

Страница 25: ...s Analogue outputs Go to AO3 Change not used to Y1 heating Return to the Configuration menu Click on the down arrow and go to the Heating menu Change Not used to Electric Return to the Configuration m...

Страница 26: ...dmin code 1111 Step 2 Go to Configuration Z N ventilation ZNV active No Step 3 Change No to Yes Summer night ventilation will only be activated if the following starting conditions are met Less than 4...

Страница 27: ...rn air temperature is below the set value e g 18 C One of the timer outputs for normal speed external stop or extended running time normal is on If the outside temperature falls below a selected value...

Страница 28: ...ded from www orcon nl wtu etool The following describes how to connect the controller to a laptop and how to change some settings in the controller To program the WTU the laptop must be connected to t...

Страница 29: ...this controller and press Search as shown in Figure 4 Figure 3 First select and then press OK as shown in Figure 5 Press OK as shown in Figure 6 The controller is now connected The status display on t...

Страница 30: ...n synchronise as shown in Figure 7 above The synchronise parameters menu will appear 2 Click on Update Tool to make the changes in the controller 3 Enter the administrator password 1111 to change the...

Страница 31: ...30 Configuring parameters Figure 9 Click on Configuration as shown in Figure 9 The System menu will appear Figure 10...

Страница 32: ...e left side of Figure 10 The Input Output menu will now appear on the right side of the screen 2 By clicking on one of the possible inputs or outputs a drop down menu appears on the far right A choice...

Страница 33: ...on the Figure 11 The Rule functions menu appears on the right hand side of the screen 2 Click on Heater type under Object types a selection menu will appear Choose the desired reheater from this menu...

Страница 34: ...above The synchronise parameters menu will appear 2 Select the changes you want to make from the synchronise parameters menu 3 Click on update controller to make the changes to the controller 4 Now e...

Страница 35: ...k that the fuses are not defective Check the control panel settings times week schedule automatic manual operation etc 2 Reduced airflow Check the settings for the ventilation modes Normal and Reduced...

Страница 36: ...nger Step 2 Replace the filters Step 3 Remove the heat exchanger and clean if necessary with a hoover Supply and return air fans The fans have EC controlled external rotor motors that can be steplessl...

Страница 37: ...observe these maintenance intervals and to follow the maintenance instructions Thorough and regular maintenance is a prerequisite for a valid warranty 1 Or in accordance with local laws and regulation...

Страница 38: ...800 EC E IE 15723080 157230 87 WTU 800 EC TA 15723580 157230 87 WTU 1000 EC E IE 15723100 157231 07 WTU 1000 EC TA 15723600 157231 07 WTU 1500 EC E IE 15723150 157231 57 WTU 2000 EC E IE 15723200 157...

Страница 39: ...nd must be replaced Thanks to a back up capacitor the controller will continue to operate for at least 10 minutes even without supply voltage Please leave battery replacement to qualified service pers...

Страница 40: ...n the making available on the market of electrical equipment Directive 2014 30 EU on electromagnetic compatibility Regulation EU No 1369 2017 on energy labelling Regulation EU No 1253 2014 Directive 2...

Страница 41: ...40 Notes...

Страница 42: ...41 Landjuweel 25 3905 PE Veenendaal PO Box 416 3900 AK Veenendaal t 31 0 318 54 47 00 service orcon nl www orcon nl Misprints and printing errors excepted 17 03 2021 r1 3876v10...

Отзывы: