MNL940-003-000-
9
3.2 WIRING
(continued)
Units supplied with the AC input bypass option should be wired slightly differently so
that neutral is “carried through” to the output but is not shorted to the GND terminal.
This
will place one side of the inverter output at the neutral potential. It should be noted that
this is only recommended to satisfy the NEC requirements. The output of the inverter is
isolated from the DC input and the line.
For units supplied with NEMA 15R type receptacles, simply connect the DC input to
the inverter and plug the load into the receptacles. Connect the chassis of the inverter to
an external earth ground.